Electrical connection planning
General wiring principle: signal lines and power lines should be laid separately to prevent interference; Analog signals (command values, actual values) must use shielded cables; The power line shall not come into contact with the control voltage; Before conducting high-voltage/insulation testing, all wiring of the machine must be removed (permitted according to VDE 0113), and the drive components must undergo high-voltage insulation testing according to VDE 0160 when leaving the factory. Pay attention to electrostatic discharge (ESD) protection - soldering iron, human body, and tools must be grounded, and ESD sensitive components can only be stored in conductive packaging.
List of main interface functions:
X1: Integrated bus connection from adjacent units, 30 pin FBK connector, connected from the power unit to each driver via flat ribbon cable, with a maximum length of 1 meter;
X2: Serial interface (D-SUB 15 pin), RS-232 mode single participant maximum 15 meters, 9600/19200 baud, can be programmed with DriveTop; RS-485 mode supports up to 31 devices with half duplex bus and a maximum distance of 500 meters. The terminal resistance switch of the RS-485 bus terminal device must be set to position I;
X3: Simulate diagnostic output AK1/AK2 (can output driver internal variables for debugging, load 4mA, DC ± 10V), Bb ready contact (DC 24V/1A, minimum load 10mA, ON current should not exceed 1A when directly driving the main contactor, disable varistor protection), and startup lockout AS+/AS -/ASQ (DC 20-30V, 1.5W; note that startup lockout cannot stop the moving shaft);
X4/X4.1/X4.2: Motor feedback 1 interface (HSF or RSF type, D-SUB 15 pin), additional modules are required when using other encoder types; It is strictly prohibited to insert X4 (HSF/Resolver) and X7 (1Vpp) incorrectly. The X7 port is covered with a protective cap when leaving the factory;
X5: Intermediate circuit, motor and power connection (A1/A2/A3+ground), tightening torque: DC bus uniformly 3Nm, motor end HDS02 is 0.5-0.6Nm, HDS03 is 2Nm, HDS04 is 4Nm, HDS05 is 6Nm;
X6: Maintain brake and motor temperature monitoring and external 24V brake power supply, with a maximum allowable braking current of 2A. If exceeded, an external switch device must be used;
X10/X11 (HDD only): SERCOS fiber optic transceiver interface, compliant with IEC/EN 61491, wavelength 640... 675nm, transmission power set to four levels (-7/-4.5/-1/0 dBm) by S4 switch, factory -4.5dBm, data rate S4/1 set to 2 or 4 Mbaud, factory 2 Mbaud;
X12.1/X12.2 (HDD only): External input, evaluation reference switch, travel limit switch, measuring probe and emergency stop, external supply voltage 18-32V, input high level 16-32V, low level ≤ 5.5V.
X7.1/X7.2 high-resolution positioning interface evaluates 1Vpp sine voltage signal, with a signal period of 2048 subdivision, maximum measurement signal frequency A/B 500kHz, reference signal R 15kHz, output power supply DC+5V (± 5%), maximum 150mA. The 1Vpp signal can be branched into multiple DLF01.1 feedback channels through DGA1.2 four-way signal distributor, or connected to a current signal measurement system using power driver DGV01.1.
Cable specifications: Rexroth Indramat finished cables are recommended for power cables, including three power lines, grounding wires, individually shielded temperature monitoring twisted pair cables, individually shielded brake twisted pair cables, and a complete shielding layer; The maximum length of the motor cable is 75 meters (assuming finished cable and ambient temperature ≤ 40 ℃), and the maximum length of the feedback line is 75 meters; The clamping point or coupling will shorten the maximum allowable wire length.
Key points of control cabinet design
Installation: Use the installation rail SUP-M01-HD (order number 271274750mm, shortened as needed), and screws can be installed in grooves. Drivers with high power demand and current should be located as close as possible to the power supply unit, and the shaft load should be evenly distributed on both sides of the power supply under ideal conditions; When the total power Pm is greater than 36kW, it must be evenly distributed on both sides (18kW each) according to the power, except for single axis power exceeding 36kW. The controller must be installed vertically with the motor terminals facing downwards. At least one M5 screw should be used to secure every second slot of the guide rail; The guide rail also serves as a potential compensation function, and the coating on the cabinet board in the installation area must be removed to ensure good contact.
Heat consumption calculation: Total heat consumption inside the cabinet=power unit loss+series switch device loss+sum of losses of each driver. The drive loss consists of control unit loss, configuration related loss (see technical data), and power level loss. The power level loss is read from the loss curve based on the average continuous current. The manual provides four axis examples: HDS04.2-W200N-HS32 spindle (53A, 581.9W)+HDS03.2-W100N-HS30 (219.7W)+HDD02.2 dual axis (143.0W), with a total drive of 944.6W and a power loss of 950W. The control cabinet needs to dissipate 1894.6W of heat - it must be naturally dissipated through the metal structure of the cabinet or carried away by an internal cooling system.