Introduction
BENDER series GPM ground and power modules provide a combination of hospital grade power receptacles and/or ground jacks to satisfy the requirements of general and critical care areas. Straight blade (single or duplex) and twist-to-lock receptacles may be provided. Also available are hospital grade ground cords to facilitate the implementation of an equal-potential environment.
Ground and power modules are designed in strict compliance with UL467, UL50, the NFPA 70 (National Electric Code), and NFPA 99.
General
GPM modules are available with hospital grade receptacles and/or ground jacks. When provided in a backbox, a ground bus arrangement may also be provided. GPM modules may also be provided without receptacles or ground jacks to serve as a collection point for all room grounding conductors.
Backbox
GPM modules are available mounted on stainless steel wall plates that are compatible with standard contractor supplied electrical gang boxes (with or without plaster ring).
Modules (GPM-F, GPM-S models) are also available on a custom front trim for use in a 12" x 8" x 4" backbox. Surface mounted enclosures are finished with a coat of hospital grade epoxy enamel or equivalent. See ordering information for available configurations.
Power Receptacles and Ground Jacks
GPM modules customized on a standard gang wall plate can accommodate either one power receptacle, or one ground jack per gang. Power receptacles are available in either straight blade single, straight-blade duplex, and twist-to-lock styles.
GPM modules customized on a faceplate are available in similar combinations with up to four (4) sections. Each section may accommodate one of the following combinations: One power receptacle and one ground jack, one power receptacle, or two ground jacks.
A reference bus connects the ground jacks. A lug connected to the bus serves as a connection point to the system's equal-potential grounding system.

Ground Bus
GPM modules customized on a faceplate are provided with a ground bus. The ground bus is constructed from highly conductive metal bar stock. The assembly contains minimum nineteen #14-4 screw connections for the attachment of grounding conductors. It also has one #4-2/0 lug for the system grounding conductor. The main ground connection in the module accommodates a #4-1/0 cable.
Additional ground bus configurations are available upon request.
Features
• Applications: Hospital Grade outlet devices for supply and grounding of portable equipment
• Features: Can contain hospital grade power receptacles, hospital grade ground jacks, and/or aluminum or copper ground buses
• Mounting: Available for flush or surface mounted applications
Typical models and configurations
Model configuration description Product number
GPM-F4DR4 4 grounding sockets+4 red dual sockets (embedded) B521300405
GPM-F4NN0 4 grounding sockets (embedded, no socket) B521300349
GPM-F0NN0 grounding bar only (≥ 20 connection points, embedded) B521300400
GPM-G4NN0 4-panel panel+4 grounding sockets B521301103
GPM-G4DR4 8-panel+4 grounding sockets+4 red dual sockets B521300408
Bottom box B120804 12 "× 8" × 4 "embedded galvanized steel bottom box B521300367
Grounding cable HGC-10L 10 feet, plug+# 10 terminal B521300053
Grounding socket HGJ-1R 30A/250V green hospital grade grounding socket B521300010
Product features and advantages
Safety compliance: fully compliant with electrical standards in the medical industry, hospital level certification, ensuring the safety of patients and medical staff;
Flexible configuration: supports various combinations such as sockets, grounding sockets, and pure grounding bars to adapt to different medical scenarios;
Durable design: The 304 stainless steel panel is corrosion-resistant and easy to clean, while the galvanized steel bottom box is sturdy and durable, meeting the requirements of medical environments;
Equipotential protection: Integrated copper grounding bar to achieve equipotential connection of all equipment and reduce the risk of electric shock;
Complete package: Provide grounding cables of different lengths to meet the flexible grounding needs of portable devices.