Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

TEKTRONIX 5A22N Differential Amplifier

来源: | 作者:FAN | 发布时间 :2025-11-18 | 7 次浏览: | Share:


TEKTRONIX 5A22N Differential Amplifier

Operation Instructions (Section 1)

1. Instrument description

Positioning: High gain differential amplifier plug-in unit, used for 5100 series oscilloscopes, can directly couple input to achieve high sensitivity.

Core features:

Bandwidth: Maximum DC to 1MHz, bandwidth can be limited by HF-3dB (high frequency) and LF-3dB (low frequency) switches to improve signal-to-noise ratio;

Deflection coefficient: The knob skirt edge emits light and displays, supporting automatic scaling of 10X encoding probes;

Other: High common mode rejection ratio (CMRR), variable DC offset, suitable for displaying small signals at large DC levels.

2. Panel controls and interfaces (key functions)

Control/Interface Function Description

Display switch plugin working status (only valid for vertical cabin), when turned on, the knob skirt light is on

POSITION adjusts the trajectory position on the screen

HF -3dB/LF -3dB - HF -3dB: 1-3-10 sequence with 7 levels (0.1kHz-1MHz), reducing the upper bandwidth limit and improving signal-to-noise ratio

-LF-3dB: 1-10-100 sequence with 7 levels (DC-10kHz), limited to 2Hz during AC coupling; adjustable DC offset in DC OFFSET level

VOLTS/DIV - Calibration mode: 18 levels 1-2-5 sequence, 10 μ V/Div to 5V/Div (accuracy 2%)

-Variable gear: Non calibrated continuous adjustment, range extended to 12.5V/Div

DC OFFSET (COARSE/FINE) requires LF-3dB to be placed in the DC OFFSET mode to achieve display adjustment of small signals at large DC levels

STEP ATTEN DC BAL balanced input amplifier to reduce trajectory offset during VOLTS/DIV switching

Input coupling button (AC/DC/GND/PRE CHG) - AC: capacitive coupling (blocking DC); DC: direct coupling

-GND: Input ground (disconnect signal); PRE CHG: Press AC+GND to pre charge the coupling capacitor to the signal DC level

+/-Input interface BNC interface,+positive signal deflects upwards, - positive signal deflects downwards; Equipped with a 10X encoded probe ring

3. Basic operation steps

Installation and startup:

Insertion: Align the plug-in guide rail with the 5100 series module compartment (priority vertical compartment: center/left; X-Y operation can be inserted into the horizontal compartment), and the panel should be level with the oscilloscope;

Power on: Adjust the oscilloscope brightness to the lowest level → Power on → Preset time base (2ms/Div) and trigger (automatic trigger).

Initial setup:

Set PLAY to ON,+/- input coupling to DC+GND, POSITION and STEP ATTEN BAL to median, HF/LF-3dB to full bandwidth, VOLTS/DIV to 50mV/Div, and variable gear to CAL (clockwise to bottom).

Preheating and trajectory adjustment:

Preheating: Short term DC measurement for 5 minutes, long-term DC measurement for 15 minutes;

Adjust the brightness to normal, and the trajectory should be near the center of the scale. Use POSITION to move the trajectory to 2 grids below the centerline.

Example of signal measurement:

Single ended DC coupling:+input connected to 400mV peak to peak calibration signal → release+GND → display 4 grid square waves (bottom alignment step 3 reference line);

Single ended AC coupling: POSITION moves the trajectory from bottom to center → presses AC → the trajectory shifts downward by about 2 grids (to the average value);

Differential AC coupling:+/- input connected to dual input cable → - input set to AC → display straight line (common mode signal suppressed).

4. Key precautions

Input protection: The maximum voltage of the input FET gate is ± 12V (diode clamp), and the input fuse will melt when the signal source current exceeds 1/16A;

Pre charge (PRE CHG): When measuring AC signals containing DC components, first connect the AC+GND signal → wait for 1 second for charging → release GND to avoid damaging the signal source due to coupling capacitor charging current;

High impedance input: When VOLTS/DIV is in the 50mV-10 μ V range, removing the circuit board jumper can disconnect the 1M Ω ground resistor, achieving high impedance input (requiring the signal source to provide a DC path for FET gate current).

