Product positioning: A "out of the box" amplifier designed for position feedback proportional valves
Bosch Rexroth VT-MSPA is an analog modular valve amplifier (component series 2X) designed for proportional directional valve and pump control without electrical position feedback. It is specifically designed for convenient selection of industrial hydraulic Rexroth valves - the valve characteristic curve is pre stored inside the equipment, and users can select the valve type by rotating the switch and optimize the parameters through buttons. All valve parameters can be adjusted.
Two variants and four ordering models:
VT-MSPA1 (single electromagnet): Command value 0...+10 V or 4... 20 mA;
VT-MSPA2 (dual electromagnet): Command value 0... ± 10 V or 4... 20 mA, maximum electromagnet current set according to A/B electromagnet respectively.
Model Material Number Instruction Value Form
VT-MSPA1-2X/A5/000/000 R901439034 Voltage 0...+10 V
VT-MSPA1-2X/F5/000/000 R901439036 Current 4... 20 mA
VT-MSPA2-2X/A5/000/000 R901439037 Voltage 0... ± 10 V
VT-MSPA2-2X/F5/000/000 R901439038 current 4... 20 mA
The device weighs only 0.14 kg and measures 114 × 22.5 × 99 mm. It is installed in a rail type (TH35-7.5 or TH35-15, EN 60715) and has 12 detachable spring terminals.
Complete solution of functional link: 11 level signal processing from command value to electromagnetic current
The internal signal chain of the amplifier can be decomposed into the following links (block diagram numbers in parentheses):
1. Power unit (1): Equipped with a built-in current limiting device to suppress peak closing current and integrated reverse polarity protection. Power supply 24 V DC (minimum 18 V - maximum solenoid current 0.8 A for valves is 21 V; maximum 36 V; residual ripple 40... 400 Hz, maximum 2.5 Vpp and must comply with allowable limits); Maximum power consumption<48 W; external 3.15 A delay fuse protection; Maximum current consumption<2 A, maximum closing current<4 A).
2. Instruction value and summation device (3): "Internal instruction value"="External instruction value" at the input of differential amplifier (2)+zero offset (4, adjustable "Z/B" in standard settings). Hydraulic directional logic (4W... valve): P → A, B → T flow is generated by the command values of electromagnet B, 0...+10 V or 12... 20 mA; Generate P → B, A → T flow through electromagnet A, 0... -10 V or 12... 4 mA; The instruction value (5) can be reversed in expert settings. Positive command value of pressure valve=pressure rise at the valve. During normal operation, internal command values can be measured at the "v" measuring socket.
3. Slope generator (6/7): Limit the slope of the instruction value. Choose between a single slope (6, all slopes share the same time, default value) or a 4Q/2Q slope (7, different times in each quadrant, expert setting) - the characteristic curve generator does not affect the slope time. The adjustable range of slope time is 0.01... 30 seconds.
4. Instruction value attenuator "G" (8): reduces the amplitude of the instruction value, with an adjustable range of 70... 110% (when the instruction value is 100%).
5. Characteristic curve generator (9): Adapt the pre stored valve characteristic curve to the actual hydraulic and control technology conditions. Expert settings adjustable: lead current "B", step "S", maximum current "G" (VT-MSPA2 can be set for electromagnet A and B separately). Step level 0... 50%.
6. Current controller (10): Record the current of the electromagnet and compare it with the command value, and compensate for the difference (PID closed-loop).
7. Clock generator (11) and power output stage (12): The output stage generates chopper electromagnet current; The clock frequency of Rexroth valve sometimes varies with the command value and/or operating voltage (set range 95... 505 Hz, depending on the selected valve). The current of the electromagnet is limited to the maximum allowable current (maximum 2.7 A) determined by the set valve, and the output stage is protected against short circuit; When there is internal interference signal or missing enable, the output stage is turned off. Electromagnetic cable (1.5 mm ²) with a maximum length of 50 meters.
8. Digital Input DI (13): Four optional functions - Enable (factory settings); VT-MSPA1 has no function (permanently enabled)/VT-MSPA2 instruction value inversion (permanently enabled); Slope ON/OFF (permanently enabled); Single/quadrant ramp switching (permanently enabled). Digital input XH2: ON (valid) 11... 36 V, OFF (invalid) -3... 5 V, RE>50 k. Special valve example: The switch position 0-5 of the proportional directional valve "4WRPH 6... SO855" is fixed at the command value ± 10 V and the command value is reversed (permanently enabled).
