Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Eaton S801+Soft Starter Complete Guide

来源: | 作者:FAN | 发布时间 :2026-03-11 | 14 次浏览: | Share:

Eaton S801+Soft Starter: The Ideal Choice for Intelligent Motor Control

In modern industry, the starting process of three-phase asynchronous motors directly affects the stability of the power grid, mechanical life, and production efficiency. Direct starting can generate a surge of up to 6-8 times the rated current, leading to voltage drops and excessive mechanical stress. The S801+soft starter launched by Eaton adopts an advanced six SCR fully controlled bridge topology, which smoothly increases the motor terminal voltage by continuously adjusting the thyristor conduction angle, thereby controlling the starting torque and current. After the motor reaches the rated speed, the thyristor is short circuited through an internal bypass contactor to achieve efficient operation. This article is based on the official user manual and provides a comprehensive analysis of the technical characteristics, installation requirements, functional configuration, parameter settings, and fault handling of S801+soft starter.


Product Overview and Technical Standards

1.1 Function and purpose

S801+soft starter is an electronic, self-contained motor soft starter device suitable for panel or cabinet installation. It controls the voltage applied to the motor to achieve smooth mechanical and electrical starting, suitable for centrifugal pumps, fans, compressors, conveyors, and other occasions that require limiting starting current and reducing mechanical shock. This series of products offers multiple current levels, covering application requirements from 37 A to 1000 A (taking S801+N37 to S801+V10 as an example).

1.2 Compliance with standards

S801+meets the following international and regional standards:

UL 508 (Industrial Control Equipment)

CSA C22.2 No.14-1995

IEC 60947-4-2 (Low voltage switchgear and control gear - AC semiconductor motor controllers and starters)

CCC GB14048 (China Compulsory Certification for Products)

1.3 Main Technical Highlights

Six SCR topology: one pair of anti parallel thyristors per phase to achieve full wave voltage regulation.

Built in bypass contactor: The motor automatically bypasses after reaching the rated speed, reducing conduction losses.

Control Interface Module (CIM): intuitive knob and DIP switch configuration, parameters can be set without software.

Multiple start/stop modes: voltage ramp, current limit, jump start, soft stop.

Comprehensive motor protection: thermal overload, locked rotor, phase loss, phase sequence, overcurrent, undervoltage, etc.

Wide environmental adaptability: Operating temperature range of -40 ° C to+50 ° C, no need to reduce capacity within an altitude of 2000 meters.


Technical data and specifications

2.1 Environmental conditions

Parameter specifications

Operating temperature -40 ° C to+50 ° C

Storage temperature -50 ° C to+70 ° C

Altitude ≤ 2000 meters, with a capacity reduction of 0.5% every 330 meters after exceeding it

Humidity ≤ 95% without condensation

Pollution level 3 (IEC 60947-1)

Anti impact 15 g (in any direction)

Anti vibration operation/non operation: 3 g

2.2 Mechanical dimensions and weight

S801+offers multiple frame sizes (N, R, T, U, V) to accommodate different current levels. For example:

S801+N37: Width 67.6mm, height 187.2mm, depth 163.9mm, weight 2.6kg.

S801+V10: width 280.6 mm, height 420.8 mm, depth 187.8 mm, weight 41.4 kg.

2.3 Short circuit rating

Different frameworks are suitable for circuits with different short-circuit capacities and should be used in conjunction with appropriate fuses or circuit breakers. Typical values:

N Framework: 10 kA/600 V (with JHFD type fuse)

R framework: 10 kA/600 V (RK5 or JHFD/HKD type fuse/circuit breaker)

T. U-frame: 18-30 kA/600 V

V-frame: 42 kA/600 V

Installation and wiring

3.1 Mechanical Installation

Check the equipment for any transportation damage before installation.

Drill holes on the panel according to the dimension diagram in the manual, and use bolts of the specified specifications (such as 1/4 inch bolts for V-frame with a torque of 50 lb in).

Ensure that the installation surface is flat and all fixing points use hardware.

For heavier V-frames (up to 103 lb), suitable lifting equipment should be used.

3.2 Main circuit wiring

S801+adopts an online connection method, where the power lines are connected to L1, L2, and L3, and the motor lines are connected to T1, T2, and T3. Wiring precautions:

Short circuit protection devices (fuses or circuit breakers) must be installed on the line side.

When wiring, follow local electrical regulations and use copper wires (75 ° C).

For T, U, and V frames, the standard supply does not include wiring terminals and requires separate ordering of wiring harness kits (such as EML22, EML28, etc.).

