Controller self-test
Power monitoring: Alarm 1 is triggered when the 24V DC voltage is below 19.3V (recording internal variables), alarm 2 is triggered when the voltage is below 15.4V (preparing to shut down), and automatic shutdown is triggered when the voltage is below 13.0V.
Temperature monitoring: A warning is triggered when the temperature is between 60 ° C and 70 ° C, a main alarm is triggered when the temperature is above 70 ° C, and the main alarm is released when the temperature drops to 64 ° C and 54 ° C (the warning is retained). When the temperature drops below 54 ° C, it returns to normal.
Interpretation of status indicator lights
|Indicator light | Status | Meaning|
|24V DC | Always on | 24V DC power supply is normal|
|| Off | No power supply or power failure|
|RUN | Always on | Running normally (executing programs, processing I/O, communication, self-test)|
|| Blinking | STOP mode (no program executed, output reset, triggered by emergency stop)|
|| OFF | VNet STOP mode (see ERROR light)|
|ERROR | Always on | Hardware failure (controller, I/O, counter), system software error, watchdog timeout (out of cycle), software restart required|
|| Off | No errors|
|PROGress | Always on | Uploading new controller configuration|
|| Blinking | Upload new operating system to non-volatile ROM|
|FAULT | Always on | Program logic error, configuration failure, operating system damage|
|| Flashing | ROM write error, I/O failure|
|OSL | Blinking | Emergency Operating System Loader Activation|
|BL | Blinking | Boot loader unable to load operating system|
|Ethernet (green/yellow) | Green constant light | Full duplex; Huang Changliang: Connection establishment|
|| Green flashing | Conflict; Yellow flashing: Interface activity|
(6) Technical specifications and certification
Core parameters
Memory: Maximum 250KB user program memory, 250KB application data memory;
Safety performance: minimum watchdog time of 10ms, minimum safety time of 20ms;
Insulation voltage: 50V DC (basic insulation) between I/O and Ethernet, Ethernet and DC power supply;
Protection level: IP20 (controller body), size 257 × 114 × 66mm (width × height × depth), weight 1.2kg.
Safety certifications: UL Listed (USA&Canada), CE (EMC Directive 2004/108/EC), C-Tick (Australia), T Ü V certification (SIL 3/IEC 61508, PLe/ISO 13849-1).
Key considerations and supplementary resources
Compliance verification: Wiring must comply with local electrical regulations (such as NEC, IEC), and safety circuit design must meet corresponding safety level requirements to avoid reducing safety performance due to improper configuration.
EMC protection: Shielded wires are required for analog inputs, high-speed counters, and Ethernet, with both ends of the shielding layer grounded; Install a filter in the power circuit to reduce the impact of electromagnetic interference on safety functions.

Email:wang@kongjiangauto.com