PCD2.F2100: RS-422/485+optional PCD7.F1xS, 110 mA
PCD2.F2150: BACnet MS/TP RS-485+optional PCD7.F1xS
PCD2.F2210: RS-232+optional PCD7.F1xS
PCD2.F2400:LonWorks ® interface module
PCD2.F2610: DALI master station, up to 64 DALI devices
PCD2. F27x0: M-Bus master station, dual M-Bus interfaces, 70 mA (5V)+8 mA (24V)
PCD2.F2810: Belimo MP-Bus+optional PCD7.F1xS
2.8 Typical Applications
Automation and Control of Small and Medium sized Devices
Modernization and functional enhancement of existing equipment
As a gateway connecting different bus systems (such as EIB/KNX, M-Bus, Modbus)
Optimize free parameters such as cooling system and heating system
EIB/KNX integration providing web connectivity for conference rooms
As an M-Bus communication interface in regional heating networks

PCD1. Room (M2110R1): Room Automation Dedicated Controller
PCD1. Room is a programmable room controller designed specifically for complex room automation and HVAC solutions, providing a wide range of communication options. In addition to integrated I/O, it also provides a free I/O slot for personalized expansion (input/output or communication). The onboard web/IT functionality supports mobile operations. This controller can achieve efficient room automation that complies with EN 15232:2012 energy efficiency levels.
3.1 Technical specifications (main differences from M2xxx)
Program memory: 256 kB Flash
User memory: 128 kB RAM
File System: 8 MB
Integrated communication: Ethernet dual port switch, USB, RS-485 (same as M2xxx)
Automated server: supports Flash, file system FTP、Web、Email、SNMP
3.2 Onboard I/O (Enhanced)
Input:
6-way digital input (4+2 interrupt), same as M2xxx
2-channel universal analog input (terminal X1): -10...+10 V, 0... ± 20 mA, Pt1000, Ni1000 L&S, 0... 2.5 k Ω, 12 bits
4-channel dedicated analog input (EA 1 slot): 0... 10 V, 0 (4)... 20 mA, Pt1000, Pt500, Ni1000, 14 bit resolution
output:
4-channel digital output (24 VDC/0.5 A)
1 PWM output (24 VDC/0.2 A)
2-channel analog output (EA 1 slot): 0... 10 V or 0 (4)... 20 mA, 12 bits, configurable through PG5
Configurable (via PG5):
4-channel digital input/output (terminal X0)
Watchdog relay (terminal X3)
3.3 Expansion Limitations and Special Instructions
Only supports one I/O slot (I/O 0): can be inserted into a PCD2.M5 I/O module or a PCD2.F2xxx communication module (up to 1 F2xxx module).
Slot I/O 1 pre installed with PCD2.W525 module: This module is part of the default configuration of the controller, and if removed, the controller will stop running. Therefore, users are not allowed to freely expand using the I/O 1 slot.
The Smart RIO Manager feature is not supported.
Supports S-Bus and Modbus stations, with a maximum of 10 units.
3.4 Communication Expansion and Memory Expansion (Same as M2xxx Series)
Slot A: PDC7.F1xxx Communication Expansion
Slot M1: PCD7.Rxxx flash module, can activate BACnet IP or LON IP
Slot I/O 0: Optional PCD2.F2150 (BACnet MS/TP), PCD2.F2400 (LON FTT10), etc
3.5 Typical Applications
Radiators, fan coil units, cooling ceilings, VAV (Variable Air Volume) control
Air quality monitoring
Signal contacts (occupancy control, presence detection, window monitoring)
Lighting control, sunshade control
Connect external devices through analog signals, S-Bus, Modbus, BACnet, LON, KNX IP, EnOcean, etc
PCD1 E-Controller (M0160E0): Energy Monitoring Controller for Distribution Box
PCD1.M0160E0 is a compact controller with free programming, pre installed with S-Monitoring application (energy monitoring) at the factory. It is designed specifically for the installation of electrical control cabinets, suitable for distribution units or narrow spaces. In addition to integrating I/O, interface, and Web/IT functions, it also supports multiple protocol connections, making it highly suitable for microcontrollers, communication gateways (EnOcean, KNX, BACnet, etc.), as well as energy consumption data collection, recording, and processing.
4.1 Technical specifications
Program memory: 1 MB Flash
Working memory: 1 MB RAM
File System: 128 MB
Integrated communication: Ethernet (dual port switch), USB, RS-485 (as before)
Automated Server: Supports
Dimensions (W × H × D): 142 × 142 × 60 mm (excluding terminals)
Installation method: Single 35mm top cap rail (DIN EN60715 TH35) or flat installation
4.2 Onboard I/O
Input:
6-way digital input (4+2 interrupt), 15... 30 VDC
2-channel analog input (terminal X1): -10...+10 V, 0... ± 20 mA, Pt1000, Ni1000, Ni1000 L&S, 0... 2.5 k Ω, 12 bits. The default factory configuration is Ni1000 sensor input.
output:
4-channel digital output (24 VDC)
1 PWM output (24 VDC/0.2 A)
Configurable (via PG5):
4-channel digital input or output (terminal X0), factory default configuration is digital input
Watchdog relay (terminal X3)
Note: This model does not have a free I/O slot (no EA slot), only one slot A is used for communication expansion.
4.3 Special Installation Requirements
When installed in the distribution box, a space of 55mm should be left above the DIN rail and 75mm below it.
It is recommended to use elbows or flexible Ethernet cables (such as SlimWire PRO) for Ethernet cables, otherwise it may not be possible to close the distribution box cover.