Lauer PCS 8010 Operator Panel
The Lauer PCS 8010 (variant 8010 A 00629) is a versatile operator panel designed for a wide range of industrial applications. With its 8-inch TFT color display, resistive touch, and comprehensive communication ports, it provides a reliable human-machine interface for machinery control, process monitoring, and data acquisition. The panel features a robust metal housing, making it suitable for harsh factory environments, and its modular design allows for easy integration into existing systems.
Technical Specifications
Display: 8-inch TFT, 800 x 600 pixels (SVGA), 16.7 million colors, LED backlight, 350 cd/m², 500:1 contrast, viewing angle 75°/75°/60°/60°.
Touchscreen: 4-wire resistive, 1 million actuations, anti-glare.
Processor: ARM Cortex-A8, 800 MHz, 512 MB RAM, 256 MB flash (expandable via SD).
Interfaces: 1 x RS232, 1 x RS422/485, 1 x Ethernet 10/100, 2 x USB 2.0 host, 1 x USB device, 1 x microSD slot, 1 x CAN (optional).
Power Supply: 24 V DC (18–30 V), consumption 10 W.
Operating Temperature: 0 °C to 50 °C.
Storage Temperature: -20 °C to 70 °C.
Humidity: 10% to 90% non-condensing.
Protection: Front IP65, rear IP20.
Mounting: Panel mount, cutout 225 x 170 mm, depth 50 mm.
Weight: 1.8 kg.
Real-time clock with battery.
Buzzer and status LEDs.
Functional Features
The PCS 8010 supports a wide range of communication drivers including Modbus RTU/TCP, Siemens S7, Allen-Bradley DF1, Mitsubishi FX, and Omron Host Link. It includes a built-in web server for remote access and diagnostics, and it can log data to USB or microSD. The panel is programmed using Lauer Configurator Pro, which offers a rich object library, trend charts, alarm management, and recipe handling. The unit supports multi-language text and up to 10 user levels with password protection.
Additional features include screen saver, adjustable backlight dimming, and a watchdog timer for automatic reset. The Ethernet port supports DHCP and static IP, and the USB ports allow connection of external storage or peripherals.
Installation Guidelines
Mount the panel in a panel cutout with the supplied clips and gasket. Connect the 24 V DC power supply with a 1 A fuse. For RS485, use shielded twisted-pair cable with 120 Ω termination resistors. For Ethernet, use CAT5e cable. Connect the USB ports for project download or data transfer. Ensure adequate rear clearance for cables and ventilation.
Ground the panel to the main earth. Avoid placing near high-voltage equipment or heat sources.
Operating Conditions
Indoor use, 0–50 °C, humidity<90%. Vibration 0.5 g (10–150 Hz), shock 10 g (11 ms). Backlight life 50,000 hours.
Applications
Commonly used in packaging lines, conveyor systems, printing presses, textile machinery, and test equipment. Also suitable for building automation and process control.
Compliance
CE, UL, and cUL certified. RoHS compliant. Meets EN 61000-6-2 and EN 61000-6-4.
Ordering Variants
Available with optional CAN, Profibus, or Ethernet/IP modules. Extended temperature range and higher brightness options are offered.