5. Electrical characteristics (core parameters)

Specific parameters of characteristics

Bandwidth (-3dB) - DC coupling: DC to ≥ 1MHz (independent of deflection coefficient)

-AC coupling: 2Hz to ≥ 1MHz

Common mode rejection ratio (CMRR) - DC coupling: 10 μ V/Div-0.1mV/Div range ≥ 100dB (DC-30kHz, 20Vp-p sine wave); 0.1V/Div-5V/Div mode ≥ 50dB (100Vp-p sine wave)

-AC coupling: ≥ 80dB at 5kHz and above, reduced to 50dB at 10Hz

DC offset range -10 μ V/Div-50mV/Div range: ± 0.5V

-100mV/Div-5V/Div mode: ± 50V

Input RC 1M Ω (± 0.1%) in parallel at approximately 47pF

Maximum input voltage DC coupling: 10V (DC+peak AC) (10 μ V-50mV range); 350V (DC+peak AC) (100mV-5V range)

-AC coupling: 350VDC+10V peak AC (10 μ V-50mV range, pre charged); 350V (DC+peak AC) (100mV-5V range)

Noise at full bandwidth (DC-1MHz) ≤ 20 μ V (25 Ω source resistance, tangent measurement)

image.png

Working principle (Section 2)

1. Overall block diagram path

Signal → Input coupling (AC/DC/GND) → Input attenuator (1X/100X, frequency compensation) → Pre amplifier (differential structure, floating ground power supply) → Low frequency limiting circuit (LF-3dB switching) → Gain switching stage (VOLTS/DIV control) → Offset generator (DC OFFSET) → Isolation stage (emitter follower) → Output amplifier (push-pull structure, POSITION adjustment) → Trigger signal amplifier (output to time base plugin, 0.25V/display panel).

2. Analysis of core circuit modules

Input attenuator:

Attenuation ratio: VOLTS/DIV 0.1V-5V range with 100X attenuation, 10 μ V-50mV range with 1X attenuation;

Features: Frequency compensation, maintaining 1M Ω//47pF input characteristics, balancing common mode signals through R132 (Atten DC CMR).

Pre amplifier:

Structure: Two identical operational amplifiers form a differential circuit (Q150A/B, Q190A/B, Q200A/B);

Floating power supply: composed of Q170/Q176 (constant current source) and VR173/175/176 (Zener transistor), it maintains the stability of the amplification device operating point and improves CMRR as the common mode signal changes;

Gate current compensation: Regulate R121/R127 to offset FET gate leakage current (≤ 100pA) and avoid high-sensitivity offset (such as 100pA × 1M Ω=100 μ V offset in 10 μ V/Div mode, which may cause trajectory offset screen).

DC offset generator:

Structure: Q240/Q244/Q246A/B form a voltage comparator, with VR251 (transistor) providing a reference voltage;

Function: By adjusting COARSE (R260) and FINE (R268), offset current is generated to cancel the DC component of the input signal, with a maximum cancellation of 0.5V.

Output amplifier:

Structure: Push pull amplifiers Q348/Q352, R351 (GAIN) adjust the total gain to match the requirements of the host;

Position adjustment: Q360/Q362 (positioning current drive), R360 (POSITION) changes the current to adjust the static position of the CRT beam.


Calibration (Section 3)

1. Calibration prerequisites and preparations

Applicable scenarios: After instrument maintenance, long-term use (component aging) leads to accuracy deviation;

Environmental requirements: Temperature of 20-30 ℃, preheating for 20 minutes;

Equipment disassembly: Remove the left protective cover of 5A22N and the left panel of 5100 series oscilloscope (or use plug-in extender 067-0645-00);

Initial settings: Set the 5A22N control to POSITION median LF-3dB=1Hz、HF-3dB=1MHz、VOLTS/DIV=50mV、 Variable gear=CAL,+/- input=DC+GND, STEP ATTEN BAL median; The 5B10N time base is set to automatic triggering,+slope, and AC coupling.

