Lauer LHT-T100t-Ne Control Panel
The Lauer LHT-T100t-Ne (version V16-10-10) is a modern operator control panel featuring a 10-inch TFT display with resistive touch. It operates on a 24 V DC supply with a current consumption of 1.25 A, making it energy-efficient and compatible with standard industrial power systems. This panel is built for machine control, process visualization, and data entry in a variety of industrial applications, offering a balance of performance and affordability.
Technical Specifications
Display: 10-inch TFT, 1024 x 600 pixels (WSVGA), 16.7 million colors, LED backlight, 350 cd/m², 500:1 contrast.
Touchscreen: 4-wire resistive, 1 million actuations, anti-glare coating.
Processor: ARM Cortex-A8, 800 MHz, 512 MB RAM, 256 MB flash (expandable via microSD).
Interfaces: 1 x RS232, 1 x RS422/485, 1 x Ethernet 10/100, 2 x USB 2.0 host, 1 x USB device, 1 x microSD slot.
Power Supply: 24 V DC (18–30 V), consumption 1.25 A (approx. 30 W).
Operating Temperature: 0 °C to 50 °C.
Storage Temperature: -20 °C to 70 °C.
Humidity: 10% to 90% non-condensing.
Protection: Front IP65, rear IP20.
Mounting: Panel mount, cutout 280 x 180 mm, depth 55 mm.
Weight: 2.2 kg.
Real-time clock with battery.
Buzzer and status LEDs.
Functional Features
The LHT-T100t-Ne supports a wide range of communication protocols including Modbus RTU/TCP, Siemens S7, Allen-Bradley DF1, Mitsubishi FX, and Omron Host Link. It includes a built-in web server for remote access and diagnostics. The panel can log data to USB or microSD, store up to 5,000 alarm events, and support recipe management. Configuration is performed using Lauer Configurator Pro, which provides a rich library of graphical objects, trend charts, and animation.
Additional features include multi-language text, password-protected user levels, screen saver, adjustable backlight dimming, and a watchdog timer for automatic system reset.
Installation Guidelines
Mount the panel in a panel cutout using the supplied clips and sealing gasket. Connect the 24 V DC power supply with a 2 A fuse. For RS485, use shielded twisted-pair cable with 120 Ω termination. For Ethernet, use CAT5e. Ensure proper grounding and avoid routing signal cables parallel to power cables. Provide at least 60 mm clearance behind the panel for ventilation and cable connections.
Operating Conditions
Indoor industrial use, temperature 0–50 °C, humidity<90% non-condensing. Vibration tolerance 0.5 g (10–150 Hz), shock 10 g (11 ms). Backlight lifetime 50,000 hours.
Applications
Ideal for packaging machinery, conveyor systems, printing equipment, textile machines, and general industrial automation.
Compliance
CE, UL, and cUL certified. RoHS compliant. Meets EN 61000-6-2 and EN 61000-6-4.
Ordering Variants
Available with optional Profibus, CANopen, or Ethernet/IP modules. Extended temperature range and higher brightness (500 cd/m²) options available.