The wiring torque depends on the wire size, for example, a 4 AWG wire with a torque of 45 lb in.

3.3 Control circuit wiring

The control circuit is connected through a 12 bit terminal block and an RJ12 interface (connected to CIM).

Power supply: The terminal+/- needs to be connected to a 24 Vdc control power supply (SELV). The power capacity needs to meet the requirements of steady-state 25 W and surge 240 W (continuous for 150 ms).

Input signal:

Terminal P: Operation allowed (24 Vdc must be continuously applied to start)

Terminal 1: Start command (triggered by level or edge, depending on DIP switch S1 setting)

Terminal 2: Jog (Jog)

Terminal 3: Overload protection disabled during startup (for debugging only)

Terminal 4: Reset

Auxiliary contacts: Terminals 13, 14, 95, 96, 98 provide relay outputs that can be used to indicate operating status or faults. Contact capacity: 3 A/120 Vac or 24 Vdc, maximum 10 A (resistive).

3.4 DIP switch settings

The detection method for selecting the start command of S1 switch:

OFF (factory default): Level triggered, that is, when terminal 1 maintains 24 Vdc, as long as the allowable conditions are met and there are no faults, the motor will start.

ON: Edge trigger, which means that terminal 1 must have a rising edge from 0 to 24 Vdc to start, and the rising edge must be reapplied after fault reset.

The S2 switch has no function in S801+.


Working principle and start/stop mode

S801+uses six thyristors internally to form a three-phase fully controlled bridge. During the starting process, by gradually increasing the conduction angle of the thyristor, the motor terminal voltage is smoothly increased from the preset initial torque value to the full voltage. When the motor approaches synchronous speed, the internal bypass contactor closes, the thyristor is short circuited, and the motor is directly powered by the power supply, thereby reducing thyristor losses.

4.1 Voltage ramp starting

This is the most commonly used mode. The voltage starts from the initial torque value and linearly increases to full voltage within the set soft start time. If the motor reaches synchronous speed ahead of schedule, the bypass contactor will close early, and the soft start time may be shortened.

4.2 Current limit starting

In this mode, the soft starter maintains a constant current upper limit (determined by the initial torque setting) instead of a voltage ramp. Suitable for situations where strict limitation of grid surge current is required. Attention: It is not recommended to use it for variable torque loads such as fans and pumps.

4.3 Kick Start

For loads with high static friction, a short-term high torque pulse can be applied during the initial start-up period. The sudden jump torque and duration can be set separately through the potentiometer on CIM.

4.4 Soft Stop

When stopping, the voltage gradually decreases within the set soft stop time, causing the motor to slowly stop to avoid water hammer effect or mechanical shock. Attention: Soft stop is not braking and will not shorten the downtime.

Parameter setting and protection function

5.1 Control Interface Module (CIM)

CIM is installed on the S801+front panel and provides the following configuration components:

FLA potentiometer: Set the motor's full load current (range: 32% to 100% of the frame's rated current).

Starting time potentiometer: 0.5-180 seconds.

Initial torque potentiometer: 1% to 85%.

Jump torque/time potentiometer.

Soft stop time potentiometer: 0-60 seconds.

Overload level DIP switch: optional levels 5-30, default 20.

Fault indicator light: The S.S. Trip LED flashes to indicate a fault code.

5.2 Protection parameters and fault codes

S801+has multiple built-in protection functions that can be enabled/disabled through CIM:

Overload protection (thermal memory model)

Stall: When starting, the motor has not reached synchronous speed and the current is greater than 2 × FLA.

Jam: Current>3 × FLA during operation.

Lack of phase/phase sequence/phase imbalance

SCR short circuit/open circuit detection

Bypass contactor malfunction

Control power undervoltage

When a malfunction occurs, the S.S. Trip LED lights up, and the flashing code can be read by pressing and holding the reset button. For example:

Description of code faults, possible causes, and countermeasures

11. Excessive thermal overload load, low FLA setting, and frequent starting.

14 phase sequence error. The incoming phase sequence does not match the set value. Swap two phases.

The 22 phase loss fuse is blown and the circuit is disconnected.

32 SCR short circuit SCR breakdown, measure phase to phase resistance to confirm.

The control voltage is low, and the 24V power supply capacity is insufficient or the line voltage drop is too large.