2. Required testing equipment (including accessories)

Specific requirements/model examples for equipment types

Oscilloscope System 5100 Series (including 5B10N Time Base Plugin)

Constant amplitude sine wave generator frequency 2Hz-1MHz, output 0.5V-40Vp-p (such as General Radio 1310-B)

Standard amplitude calibrator 1kHz square wave, output 5mV-50V, accuracy ± 0.25% (recommended 067-0502-01)

Accessories - Coaxial Line: 50 Ω, 42 inches, BNC(012-0057-01)

-Dual input cable: matching signal path, BNC(067-0525-00)

-1000:1 voltage divider: accuracy ± 0.2% (067-0529-00)

-Input RC Normalizer: 1M Ω× 47pF (067-0541-00)

-Serial terminal: 50 Ω, accuracy ± 2% (011-0049-01)

3. Key Calibration Steps (Core 8 Steps)

Step attenuator balance:

R292 (AC STEP ATTEN BAL): Switch between VOLTS/DIV 50mV-0.1V to minimize trajectory offset;

Adjust R318 (VAR BAL): Shift the variable gear from CLOCKWISE to COUNTERCLOCKWISE to minimize trajectory deviation;

Adjust R250 (COARSE DC BAL): Set LF-3dB to DC, switch VOLTS/DIV 50mV-0.1V, and minimize trajectory offset.

Gate current regulation:

+Input to 50 Ω terminal → LF-3dB=DC → Release+GND → Switch+AC, adjust R121 (+GATE CURRENT), minimize trajectory offset;

-Input to 50 Ω terminal → press+GND → release - GND → switch - AC, adjust R127 (- GATE CURRENT), minimize trajectory deviation.

Attenuator DC common mode rejection:

Release+/- GND → VOLTS/DIV=0.1V →+/- Input through dual cables connected to a 50V square wave (calibrator) → Adjust R132 (ATT DC CMR) to display the minimum amplitude.

Input compensation:

-GND pressed ->VOLTS/DIV=50mV ->+input connected to 0.5V square wave (normalized by RC) ->C118 adjusted (Atten Time Constant), with the best square wave front;

Similarly, input C148, C145, C142.

Amplifier gain calibration:

VOLTS/DIV=10mV →+input connected to 50mV square wave → adjust R351 (GAIN), display amplitude exactly 5 grids;

Turn the variable gear to COUNTERCLOCKWISE, with a display amplitude of<2 grids, and then turn it back to CAL.

VOLTS/DIV accuracy check:

VOLTS/DIV=5V →+input connected to 20V square wave (through 1000:1 voltage divider X1 gear) → gradually decrease VOLTS/DIV, synchronously adjust the calibrator output, ensure display of 4-5 grids, accuracy ± 2%;

VOLTS/DIV=5mV gear → voltage divider set X1000 → calibrator output 20V → HF-3dB=10kHz → repeat the above checks.

Common mode rejection ratio (CMRR) calibration:

Release - GND → VOLTS/DIV=10mV →+/- input connected to 20Vp-p, 50kHz sine wave → adjust C160 (CMR 2), display minimum;

VOLTS/DIV=50 μ V → Time base=10 μ s/Div → Adjust C220 (CMR 1), display minimum;

LF-3dB=0.1kHz → switch to C210 (CMR 3), display minimum, repeat until there is no interaction effect.

Bandwidth calibration:

-GND pressed → VOLTS/DIV=1mV → LF-3dB=DC → Time base=1ms/Div →+input connected to 1kHz, 8-grid sine wave → Generator output 1MHz → C330 adjusted, display amplitude reduced to 5.6 grid (-3dB point).


Drawings and Parts List (Section 4)

1. Symbols and reference identification rules

Component symbol: Following ANSI Y32.2-1970 standard, logical symbol follows MIL-STD-806B (positive logic);

Reference identification prefixes: C=capacitor, R=resistor, Q=transistor, CR=diode, F=fuse, J=fixed connector, S=switch, VR=voltage regulator (transistor), etc.

2. Core Parts List (Example)

Part Type Reference Identification Tektronix Part Number Specification Description

