Products Drives Low voltage AC drives Machinery drives
General Information
Global Commercial Alias: ACS850-04-387A-5
Product ID: 3AUA0000089794
ABB Type Designation: ACS850-04-387A-5
Catalog Description: ACS850-04-387A-5 PN:200kW, IN:387A
Ordering
Country of Origin: Finland (FI)
Customs Tariff Number: 85044088
Invoice Description: ACS850-04-387A-5 PN:200kW, IN:387A
Made To Order: Yes
Minimum Order Quantity: 1 piece
Order Multiple: 1 piece
Quote Only: No
Selling Unit of Measure: piece
Stocked At (Warehouses): FIPSEEXPU
US Drive Services
SGRDC002EXPU
CNIAB001EXPU
SGIND002EXPU
AUABB024EXPU
Dimensions
Product Net Height: 1462 mm
Product Net Length: 505 mm
Product Net Weight: 161 kg
Product Net Width: 305 mm
Technical
Enclosure Class: IP00
Frequency (f): 50 ... 60 Hz
Input Voltage (U ): 400 ... 500 V
Mounting Type: Module for cabinet assembly
Number of Phases: 3
Output Current, Heavy-Duty Use: 300 A
Output Current, Light-Overload
Use:
377 A
Products Drives Low voltage AC drives Machinery drives
in
Output Current, Normal Use: 387 A
Output Power, Heavy-Duty Use: 160 kW
Output Power, Light-Overload
Use:
200 kW
Output Power, Normal Use: 200 kW
Additional Information
Product Main Type: ACS850-04-387A-5
Product Name: Frequency Converter
Classifications
ProductSeries: ACS850-04
Removing the cover assembly of the external control unit
The cover assembly needs to be removed before the installation of optional modules
and the connection of control cabling. Follow this procedure to remove the cover
assembly. The numbers refer to the illustrations below.
1. Press the tab slightly with a screwdriver.
2. Slide the lower cover plate slightly downwards and pull it out.
3. Disconnect the panel cable if present.
4. Remove the fastening screw at the top of the cover assembly.
5. Carefully pull the lower part of the base outwards by the two tabs.
6. Refit the cover in reverse order to the above when the control cables have been
connected.
Drive-to-drive link (XD2D)
The drive-to-drive link is a daisy-chained RS-485 transmission line that allows basic
master/follower communication with one master drive and multiple followers.
Termination activation jumper T (see section Jumpers above) next to this terminal
block must be set to the ON position on the drives at the ends of the drive-to-drive
link. On intermediate drives, the jumper must be set to the OFF position.
Shielded twisted-pair cable (~100 ohm, for example PROFIBUS-compatible cable)
must be used for the wiring. For best immunity, high quality cable is recommended.
The cable should be kept as short as possible; the maximum length of the link is
100 meters (328 ft). Unnecessary loops and running the cable near power cables
(such as motor cables) must be avoided. The cable shields must to be grounded to
the control cable clamp plate on the drive as shown on page 102.
The following diagram shows the wiring of the drive-to-drive link.