Cooling system: If the temperature is above 45 ℃, it must be operated at a reduced capacity, so a cooling system is usually required. Key anti condensation rules: The layout of the cooling system must ensure that condensed water does not drip or splash onto electronic devices; The cooling temperature setting shall not be lower than 40 ℃; The temperature inside the self regulating cooling system cabinet shall not be lower than the temperature outside the cabinet; Use well sealed cabinets to prevent moisture from entering; When closing the door again after debugging, the cooling system must continue to operate until the air inside the cabinet is at the same temperature as the equipment, otherwise condensation may occur.
Interference suppression: To meet the requirements of DIN VDE 0470-1 Class B (RF interference level N) and DIN EN 55014 limits, the motor power cable must be shielded and fully grounded on the controller side using XS1 shielding fixtures; Install appropriate interference suppression filters on the main power cord; The switching action of inductive loads (contactors, relays, reactors) must be suppressed - three-phase current driven freewheeling diodes are used, AC driven contactors are matched with RC suppression modules, and suppression components must be installed at the suppressed load (otherwise the effect will be greatly reduced). The use of varistors is prohibited; High frequency equipment (such as anodizing device components) should be wired outside the control cabinet. The frequency converter components are only terminal diagram support tools, and the wiring should be based on the terminal diagram provided by the machine manufacturer.
Maintenance and troubleshooting services
The controller outputs fault information through the SERCOS interface and the panel status display H1. The fault codes for the entire DIAX04 line have the same meaning, as described in the corresponding functional description. Repairs can only be performed by Rexroth Indramat customer service or trained and qualified personnel; The process of replacing units and components can be found in the "DIAX04 Troubleshooting Guide", and a restart must be performed after replacing the unit. The drive components have undergone high voltage and insulation testing according to DIN VDE 0160. Before contacting the service, prepare the model data, fault status, error or diagnostic display, and software status of the controller/motor/gearbox. The service hotline is open from 5:00-23:00 CET on weekdays, 8:00-20:00 CET on Saturdays, and 9:00-19:00 CET on Sundays and holidays.