5.3 Thermal Overload Model

S801+uses a thermal memory model to simulate motor temperature rise and can provide overload protection levels 5, 10, 20, and 30 as specified in IEC 60947-4-2. The heat accumulation value is stored in non-volatile memory and will not be lost when powered off. After each overload trip, the reset suppression time gradually increases (3 minutes for the first time, 6 minutes for the second time, and 9 minutes for the third time) to allow the motor to cool down.


Typical wiring and application precautions

6.1 Three wire button control

The manual provides wiring diagrams for three wire and two wire button systems. Typical three wire wiring: the stop button (normally closed) is connected in series with the allowable circuit (terminal P), and the start button (normally open) is connected to terminal 1. Auxiliary contacts can be used to indicate operational status.

6.2 Selection of 24 Vdc Power Supply

S801+requires control of power capacity: steady-state 25 W, surge 240 W for 150 ms. It is recommended to use Eaton PSG series power supplies, such as PSG240E (240 W) or PSG480E (480 W).

6.3 Coordination with bypass contactor

If an isolation switch or contactor needs to be installed on the load side, it must be operated after the soft starter has stopped, otherwise it may damage the SCR or cause false faults.

6.4 Power factor compensation capacitor

The power factor compensation capacitor must be connected to the power supply side of the soft starter and maintain a minimum cable distance of 10 feet from the soft starter. It is strictly prohibited to connect capacitors to the load side, otherwise it will affect overload detection.

Debugging and troubleshooting

7.1 Pre commissioning checklist

The main circuit wiring is correct and the phase sequence is correct.

Control the power supply to 24 Vdc and connect it correctly, with a voltage of ≥ 18 Vdc.

Allow terminal P to have a 24 Vdc signal.

CIM parameter setting: FLA equals the motor nameplate value; The starting time and initial torque are adjusted according to the load; Set the overload level to an appropriate value (usually 20).

If there is a phase sequence fault during the first power on, switch the incoming lines L1 and L2.

7.2 Common Fault Handling

The device does not respond to the start command: check if the allowed terminal P has 24V; if the LED is green; If it is red, read the fault code and handle it; If it is edge triggered mode, the start signal needs to be reapplied.

Starting time too long or too short: Adjust the initial torque and starting time potentiometer. If the static friction force of the load is high, a sudden jump start can be activated.

Sudden tripping during operation: Record fault codes and check for overload, phase loss, or overheating. If it is an overload, check if the load has increased or if the FLA setting is too low.

The bypass contactor cannot be closed: check if the control power supply capacity is sufficient (the voltage drop during surge should not be lower than 17V); Check if the contactor coil is normal; If the soft starter fails to close after multiple attempts, it will switch to SCR operation mode and may eventually overheat and trip.

7.3 Fault code reading

In the fault state, press and hold the reset button on CIM (or apply 24V to terminal 4), and observe the number of flashes of S.S. Trip LED. For example, flashing 3 times, stopping and then flashing 2 times indicates fault code 32. After releasing the button, determine the cause of the malfunction according to Appendix E of the code query manual.


Accessories and Options

S801+offers multiple options to meet different installation needs:

Wiring kit: EML22~EML33, suitable for different cable specifications and quantities.

Panel installation kit: EMA69A~EMA69D, including 3-10 feet of cable, used for remote installation of CIM on cabinet doors.

Installation board/anti vibration board: EMM13xx, EMM14xx, used to simplify installation or enhance anti vibration.

IP20 protective cover: SS-IP20-xx, used to improve terminal protection level.

Fan kit: EMM18, designed to enhance heat dissipation (for high-power applications).


Motor and special application considerations

9.1 Motor type

S801+is suitable for standard squirrel cage motors and can also be used for special motors such as star delta, partial winding, dual voltage, multi speed, etc., but correct wiring is required. For star delta motors, they must be connected in a delta operation mode, and soft starters cannot be connected between internal windings.

9.2 High inertia load

For high inertia loads such as fans and centrifuges, it is necessary to increase the starting time and initial torque appropriately, and use jump starting if necessary. Pay attention to checking the number of starts per hour to avoid exceeding the SCR thermal capacity.

9.3 Frequent Jogging

In Jog mode, the bypass contactor will not close and the motor will be powered entirely by SCR. Frequent tapping can cause SCR to heat up, and it should be ensured that the cumulative on-time per hour does not exceed the allowable value.

