Technical specifications and certification
Input characteristics:
Frequency range: 47-70 Hz (50 Hz system)/56.5-70 Hz (60 Hz system)
In low-frequency sensitivity mode, it can be as low as 40 Hz
Output characteristics:
Voltage accuracy: 230 V (+6%/-10%)
Frequency accuracy: 50/60 Hz ± 0.1% (automatic tracking)
Battery backup time (50%/70% load):
5P 650:9/6 minutes
5P 850:12/7 minutes
5P 1150:12/7 minutes
5P 1550:13/8 minutes
Environment and Certification:
Working temperature: 0-35 ° C
Noise level:<40 dB (5P 1550 is 40 dB)
Safety standards: IEC/EN 62040-1, UL 1778
EMC and Performance: IEC/EN 62040-2, IEC/EN 62040-3
Certification: CE, CB report (TUV)
Size and weight (taking 5P 1550 as an example):
Tower type: 230 × 150 × 445 mm, 15.6 kg
Rack mounted 1U: 43.2 × 438 × 554 mm, 19.4 kg
Deployment flexibility and attachment support
Tower and rack conversion: All models support two installation methods, adapting to different computer room layouts.
Hot swappable battery: The battery module can be replaced without tools to ensure continuous operation.
Hot swappable maintenance bypass module: allows for the replacement of the entire UPS without interrupting the load, greatly improving availability.
Multiple output socket configurations: Depending on the model, 4-8 IEC C13 sockets are provided, with two groups being controlled sockets.
Applicable scenarios
Server and storage devices: Provide pure sine wave power for rack mounted servers and storage arrays to ensure data integrity.
Network equipment: Protect critical network facilities such as switches, routers, and firewalls to prevent network interruptions.
Edge computing node: applicable to edge computer rooms with limited space. 1U high-density design saves cabinet space.
Industrial control: provides voltage stabilization and backup protection for industrial PC, PLC and other equipment.