Type 1 IP30 (adapted) cleanroom (such as electronic workshop) -10~+40 ℃ space heater, blower starter
Type 12 IP54 (external heat sink) for dusty environments (such as machinery factories) -10~+50 ℃ external heat sink adapter
Type 3R IP54 (weatherproof) outdoor/humid environment (such as pump station) -10~+50 ℃ (optional 50 ℃ adaptation) independent support leg (UUX000923, 12 inches), lightning arrester
Technical parameters and environment Derating
1. Key technical specifications
Project specification description
Output frequency 0-590Hz
Control mode: open-loop/closed-loop vector, open-loop/closed-loop V/f
Motor compatibility sensitive motor, surface permanent magnet motor (SPM), built-in permanent magnet motor (IPM), synchronous reluctance motor
Standard I/O with 8 digital inputs (24Vdc), 3 analog inputs (0 ± 10V/4-20mA), and 3 relay outputs
Safe Torque Off (STO), SIL3 (IEC 62061), PLe (ISO 13849-1)
Certified UL, CSA, CE, RCM, RoHS, SEMI-F47, IEEE1668
2. Derating rules for the environment
Temperature Derating:
When the ambient temperature is greater than 40 ℃ (Type 1)/greater than 50 ℃ (IP20), for every 1 ℃ increase, the output current will decrease by 2%
Altitude Derating:
≤ 1000m: No capacity reduction
1000-4000m: For every 1000m increase, the output current decreases by 8%
Voltage Derating (altitude>2000m):
Neutral grounding system: No need to reduce capacity
Non neutral grounding system: higher voltage level needs to be selected (such as 600V frequency converter for 480V scenario)

Email:wang@kongjiangauto.com