  • UNIOP ETOP307-U301 High-Performance Touch HMI
  • UNIOP CP01F-02-0042 Industrial Control Panel
  • UNIOP CP01F-02-0021 Compact Operator Panel
  • UNIOP MKDL 16 0021 LCD Operator Terminal
  • UNIOP MD02R-04-00A6 Alphanumeric Display Module
  • UNIOP eTOP11-0050 10.1" Widescreen HMI
  • UNIOP ETOP 05-0045 5.7" HMI
  • UNIOP eTOP40C-0050 4.3" Compact HMI
  • UNIOP epad05 5" Industrial Tablet HMI
  • UNIOP CP10G-04-0045 10.4" Graphic HMI
  • UniOP EK04 Operator Panel HMI Display Keypad 6ZA983-7
  • UniOP TP-01 Touch Screen Panel Industrial HMI Interface
  • UniOP PQ5187 Operator Interface Module Industrial HMI
  • UniOP MD02R-04-0045 Operator Interface Module
  • UniOP MD03R-02-0042 Operator Interface Module Industrial HMI
  • UNIOP MD00R-04-0045 Text-Based Operator Module
  • UNIOP MKDR-16-0045 Alphanumeric Operator Terminal
  • UNIOP eTOP05-0045 Compact HMI Touch Screen
  • UNIOP EK-04 CONTROL Operator Terminal
  • UNIOP eTOP30-0050 Industrial HMI Touch Panel
  • UNIOP ETOP03-0046 3.5" Touch HMI
  • UNIOP CP01F-02-0045 Function Key HMI
  • UNIOP CP01R-04-0045 Text Display HMI
  • UNIOP eTOP06-0050 5.6" Touch HMI
  • UNIOP eTOP10B-0050 10.1" Touch HMI
  • UNIOP eTOP03-0046 Touch Screen HMI
  • UNIOP MKDR-16-TA-0045 Keypad Display Terminal
  • UNIOP MD02R-04-0042 Micro Display Module
  • UNIOP ECT-16-0045 Ethernet HMI Controller
  • UNIOP CP05R-04-0045 HMI Operator Panel
  • UniOP ETOP05-0045 Operator Panel Industrial HMI Interface
  • UniOP MD02R-04-0045 Operator Interface Module Industrial HMI
  • UniOP MD00R-02-0045 Operator Interface Module Industrial HMI
  • UniOP MD00R-04 Operator Interface Module Industrial HMI Panel
  • UniOP ePALM10-0060 Operator Panel HMI Interface Terminal
  • UNIOP MD00R-02-0045 Alphanumeric Display Module
  • UNIOP CP10G-04-0045 Graphic Operator Interface
  • UNIOP MKDR-04-0021 Compact Text Operator Terminal
  • UNIOP MKDL-16-0021 Alphanumeric Operator Terminal
  • UNIOP eTOP20C-0050 Color HMI Touch Panel Technical Data
  • UNIOP eTOP20C-0050 Color HMI Touch Panel Data
  • UNIOP MD00R-02-0045 Text-Based Display Module
  • UNIOP eTOP05-0045 Operator Interface
  • UNIOP ETOP11-0050 HMI Color Operator Interface Data
  • UNIOP eTOP306 Industrial Touch Panel
  • UNIOP CP04F-04-0045 HMI Panel
  • UNIOP ETOP308U301 HMI Touch Panel
  • UNIOP MD00R-02-0045 Operator Panel
  • UNIOP ePALM10-0061 Handheld Teach Pendant
  • UNIOP CP05R-04-0045 HMI Operator Panel
  • UNIOP MD02R-04-0045 Text-Based Operator Module
  • UNIOP CP02R-04-0021 Compact Operator Panel
  • UNIOP CP04F-04-1945 Industrial HMI Control Panel
  • UNIOP ECT-16-0045 Communication Module Data Sheet
  • UNIOP EPALM10-0061 Handheld HMI Technical Specifications
  • UNIOP ERT-16-0042 Remote Terminal Unit
  • UNIOP ePAD04-0046 HMI Controller
  • UNIOP BKDR-16 Operator Interface Display
  • UNIOP MKDR-04-004 Control Unit Panel
  • UNIOP ETOP515U3P1 HMI Touch Panel
  • AMAT 0190-15779 Advanced Controller Module
  • Applied Materials AMAT 0010-23715 Mechanical Assembly
  • AMAT 0190-14502 Communication Interface Module
  • AMAT 0195-14157.RMA Power Distribution Module
  • Applied Materials AMAT 0021-84842 Precision Component
  • AMAT 0190-37519 DC Power Supply
  • AMAT 0100-71267 RF Generator Module
  • ALSTOM V4561484-0100 Analog Input Module