9. Digital output (15): The device outputs a "ready" signal when there are no disconnections, no internal errors, and UB ≥ UB min. Simulate actual output X2A: IA is 0... -2.5 V (V ≙ A), IB is 0...+2.5 V, and the minimum load impedance is 1 k Ω.
Switch position valve type comparison: plug and play configuration for over 50 valve types
The core value of the amplifier lies in the direct selection of valve type by the rotary switch, without the need for external parameterization tools. The switch position is a two digit number (ten positions x one position, 0-0 to 9-8), divided into two sets of mapping tables according to the number of valve electromagnets:
VT-MSPA1 (single electromagnet) main mapping (component series requirements in parentheses):
0-0 No valve; 0-1 is 4WRA6... -2X; 0-2 is 4WRA10... -2X; 0-3 is 4WRZ... -7X; 0-4 is 3DREP6... -2X; 0-5 is 4WRPH6... -2X (SO855); 0-6 is DBEP6... -1X; 0-7/0-8 are DBET-6X/7X... G24 (G24-8 variant); 0-9/1-0 is DBTX-1X... G24-25/G24-8; 1-1 to 1-7 are (Z) DBE6-2X and DBEM10/20/30... -7X series (G24/G24-8); 1-8 to 1-9 are (Z) DRE6... -1X and ZDRE10... -2X... G24; 2-0 to 2-6 are ZDRE10, DRE... 10/20/30... -6X series (G24-8 variant); 2-7/2-8 is 3DRE... -7X... G24 (G24-8); 2-9/3-0 is 3FREX6/10... -1X... G24-25; 3-1 is 3DREP6... -2X... (SO674); 3-2 is Z3DRE10... -1X... G24 (starting from component series 21); 3-3 to 3-6 are DBE6X-1X... G24-25/G24-8, DRE6X-1X-G24-8, DBET-1X... HG24-8 (starting from component series 21);
Pump control dedicated position: 3-7 pump control 1 (0.7 A) EP2 (A7VO); 3-8 pump control 2 (0.6 A) ED72/ER72 (A10VSO/31); 3-9 pump control 3 (0.6 A) EP2/EK2 (A10VSO/52,53), L4/E2 (A15VSO...), EP2,6 (A6VM); 4-4 pump control 4 (1.9 A) U7 (A15VSO...), EC4 (A10VSO...); 4-5 Pump Control 5 (2.7 A) U8 (A15VSO...), EB4 (A10VSO...) - Pump Control 4/5 requires component series starting from 23;
4-0/4-1 refers to DBE10Z-1X... G24-8, DRE10Z-1X... G24-8 (starting from component series 21); 4-2/4-3 are (Z) 3DRE6... -2X/... G24 (G24-8, component series 22 onwards);
Universal position: 9-6 universal (0.8 A), 9-7 universal (1.6 A), 9-8 universal (2.5 A) - used for valve types not listed in the table.
VT-MSPA2 (Dual Electromagnetic) Mapping: Only 0-1 to 0-6 (4WRA6/10... -2X, 4WRZ... -7X, 3DREP6... -2X, 3DREP6... -2X (SO674), DBEP6... -1X), 3-7 Pump Control 1 (0.74 A) EP (A4CSG), and 9-6/9-7/9-8 universal positions are valid, while the rest of the switch positions are "-" (invalid) - the selection range for dual electromagnetic applications is significantly narrowed, and the table must be checked before selection.
Installation, Environment, and EMC Compliance
Installation position: Vertical installation; To ensure the breathing and heat dissipation of the device, the top and bottom ventilation ducts should be at least 2 cm away from the cover plate, wall, etc. When the ambient temperature exceeds 50 ℃, the distance between adjacent devices should be 1 cm. The ambient temperature should be 0...+60 ℃; Storage (UV protection)+5...+40 ℃; Transportation -40...+70 ℃; Relative humidity 10... 95% (no condensation); Maximum usage altitude of 2000 meters; maximum temperature change of 5 ℃/min; Start time<1 s; UV resistance is conditional (prolonged exposure may cause discoloration); Free drop of 1 meter from original packaging; glass fiber reinforced polyamide shell; Prohibit contact with conductive dust and avoid contact with hydraulic oil.
