Introduction
In the field of modern generator system management and power distribution, intelligent circuit breaker control units play a crucial role. The easyYgen LS-6XT series launched by Woodward is a high-performance control unit designed to meet this demand. As an industrial grade product designed in Germany, LS-6XT not only has excellent reliability, but also provides flexible configuration options and wide application compatibility. This article will delve into the technical characteristics, installation requirements, configuration methods, and practical application scenarios of the device, providing a comprehensive reference guide for engineers and technicians.
Product Overview and Technical Features
1.1 Product positioning and functions
The Woodward easyYgen LS-6XT series is a circuit breaker control unit designed specifically for engine generator system management. This device can be used as an independent unit or combined with Woodward easyYgen-3400/3500XT generator control unit and/or easyYgen | GC-3400XT to form a complete power management system.
The core functions of LS-6XT include:
Dual circuit breaker control (CBA and CBB modes)
System synchronization check and grid connection function
Real time monitoring of power parameters (voltage, current, frequency, power, power factor)
Advanced protection functions (overvoltage, undervoltage, overclocking, underflocking, etc.)
Multiple communication interface support (CAN, Ethernet, RS-485, USB)
Programmable Logic Manager ™) Analog Manager ™)
1.2 Technical Specifications Highlights
According to Chapter 8 "Technical Specifications" of the technical manual, LS-6XT has the following key characteristics:
Measurement performance:
Voltage measurement range: 0-690V AC (phase voltage)
Current measurement range: compatible with 1A/5A CT
Frequency measurement range: 0-75Hz
Power measurement accuracy: ± 0.5% of rated value
Real time clock battery: lithium battery backup
Environmental adaptability:
Working temperature: -25 ° C to+70 ° C
Storage temperature: -40 ° C to+85 ° C
Protection level: Complies with UL standards and is suitable for Type 1 enclosures
Humidity range: 5% to 95% relative humidity (non condensing)
Interface capability:
3 Ethernet ports (10/100Base-T)
CAN bus interface (supporting CANopen protocol)
RS-485 serial interface
USB 2.0 service port
12 digital inputs/12 relay outputs
3 analog inputs/2 analog outputs
1.3 Hardware Configuration and Packaging Content
The standard delivery scope includes:
EasyYgen LS-6XT equipment body
All pluggable terminal connectors
Installation Program Supplemental Instructions (IPS) and Printed QR Code Labels (2 copies)
Configuration files and technical manuals stored in the internal memory of the device
It is worth noting that the documents stored inside the device are in "delivery status" and may not be the latest version. The latest version needs to be obtained from Woodward's official website.
Safety regulations and installation requirements
2.1 Safety precautions
Section 1.3 of the technical manual emphasizes the important safety regulations that must be followed when using LS-6XT:
Personnel qualification requirements:
Electrical work must be carried out by qualified electricians
Operators need to receive relevant training and be familiar with all applicable regulations
Prohibit personnel under the influence of alcohol and drugs from operating equipment
Electrical safety measures:
Ensure that the system is powered off and prevent accidental restarts before operation
Voltage measurement input requires 2-6A slow melting fuse
One end of the CT secondary side must be grounded nearby
The power line requires the use of cables with a temperature rating of not less than 90 ° C
Anti static protection:
Release static electricity by touching grounded metal objects before operation
Suggest using an ESD wristband
Avoid wearing synthetic fiber clothing
Keep plastic and vinyl materials away from the work area
2.2 Mechanical Installation
For the sheet metal shell model (LS-612XT-P1), installation should follow the following steps:
Hole positioning: Drill installation holes according to the hole spacing of 42.45 × 96.2mm
Equipment fixation: Use screws with a maximum diameter of 6mm (M6) for fixation
Torque control: Tighten according to the required torque of the screw quality grade
Wiring space: Ensure sufficient operating space above and below the terminals
Key installation dimensions:
Equipment width: 250mm
Installation hole spacing: horizontal 42.45mm, vertical 96.2mm
Maximum wire diameter: The terminal supports a maximum of 2.5mm ² wire
2.3 Electrical Connections
Power connection:
Power range: 8-40V DC (nominal 12/24V)
Positive terminal connected to terminal 63, negative terminal connected to terminal 64
Protective grounding (PE) connected to the bottom center of the sheet metal shell
Suggest using 6A fuses or C-type miniature circuit breakers for protection
Voltage measurement connection:
System A voltage: terminals 30-36
System B voltage: terminals 22-28
Auxiliary voltage: terminals 38-40