  • ALSTOM PIB903 Process Interface Board
  • ALSTOM 029.202.781 Protection Relay
  • ALSTOM 029.148.924 Enhanced Motor Relay
  • ALSTOM 029.148.906 Motor Protection Relay
  • ALSTOM 029.147.908 Transformer Protection Relay
  • ALSTOM 029.144.456 Advanced Feeder Relay
  • ALSTOM 029.144.440 Feeder Protection Relay
  • ALSTOM P40 AGILE MiCOM P141 Feeder Protection Relay
  • ALSTOM I/OBE2 12004-104-00 V1.0.0 I/O Interface Module
  • ALSTOM V4561983-0100 Industrial Control Module
  • ALSTOM VOOB8-B 12004-106-04 V1.0.0 Output Interface Board
  • ALSTOM VPS 12004-102-03 V1.0.0 Voltage Processing Board
  • ALSTOM POS1846 TRVC062333000 CP00000310 Position Control Module
  • ALSTOM DSI1817 TRVC062335000 CP00003934 Digital Input Module
  • ALSTOM CMP1838 TRVCO62345000 CP00005202 Processor Module
  • ALSTOM STO1726KO1 Integrated Control Module
  • ALSTOM I/OBUS2 12004-103-01 VER:V1.2.0 Communication Interface
  • ALSTOM 730475-D ELEMENTS-F2 Cabinet Heater
  • ALSTOM N897163510Q / N897163050Q MODEM and N897163100U Interface Unit
  • ALSTOM N897066 AOVD Analog Output Module
  • ALSTOM CMU 42015-115-00 Communication Unit
  • ALSTOM NRD108028 Digital Protection Relay
  • ALSTOM 42011-106-00 ITC_VIOM_VIOC VER.A01 Interface Card
  • ALSTOM N897093511D DIAGNOSTICA N897093400H Interface Unit
  • ALSTOM N895609510K N895609010R E32OUT Digital Output Module
  • ALSTOM MLU VER.A01 Main Logic Unit
  • ALSTOM NRD109475 8RDA44670G01 SA44670.E Control Module
  • ALSTOM VIIB16-C 12011-105-00 Interface Board Module
  • ALSTOM VCS232 590.043158 Control System Module
  • ALSTOM V0701596-001102 Industrial Control Module
  • ALSTOM N895313512X N95313012D SUP-AL Control Module
  • ALSTOM 12004-102-01 VPS Board Ver.C Power Control Board
  • ALSTOM NRD108034 8RDB44674G01 SA44674.C Control Card
  • ALSTOM N897092520B N897092057Y TRENO N897092500E
  • ALSTOM NRD108033 8RDC44667G01 SA44667.C Control Circuit Board
  • ALSTOM TRVC062105000 TRVC070938000 Series Specification
  • ALSTOM SDK-C0147 12004-101-00 SBS04M17C Control Module Technicals
  • ALSTOM N895313512X Digital Output Module
  • ALSTOM P70035W82V Feeder Protection Relay
  • ALSTOM N897164624A Digital Input Module
  • ALSTOM N897164611M Power Supply Module
  • ALSTOM N897164610L Communication Interface Module
  • ALSTOM N70032702L Protection Relay Module for Power Systems
  • ALSTOM MVAJ21L1GB0771B Voltage Protection Relay
  • ALSTOM MFAC34N1AA0001A Overcurrent Protection Relay
  • ALSTOM MCTI40N1AB0751G Current Differential Protection Relay
  • ALSTOM MCGG22L1CB0753E Overcurrent Protection Relay
  • ALSTOM MVAW 11B1AB0513A Trip Circuit Supervision Relay
  • ALSTOM MVTU 11K1CD0751G Voltage Transformer Supervision
  • ALSTOM MVAJ27L1FB0784D High Speed Tripping Relay Guide
  • ALSTOM MAVS01L1AB0501D Voltage Selection Relay Documentation
  • ALSTOM MVAW11B1AB9007A Trip Circuit Supervision Relay
  • ALSTOM MFAC14K1AA0001A Feeder Protection Relay
  • ALSTOM MCGG62N1CB0753F Generator Protection Relay
  • ALSTOM MAVS01L1AB0751D Protection Relay
  • ALSTOM PIB1201A 3BEC0067 Interface Module
  • ALSTOM V4555724-0100 Voltage Protection Relay
  • BENTLY 1900/65A-01-01-03-00-01 Monitor
  • BENTLY 3500/42-01-00 Proximitor Monitor
  • BENTLY 3500/54-03-00 Temperature Monitor