Mechanical strength: sinusoidal test at 10... 500 Hz/maximum 2 g/10 cycles/3-axis (EN 60068-2-6); Noise test 20... 500 Hz/2.2 gRMS/6.6 g peak/0.5 h/3 axes (EN 60068-2-64); Transport impact 15 g/11 ms/3-axis (EN 60068-2-27); IP20 (EN 60529) - Only for installation inside control cabinets.
EMC Matrix (CE compliant with EMC Directive 2014/30/EU, RoHS 2011/65/EU): EN 61000-6-2 Immunity - ESD 4 kV CD/8 kV AD (BWK B), HF radiation 10 V/m(80…6000 MHz,BWK A)、Burst 2 kV(5/100 kHz,BWK B)、Surge 0.5 kV(2 Ω/12 Ω) to operating voltage and 1 kV (42 Ω) to signal (BWK B), HF conduction 10 Veff (150 kHz... 80 MHz, BWK A), magnetic field 50/60 Hz 100 A/m (BWK A); EN 61000-6-3/6-4 emission - Interference voltage 0.15... 30 MHz (Class A), RF interference field strength 30... 6000 MHz (Class B, EN 55016-2-1/-2-3)。

Terminal allocation and operation panel
12 Terminal Allocation Table: XH1- Terminal 1+UB, Terminal 2 0 V, Terminal 3 Electromagnetic B+, Terminal 4 Electromagnetic B −; XH2-5-terminal digital input, 6-terminal Ready, 7-terminal electromagnet A+, 8-terminal electromagnet A − (VT-MSPA2 only); X2A -9-terminal instruction value+, 10 terminal instruction value -, 11 terminal actual value+, 12 terminal actual value -.
Five elements of the front panel: ① Status LED group (displaying the current operating status, menu hierarchy, and error conditions); ② SET key (edit selected parameters, select work run, enter "expert mode"); ③ +/- keys (select parameters and adjust parameter values); ④ Rotary switch (valve type selection, 0-9 scale x two layers); ⑤ Measurement sockets (IB, IA, v, ⊥) - command value/set "v" to 0... ± 10 V, actual current value IA/IB to 0... ± 2.5 V (V ≙ A), reference potential "⊥", can be connected to an external multimeter for real-time observation of each node in the signal chain.
LED status diagnosis matrix (the first entry point for troubleshooting)
Yellow "Digital input" LED: normally running, constantly on/off=digital input status; Flashing in settings=standard settings activated; Setting to disable=Expert setting to activate; Settings: Bright/Flash/Tremble=Expert settings: Digital input settings.
Red/Green "Ready" LED (Core Diagnostic Light):
Meaning of display mode
Constant green module ready
Chang Lianghong Error
The red green flashing valve setting has been changed
Red flashing is not allowed for valve numbers (the rotary switch is in the invalid switch position)
Extinguish module not ready
Green Flash (in settings) Expert settings activated
LED display symbol meanings: DI=enable, t=ramp, Z/B=zero/pilot current, G=command value attenuator, S=command value step level ☺= Ready, four diagonal symbols=quadrants 1-4 (positive command value up/positive command value down/negative command value up/negative command value down) - quadrant indication allows the operator to intuitively confirm the direction of the command value and the slope action status. For detailed description, please refer to operating instruction 30232-B.
Project planning and wiring specifications (core line of defense against failures)
The eight iron rules for wiring:
Maintain maximum possible spatial separation between signal lines and load lines;
Do not pass signal lines through magnetic fields;
Lay signal lines with as few intermediate terminals as possible;
Do not lay signal lines parallel to load lines;
Connect the cable shielding layer (see operating instructions 30232-B);
Digital input/output and command/actual value cables: The maximum allowable length for unshielded cables is 30 meters, and shielded cables are required for longer cables;
Maintain sufficient distance (>1 m) from wireless equipment;
When the working voltage fluctuates strongly, in some cases, it may be necessary to use an external smoothing capacitor with a capacity of at least 2200 µ F.
EMC sensitive environment: Additional measures must be taken according to the application (such as shielding, filtering). Recommended capacitor module VT 11110 (data sheet 30750) - sufficient to support power smoothing for up to 3 amplifier modules.
Heat dissipation and delivery status: The upper and lower ventilation ducts must not be obstructed by adjacent devices to ensure sufficient cooling; The device has been tested in the factory and delivered with default settings - it can operate upon first power on, but the valve type switch position must first be rotated to the corresponding position of the actual valve.
Typical troubleshooting process
Electromagnetic cable breakage protection action with a maximum length of 50 m (1.5 mm ²); Shielded and unshielded 30 meter rule