Capacitor C103 283-0002-00 0.01pF, ceramic, 500V

Capacitor C133 283-0626-00 1800pF, mica, 5%

Resistance R120 322-0481-07 1M Ω, 1/4W, 1/10%

Resistance R121 311-1223-00 250 Ω, variable

Transistors Q150A/B 151-1027-00 silicon FET, replaceable with D/2N4394 or FD1392

Transistors Q103/Q105 151-0347-00 silicon NPN, replaceable with 2N5551

Diode VR138 152-0520-00 Zener diode, 1W, 12V, replaceable with UZ8712 or HW12B

Switch A10 (LF-3dB) 105-0310-00 cam switch

Switch S280 (VOLTS/DIV) 105-0309-00 cam switch

Circuit board A1 670-1894-00 main circuit board component

image.png

  • ABB DSTA131 2668180-48/2 Programmable Logic Controller
  • ABB COM00012RAA005844A0004J2RAA005696N Control Panel Module
  • ABB MR7557891MRS050640C power relay
  • ABB 2RCA025057A0001R safety relay
  • ABB 2RCA013892A0003H power relay
  • ABB 2RCA013655A0001H power relay accessories
  • ABB 07KT94-98 controller
  • ABB 1MRK002247 Apr04 Transformer Module
  • ABB UNS0884a-v1 3BHE004385R0001 current sensor
  • ABB WMDOLT2-A75 (65KA) 6E 1TGE106812P0001 Input and Output Board
  • ABB Uras26 F-No. 3.346368.0 A-No 0240462201/2030 Gas Chamber Detector
  • ABB UFC911B101 3BHE037864R0101 control board
  • ABB TU841 3BSE020848R1 Termination unit for 1+1 TB840
  • ABB REF541KM115AAA relay feeder protection
  • ABB NINT-71C main circuit interface board
  • ABB LS14250 lithium battery
  • ABB ICSF08D1 FPR3323101R1012 24VDC high-speed counter
  • ABB DO814 Input/Output System
  • ABB 769111B gas chamber detector
  • ABB CM10/00MU1E0/STD Process Controller
  • ABB 769154 A filter element
  • ABB 769137 C 13CO2-10% 0746919 E detector
  • ABB 0769143 A Sample cell (Al), 175 mm
  • ABB 0002-07-2-000001-01 BMXS Scientific Module (ADC)
  • ABB CM15/000S0E0/STD Universal Process Indicator
  • ABB BSD0750 servo drive
  • ABB CI854BK01 Communication Interface Module
  • ABB XVC772A102 3BHE0322285R0102 circuit board
  • ABB AI04 Input/Output System
  • ABB TU847 module terminal unit
  • ABB TB807 module bus terminator
  • ABB PP877K control panel
  • ABB AO845A eA Analog Output Module
  • ABB SD822 power supply equipment
  • ABB 3BHB006716R0277 SYN5302A-Z.V277 synchronizer
  • ABB GFD233A103 3BH02294R0103 Controller
  • ABB 129740-002 134177-001 Intelligent I/O Module
  • ABB XUD194 3BHE018137R0001 AC800PEC High Performance Controller
  • ABB T3N225 Circuit Breaker
  • ABB A30-30-10RT three pole AC contactor
  • ABB SYN5302A-Z, V217 3BHB006716R0217 digital synchronizer
  • ABB NBIO-31 3BSE011337R1 I/O and Expansion Control Module
  • ABB 5SHX1960L0006 3BHB016120R0002 3BHE019719R0101 GVC736BE101 High Voltage Inverter Module
  • ABB PPC905AE101 3BHE014070R0101 control module
  • ABB REF615E_E HBFHAEAGNBA1BNN1XE digital feeder protection relay
  • ABB XVC770BE101 3BHE02103R0101 circuit board module
  • ABB 3BHL000986P7001 redundant DC power supply unit
  • ABB 3HAB8101-18/09A servo drive
  • ABB PM876-1 3BDH000707R1 Controller
  • ABB PPD117A3011 3BHE030410R3011 Excitation Controller Module
  • ABB 1MRK0023505-AA Transformer Differential Protection Relay
  • ABB PFSA140RULLM7A 3BSE006503R1 safety relay module
  • ABB PFSA140RULM1I 3BSE06503R1 drum power supply device
  • ABB MVME162-010A Embedded Controller Module
  • ABB 500BIM01 1MRB150024R0002 Digital Input Module
  • ABB 500BIM01 1MRB160024R0002 Digital Input Module
  • ABB 500PSM03 1MRB 150038 R1 894-030375D 136-011100H power module
  • ABB 500PSM02 1MRB150015R1 AD-272.100.20-01 AZ: C digital power module
