Installing the Module:
1. Make sure system power is off.
2. Install the module in slot 0 of the remote chassis by aligning the circuit board with the chassis card guide. The 1747-ASB module must be installed only in slot 0 (the left slot) of the remote chassis. Do not install the 1747-ASB module in the remote expansion chassis.
3. Slide the module into the chassis until the top and bottom tabs lock into place. To remove the module, press and hold the release located on each self-locking tab and slide the module out.
4. Cover all unused slots with the Card Slot Filler, Catalog Number 1746-N2.
Connecting RIO Link Devices:
Link Wiring
The modules are connected in a daisy chain configuration on any RIO link. A daisy chain network is formed by connecting network devices together in a serial manner using Belden 9463 cable. Belden 9463 cable is the only approved cable for Allen-Bradley RIO links. The total number of adapters allowed on the RIO link is:
• 32 if the scanner and all adapters on the RIO link have extended node capability
• 16 if the scanner or any adapter does not have extended node capability
There are no restrictions governing the spacing between the devices, as long as the maximum cable distance is not exceeded.
Other Products in operation:
MOTOROLA MVME-147A
ABB CI867K01
GE IC695ETM001
SCHNEIDER TSXP572634
SCHNEIDER 490NAA21302
ABB KUC711AE
GE 531X139APMALG2
TRICONEX 3481
GE EP62 C16 SWITCH
HONEYWELL MC-PAIH03
Triconex 3003 EMPII
GE DS3800HSCD1F1C
GE 237B8632G1
MVME172P-644L
WOODWARD 9907-164
email:1583694102@qq.com