Supports multiple wiring configurations: 3-phase 4-wire, 3-phase 3-wire, 1-phase 3-wire, 1-phase 2-wire
Current measurement connection:
System A current: terminals 3-8 (L1, L2, L3 phases)
System B current: terminals 1-2 (single-phase)
The CT direction should be based on the software version. Note that version 2.10-0 points to system A, while version 2.10-1 and above points to system B
Power measurement configuration:
CBA mode: measuring power flow between system A and system B
CBA/BBB mode: Simultaneously monitor the power status of two circuit breakers
The definition of power factor follows international standards (inductive load is positive, capacitive load is negative)

System configuration and parameter settings
3.1 Access Level and Password System
LS-6XT adopts a multi-level password protection system, providing 5 access levels:
Basic level (CL01): Restricted viewing permission, no configuration permission
Temporary debugging level (AC02): Algorithm code access, expires after session ends
Debugging Level (CL03): General Debugging Parameter Access
Temporary Super Debugging Level (AC04): Algorithm Code Access Advanced Features
Super Debugging Level (CL05): Almost Full Access (except for calibration and super user items)
Access channels include:
Local HMI of the device (basic code input)
USB connection ToolKit (user account login)
Ethernet remote panel (user account login)
Third party devices use Modbus TCP/CANopen/RS-485
3.2 HMI Operation and Navigation
The main screen of the device is divided into five main areas:
Numerical display area: real-time data such as voltage, current, frequency, power, etc
Status message area: operating mode, device status
Alarm message area: Latest unconfirmed alarm
Single line diagram area: visualization of circuit breaker status and power flow direction
Soft key function area: Navigation and operation control
Special function screen:
Customer customized screen: up to 18 customizable monitoring values can be configured
Synchronous oscilloscope: visually display the phase difference between system A and B
Logic Manager: Visualize Logic Conditions and Variable States
Event history: system event records with timestamps
3.3 Key parameter configuration
Language and clock settings:
Supports English, German, and one reserved language
Real time clock with configurable time zone and daylight saving time rules
Network time can be synchronized through SNTP protocol
Measurement configuration:
Voltage Transformer Ratio Setting (Parameters 1800, 1803, 1812)
Current Transformer Ratio and Direction Configuration
Definition of power measurement symbols (based on CT installation direction)
Circuit breaker configuration:
Operation mode selection: manual/automatic
Synchronization parameters: frequency difference, voltage difference, phase angle, dwell time
Dead bus closure condition setting
Logical Command Configuration (AMF Function)
Monitoring function configuration:
System A/B protection: overvoltage, undervoltage, overclocking, underfrequency, voltage asymmetry, etc
Circuit breaker monitoring: closing transition monitoring, unloading mismatch detection
Communication monitoring: CAN, Ethernet, multi unit system status
Application Mode and Advanced Features
4.1 Application layer architecture
LS-6XT supports a two-tier application architecture:
Layer 1: Generator Unit Layer
Communicate with easyYgen-3000XT and other LS-6XT
Support CBA or CBA/BBB circuit breaker modes
Special application modes: L-MCB, L-GGB, L-MCB/GGB
Main power failure detection and main power decoupling
Layer 3: Power Station Layer
Communicate with group controller (GC) and other LS-6XT
Support CBA or CBA/BBB circuit breaker modes
Main power fault detection and decoupling (GCB)
4.2 Synchronization check function
As a redundancy check function, synchronous inspection enhances system security:
Available command variables:
02.29 Synchronization conditions: dependent on voltage, frequency, and phase angle
02.30 Dead bus closure condition: depends on system A/B voltage and dead bus configuration
02.28 Synchronization check relay: Triggered when any of the above conditions are met
Key parameters:
Positive/Negative Frequency Difference CBA (5711/5712)
Voltage difference CBA (5710)
Maximum positive/negative phase angle CBA (5713/5714)
Phase matching dwell time CBA (5717)
4.3 Expansion of External I/O Modules
External I/O modules can be connected via CAN1 bus:
IKD1: Up to 2, providing 16DI/16DO
IKD-IN-16:1, providing 16DI
IKD-OUT-16:1, providing 16DO
The configuration tool can be accessed through ToolKit and supports flexible digital input monitoring and relay output control.
4.4 Communication and Protocol Support
CAN interface:
CAN1 interface supports CANopen protocol
Support Process Data Objects (PDO) and Service Data Objects (SDO)
Configurable load balancing communication parameters
Ethernet interface:
Three independent 10/100Base-T ports
Supports Modbus TCP/IP protocol
Remote Panel Access (RP-3000XT)
System interconnection function (new feature)
Serial interface:
RS-485 supports half duplex/full duplex operation
Modbus RTU protocol
USB 2.0 Device Interface (ToolKit Connection)
Load balancing:
Broadcast messages via CAN bus or UDP (Ethernet)
Configurable transmission rate and timeout period