Red/Green "Ready" LED (Core Diagnostic Light):
Meaning of display mode
Constant green module ready
Chang Lianghong Error
The red green flashing valve setting has been changed
Red flashing is not allowed for valve numbers (the rotary switch is in the invalid switch position)
Extinguish module not ready
Green Flash (in settings) Expert settings activated
LED display symbol meanings: DI=enable, t=ramp, Z/B=zero/pilot current, G=command value attenuator, S=command value step level ☺= Ready, four diagonal symbols=quadrants 1-4 (positive command value up/positive command value down/negative command value up/negative command value down) - quadrant indication allows the operator to intuitively confirm the direction of the command value and the slope action status. For detailed description, please refer to operating instruction 30232-B.
Project planning and wiring specifications (core line of defense against failures)
The eight iron rules for wiring:
Maintain maximum possible spatial separation between signal lines and load lines;
Do not pass signal lines through magnetic fields;
Lay signal lines with as few intermediate terminals as possible;
Do not lay signal lines parallel to load lines;
Connect the cable shielding layer (see operating instructions 30232-B);
Digital input/output and command/actual value cables: The maximum allowable length for unshielded cables is 30 meters, and shielded cables are required for longer cables;
Maintain sufficient distance (>1 m) from wireless equipment;
When the working voltage fluctuates strongly, in some cases, it may be necessary to use an external smoothing capacitor with a capacity of at least 2200 µ F.
EMC sensitive environment: Additional measures must be taken according to the application (such as shielding, filtering). Recommended capacitor module VT 11110 (data sheet 30750) - sufficient to support power smoothing for up to 3 amplifier modules.
Heat dissipation and delivery status: The upper and lower ventilation ducts must not be obstructed by adjacent devices to ensure sufficient cooling; The device has been tested in the factory and delivered with default settings - it can operate upon first power on, but the valve type switch position must first be rotated to the corresponding position of the actual valve.
Typical troubleshooting process
Electromagnetic cable breakage protection action with a maximum length of 50 m (1.5 mm ²); Shielded and unshielded 30 meter rule