  • ABB 500AIM02 1MRB150022 R0002 1HDF 930412 X010 Controller Module
  • ABB 500AIM02 1MRB150022 R0002Y 1HDF 930412 X010 Controller Module
  • ABB 500AIM02 1MRB150022R001 1HDF 930412 X010 Analog Input Module
  • ABB 500MTM02 1MRB150020R1102 1HDF 930512 X010 Controller Module
  • ABB 500MTM02 1MRK001967-AA 1HDF 930512 X010 Input/Output Module
  • ABB 500MTM02 1MRB150020R0712 1HDF 930512 X010 module
  • ABB 500BOM01 1MRB150023R0002 digital output module
  • ABB 500TRM02 1MRB150011R1 Terminal Relay Module
  • ABB 500TRM02 1MRB150011R0001 Transformer Monitoring Relay
  • ABB 500CPU03 1HDF700003R5122 Central Processing Unit
  • ABB 500PB101 1MRB178009R0001 1MRB200064/C Binary Input Module
  • ABB 500CSP04 HE401314/0002 1MRB150051R2 Input Module
  • ABB 500CMP04 HE401314/0001 1MRB150051R1 power module
  • ABB DSAO120 57120001-EY Digital Output Module
  • ABB SUE3000 1VCF750090R0804 servo drive module
  • ABB PFRL101C-1.0KN 3BSE023316R1002 radial weighing sensor
  • ABB UNS4684A-P, V.1 HIEE30514R00R00001 Communication Module
  • ABB PVD164A2059 3BHE014340R2059 excitation controller
  • ABB 3BHE046836R0102 GFD563A102 Analog I/O Module
  • ABB PFCL201CE 10KN 3BSX105983-100 Weighing Sensor
  • ABB PFCL201C 20KN 3BSE023409R20 Weighing Sensor
  • ABB 216VC62A HESG324442R112/F Signal Digital Processor
  • ABB 216EA61B HESG448230R1/G High Voltage DC Converter Valve
  • ABB 216AB61 HESG324013R101 digital output unit
  • ABB REF542 1VCR007346 G0028 Intelligent Sensor
  • ABB INSUMMCU2 MCU2A02V24 Intelligent Motor Control Unit
  • ABB MCU2A01C0-4 motor control unit
  • ABB PDP22-FBP fieldbus interface
  • ABB PNI800A Network Interface Module
  • ABB 3BHE039724R0C3D PPD513AOC 100440 Controller
  • ABB SDCS-CON-2-COAAT 3ADT220090R2 Controller
  • ABB CI543 communication interface
  • ABB PM510V08 3BSE00B373R1 processor module
  • ABB UNITRAL1010 3BHE035301R0001 UNS0121A-Z-V1 Exciter
  • ABB CI873K01 3BSE058899R1 Ethernet/IP interface module
  • ABB DYTP600A 61430001-ZY Signal Processor Module
  • ABB REF615C-E HCFFAEAGAABC2BAA11E feeder protection and control
  • ABB PCD235C101 3BHE057901R0101 Expansion Adapter
  • ABB UAD149A0001 3BHE014135R0001 excitation controller
  • ABB UAD149A1501 3BHE014135R1501 Controller Module
  • ABB REF545KC133AAAA protective relay
  • ABB PFSA103D 3BSE002492R0001 intermediate relay
  • ABB KUC321AE HIEE300698R1 power module
  • ABB PFVK135 PLC signal processing board
  • HIMA X-CPU 01 processor module
  • ABB TU811 Compact Module Terminal Unit
  • ABB REM610C55HCNN02 motor protection relay
  • ABB IMRIO02 Remote Input/Output Module
  • ABB PFEA113-20 3BSE050092R0 Tension Electronic Equipment
  • ABB UFC911B108 3BHE037864R0108 communication interface
  • ABB REU615E_D Voltage Protection and Control Relay
  • ABB PPD512A10-150000 Controller
  • ABB 5SHX1445H0001 3BHL0000391P0101 3BHB003230R0101 5SXE05-0152 module
  • ABB ICST08A9 Modular Controller
  • ABB 1SVR011718R2500 Analog Converter
  • ABB TB807 3BSE008538R1 module bus terminator
  • ABB PM511 processor module
  • ABB PP877 3BSE069272R2 Industrial Touch Screen
  • ABB EasyLine EL3020 Continuous Gas Analyzer
  • ABB PFEA111 series optical discs
  • ABB DSTD150 I/O connection terminal unit
  • ABB AO801 Analog Output Module
  • ABB PM866 controller
  • ABB 408368B IAM module
  • ABB 3HAC025562-001/06 capacitor unit
  • ABB IEPAS02 power module
  • ABB MSR04X1 serial communication module
  • ABB ICSI16E1 Digital Input Module
  • ABB 3HAC026271-001/DSQC646 Robot Drive
  • ABB SPBRC400 PLC module/rack