ABB Advant Controller 450 Controller
Product positioning and core advantages
AC 450 is a process controller suitable for high demand industrial applications, with the main features including:
Upgrade and compatibility: As an upgrade path for MasterPiece 200, it supports a longer lifecycle and can be fully integrated with System 800xA systems.
High performance and scalability: With high processing capabilities, it is suitable for complex applications and can support process expansion while controlling engineering costs.
High availability: Supports redundant backup of communication, power, CPU, and I/O boards to ensure high availability of the factory.
Multi protocol support: compatible with multiple communication protocols such as MODBUS, Profibus, Masterbus 300/300E, Advant Fieldbus 100, etc., facilitating the construction of optimized control system architectures.
I/O Capacity and Configuration
1. S100 I/O capacity
Supports up to 5 S100 I/O racks and 100 S100 I/O modules.
The maximum number of analog input/output modules is 32, and the maximum number of digital input/output modules is 48.
Note: Up to 25 S100 I/O racks can be connected through optical bus expansion.
2. S800 I/O capacity
Each Advant Fieldbus supports up to 79 S800 I/O stations (if there are other stations on the bus, they need to be reduced accordingly).
Each I/O station can have up to 24 S800 I/O modules (without optical expansion).
3. Total I/O capacity (S100+S800)
Total I/O channels: up to 5700.
Analog inputs (including calculated values): up to 910; Analog output (including calculated values): up to 963.
Number input (including calculated values): up to 2340; Digital output (including calculated values): up to 1489.
Other features: Each channel is equipped with LED status indicator lights, and the longest on-site cable length is 300 meters.
Hardware Options
CPU and Redundancy: Up to 2 redundant CPU boards (PM511), supporting dual redundancy configuration.
Submodule carrier: up to 6 SC520 or 7 SC510, totaling up to 8 modules including CPU.
Communication submodule: up to 12 (with redundant CPUs), supporting multiple interfaces:
V. 24/RS232 (CI531, 2 channels): up to 4;
MasterBus 300/300E (CS513): up to 2 (executed by the main CPU) or 6 (executed by the slave CPU);
Advance Fieldbus 100 (CI522A), Profibus DP (CI541V1): up to 8 each;
Modbus, Allen Bradley DF1 and other protocol interfaces: up to 5 each.
Power supply and auxiliary equipment: up to 2 voltage regulators (SR511), 2 battery chargers (SB510).
Cabinet: Provides RM500V1 (IP21/IP41/IP54, size 800 × 512 × 2125mm) and RM500V2 (IP21/IP41/IP54, size 700 × 637 × 2225mm), which can be combined into multiple cabinet groups.
email:1583694102@qq.com
wang@kongjiangauto.com