High end industrial PC (enhanced environmental capability: vibration 1 g, impact 15 g, components continuously compatible for at least 5 years):
VPP 16.1/40.1:12 "/15" color display, 3-slot chassis (2 x PCI+1 x PCI/ISA), Celeron M minimum 1.3 GHz, 512 MB or 1 GB RAM;
VPB 40+VDP Passive Panel: A high-end host with 3 or 4 slots installed inside the cabinet, connected to the VDP panel through the GIGASTAR interface, with a maximum cable length of 35 meters.
Key selection constraints: IndraControl P40 can only be used for Bosch Rexroth standard industrial PCs; P60 can be used for all Bosch Rexroth industrial PCs, including high-end models. The two modules are ordered as industrial PC sub items in the form of "Control Configuration (CFG -...)", and the configuration code includes both high-speed I/O interfaces (8 in/8 out) and DeviceNet extension options. The CFG code table should be accurately specified when ordering.

Peripheral and supporting components
VAM machine control panel (VAM 10/40/11/41): provides operation mode selection and manual operation, including LED buttons, feed and spindle magnification knobs, emergency stop button, and key switch; The back is equipped with a handwheel and manual operation panel interface, as well as 16 digital 24V inputs and 8 outputs, which communicate with the main control through PROFIBUS-DP (IKB0033 connects P40/P60 and VAM, IKB0034 is used for VAM cascading);
VCP Mini Control Panel (VCP 02/05/08/20/25): Compact operation and monitoring terminal, communicating via PROFIBUS interface; VCP 25 is a 5.7 "touch terminal, equipped with a 32-bit RISC CPU (74 MHz), 3 MB flash, and 512 kB CMOS-RAM;
VAK PC keyboard: Pull out (VAK 10.1/40.1, 86 key PS/2 with integrated pointing device) and embedded touchpad keyboard (VAK 11/41106 key low installation depth);
UPS uninterruptible power supply (VAU01.1S-230-255-NN): triggers the operating system to shut down in an orderly manner when there is a brief voltage drop or a prolonged power outage. It is recommended to always install it to avoid data loss and communicate with the industrial PC via serial port COM1;
External battery pack (SUP-E01-BTV16/40): provides power-off data protection for high-end industrial PCs, connected via IKL0264 cable (1 m/3 m);
RECOM Inline module: Modular I/O (bus coupling, feeding, 24V input/output, relay, analog, counter, etc.) installed on the top cap guide rail inside the cabinet;
RECOM Fieldline module: IP65/IP67 protection, used for direct access of sensors/actuators in harsh environments near the station, with three models covering 8-in, 4-in/4-out (2A), and 8-out (2A).
Interface and Diagnostic Key Points
P40/P60 provides three sets of dual LEDs (red green multiplexing) and one red LED on the keyboard:
Ready Active/Watchdog Error LED: Green light=Ready contact closed, watchdog triggered; Red high-frequency flashing=local CPU is in reset state; Red light constantly on=Ready error has occurred and the watchdog is responding;
Power Good/Trigger LED: Off=At least one voltage of the four onboard DC/DC transformers is incorrect (due to vector group or PC power failure); Green=normal voltage on all four channels;
SERCOS LERR LED: Directly driven by the SERCON816 controller, it reflects the quality of fiber optic reception and should not light up under normal conditions;
Watchdog Reset button: Reset pending watchdog errors, cancel PC NMI disable signal, or switch to RAM Boot during power on and LRRESET periods.
The SERCOS interface X7S1/X7S2 uses fiber optic to construct an IEC 1491 ring topology, with the ring starting and ending at the control module (X7S2 output → first driver input →... → last driver output → X7S1 input), with a maximum transmission rate of 16 Mbaud. The PROFIBUS-DP main station interface X7P has a maximum of 12 Mbaud and connects the VAM operation panel to the Inline/Fieldline sensing execution layer. Ethernet (RJ45) can connect to the upper computer layer with a maximum of 100 Mbaud. Ready contact (maximum 60 V/1 A) disconnects when the module is not started or the watchdog error occurs. It is recommended to connect it to the machine emergency stop link; The signal line must use shielded cables and large-area shielded connectors, as poor shielding may cause misoperation.
The maintenance strategy for P40/P60 is to replace the entire module, and on-site maintenance is prohibited. Only the CPU fan (Celeron P3 fan, part number 1070922532) can be replaced separately; Complete module spare parts: P40 corresponds to CMP40.1-SP-304-FN-NNNN-NW (R911170066), P60 corresponds to CMP60.1-SP-304-FN-NNNN-NW(R911307078)。 When replacing fans or modules, it is necessary to comply with the requirements of EN 61340-5-1/-5-2 for electrostatic discharge protection.
Core clauses of safety regulations
The system follows the ANSI Z 535 hazard level classification (Danger=inevitable death or serious injury; Warning=Possible occurrence; Caution=mild to moderate injury or property damage), and provide multiple mandatory regulations for electric drive:
>50 V electric shock protection: The grounding conductor must be permanently connected and non removable. When the leakage current is greater than 3.5 mA, the minimum cross-sectional area of the grounding copper wire is 10 mm ²; After the power failure of the driving and filtering components, wait for 30 minutes for the capacitor to discharge. Before operation, measure the capacitor voltage to confirm safety; Residual current protectors (RCDs) cannot be used for electric drive, and alternative methods such as overcurrent protection devices must be used for indirect contact protection;