Product Overview
Bender LINETRAXX ® The CTUB100 series is an AC/DC sensitive measuring current transformer designed specifically for residual current monitoring. It adopts a "electronic module+transformer core" modular structure that can be combined. Its core advantages include supporting AC/DC current signal conversion, replaceable modules (without separating primary conductors), adaptability to multiple evaluation devices, and some models have full magnetic shielding, which can withstand high load currents and surge currents. The product complies with international and railway industry standards and is widely used in industrial control systems, railway vehicles, and other scenarios that require high accuracy and stability in current monitoring.
Core components and specification parameters
(1) Types and Differences of Electronic Modules
Module model, power supply voltage adaptation equipment, key characteristics, product number
CTUB101 DC ± 12V RCMA420/423 with T terminal, output full range 8A B78120050
CTUB102 DC24V RCMS4 series, EDS441-LAB replaces CTUB104, supports maximum positioning current of 25mA B78120051
CTUB105 DC24V RCMS4 series measurement range 3 fixed non adjustable B78120054
(2) Specification of transformer core
Is the inner diameter of the iron core model equipped with magnetic shielding and weight? Product number
CTBC20 20mm No ≤ 230g B98120001
CTBC20P 20mm is ≤ 290g B98120002
CTBC35 35mm No ≤ 310g B98120003
CTBC35P 35mm is 390g B98120004
CTBC60 60mm No ≤ 530g B98120005
CTBC60P 60mm is ≤ 690g B98120006
CTBC120 120mm No ≤ 1460g B98120007
CTBC120P 120mm is 1820g B98120020
CTBC210 210mm No ≤ 4290g B98120008
CTBC210P 210mm is 4940g B98120021
(3) Core technical parameters
Category specific parameters
Output characteristics: Output terminals S1 (k) and S2 (l); Scale 400mV/1A; Maximum voltage ± 10V
Power supply requirements CTUB101: DC ± 12V; CTUB102/105: DC24V
Environmental adaptability working temperature -25 ℃~70 ℃; Climate grade 3K22 (fixed use)
Mechanical characteristics Mechanical grade 3M11 (fixed use); Support any installation location
Connection standard wire type: Copper wire 0.2~1.5mm ² (rigid/flexible); Terminal type DFMC 1.5/4-ST-3.5 BK
The protection level of internal components for security protection is IP40; Terminal protection level IP20; Flame retardant grade UL94V-0

Installation and wiring specifications
(1) Installation requirements
All current carrying cables must pass through the core of the transformer, and protective conductors and low resistance conductor circuits must not pass through the core;
Avoid placing connecting cables (power supply, secondary connections, etc.) directly close to the transformer core to prevent interference pulses;
A conductor bending must meet the minimum distance requirement (90 ° angle distance=2 x conductor outer diameter) and be aligned with the center of the transformer;
Fixing method: M5 screws are used for CTBC20 (P)~CTBC60 (P), and M6 screws are used for CTBC120 (P)~CTBC210 (P), with tightening torques of 0.6km and 1km respectively.
(2) Wiring specifications
When multiple transformers are powered, star connections (such as through potential dividers) should be used, and daisy chain connections are prohibited;
60/75 ℃ rated copper wire must be used, with a maximum connection cable length of 10m;
Special cables are required to connect with the evaluation equipment: CTX series for RCMA420/423, CTXS series for RCMS4 series/EDS441-LAB;
Two types of surge protectors (such as Finder 7P.22.8.275.1020) need to be installed upstream of the power supply unit.
(3) Measurement range setting (applicable to CTUB101/102)
Potentiometer setting evaluation equipment response value I ∆ n effective value measurement range peak measurement range
1 ≤0.1A 0~450mA 0~900mA
2 0.1A<I∆n≤0.5A 0~0.75A 0~3.5A
3 >0.5A 0~10A 0~20A
System status and LED indication
System Status Green LED Red LED Description
The device is turned off and extinguished. The device is not powered on
Normal operation, constant on/off, normal power supply, good connection between electronic module and iron core
The device has malfunctioned and is flashing. The power supply is normal, but the iron core connection is abnormal or there are other device malfunctions
Key issues
Question 1: What is the core component combination logic of the CTUB100 series? What are the differences in adaptation scenarios for different electronic modules?
Answer: The core combination logic is "electronic module+transformer core", and any electronic module can be combined with all CTBC series cores to form a complete transformer. The adaptation scenarios of different electronic modules differ as follows: ① CTUB101 (DC ± 12V): only compatible with RCMA420/423 series evaluation equipment, including T terminal, suitable for industrial circuit monitoring that requires bipolar power supply; ② CTUB102 (DC24V): compatible with RCMS4 series evaluation equipment and EDS441-LAB, can replace CTUB104, supports a maximum positioning current of 25mA, and is suitable for multi scene compatibility requirements; ③ CTUB105 (DC24V): Only compatible with RCMS4 series, with a fixed and non adjustable measurement range of 3, suitable for fixed monitoring scenarios that do not require flexible range adjustment.
Email:wang@kongjiangauto.com