EATON FP-4000 feeder protection relay

F: | Au:FAN | DA:2026-03-12 | 596 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:


EATON FP-4000 feeder protection relay

Product Overview

Cutler Hammer under Eaton ®  FP-4000 feeder protection relay is a multifunctional protection device based on microprocessors, designed to provide comprehensive monitoring, protection, and control for medium voltage main incoming circuit breakers, bus tie circuit breakers, and feeder circuit breakers. It integrates three-phase overcurrent, ground fault, voltage protection, and energy measurement functions into a compact fixed chassis that meets ANSI and UL standards, significantly reducing panel space, wiring, and costs.

FP-4000 fully utilizes microprocessor technology to provide users with rich data acquisition functions and unprecedented flexibility. It continuously self checks all hardware and firmware protection components to ensure reliable operation in the event of system or component electrical failure. Its protection function is widely applicable to main incoming lines and distribution feeder circuits, and its programmable logic control function makes it particularly suitable for main tie main and dual main incoming line switching schemes.


Application Description

FP-4000 is mainly used in medium voltage switchgear as the primary protection for feeders, incoming lines, and bus tie circuit breakers. It can also serve as a backup protection for transformers, high voltage lines, and differential protection. Its typical applications include:

Main incoming line protection: provides complete overcurrent, ground fault, and voltage protection.

Feedline protection: provides sensitive selective protection for distribution lines.

Bus tie circuit breaker control: supports main bus tie main automatic switching logic to enhance power supply reliability.

Backup protection: Provide reliable backup when upstream or downstream protection fails.

Through the Zone Interlocking function, FP-4000 can directly cooperate with Cutler Hammer Digitrip 3000 and Digitrip MV relays to achieve busbar protection, replacing the expensive and complex busbar differential (87B) scheme. The newly added breaker failure logic can quickly trigger remote backup clearing when the circuit breaker refuses to move, significantly reducing the fault removal time.


Core protection function

FP-4000 provides comprehensive and flexibly configurable protection functions, covering multiple dimensions such as current, voltage, frequency, etc. The following is a list of its main protection functions (see Figure 1 for a single line diagram):

1. Phase overcurrent protection

Two stage instantaneous overcurrent (50P-1, 50P-2): with independent timer, can set instantaneous or short delay.

Inverse time overcurrent (51P-1): Supports 10 standard characteristic curves (such as Mod, Very, Extremely, IECA, IECB, IECC, I ² t, etc.), and can choose instantaneous reset or delayed reset.

Setting range: starting value of 0.1~4.0 pu (step size 0.01), time multiplier of 0.05~10.0 (step size 0.01), instantaneous starting value of 0.1~20.0 pu (step size 0.01).

2. Grounding overcurrent protection

Similarly, it provides both inverse time limit and instantaneous two-level protection, with a setting range similar to phase overcurrent.

3. Voltage imbalance protection (47)

Monitor the ratio of negative sequence voltage to positive sequence voltage (% V2/V1), set a startup threshold of 4% to 40% (step size 1%), and set the minimum voltage threshold (1~100V) with a delay of 0~9999 cycles.

4. Current imbalance protection

Monitor the ratio of negative sequence current to positive sequence current (% I2/I1), with a startup threshold of 4% to 40% (step size 1%), a minimum current threshold of 0.1 to 20.0 pu, and a delay that can be set.

5. Undervoltage/Overvoltage Protection

The voltage setting range is 10~150V (step size 1V), with a delay of 0~9999 cycles.

6. Underfrequency/Overfrequency Protection

The frequency setting range is 45~65 Hz (step size 0.01 Hz), with a delay of 0~9999 cycles.

7. Circuit breaker failure protection

The current starting value is 0.1~5.0 pu (step size 0.01), with a delay of 0~9999 cycles.

8. Power factor protection

Trigger/reset threshold 0.5 lag~0.5 lead (step size 0.01), delay 0~1000 seconds.


Measurement and measurement accuracy

FP-4000 is not only a protective device, but also a high-precision energy meter that provides complete measurement of power parameters:

Phase current accuracy: ± 0.5% or ± 0.025A (0.02-20 pu full offset waveform)

Grounding current accuracy: ± 0.5% full range (0.02~2.0 pu)

Phase voltage accuracy: ± 0.5% or ± 0.2V (0~160 Vac)

Frequency accuracy: ± 0.02 Hz

Phase angle accuracy: ± 1 °

Power accuracy: ± 1.5%

Clock accuracy: Free running ± 1 minute/month (25 ° C), automatically calibrated by PowerNet host

In addition, FP-4000 can record demand, minimum/maximum values, and provide up to 40 days of load trend data to help users optimize energy use.

Event recording and fault analysis

When there is a disturbance or fault in the power system, FP-4000 immediately stores the following data in non-volatile memory:

Voltage and current sampling data

Calculated values (such as power, demand)

Internal protection component status

Logic Input Output Status

Fault recording capability:

Event record: Record the most recent multiple tripping and alarm events with time stamps.

Waveform capture: up to 256 cycles of fault waveforms can be analyzed using PowerNet or specialized waveform viewing software to accurately locate the cause of the fault.

Data logger: provides energy usage profiles for planning and energy efficiency analysis.

These functions greatly simplify post fault analysis and shorten system recovery time.


Control and Programmable Logic

FP-4000 has rich built-in control functions and supports user-defined logic, which can replace external auxiliary relays, timers, and wiring.

Standard control function:

Local switch on/off (front panel button)

Remote opening and closing (via communication)

Circuit breaker tripping circuit monitoring (continuous monitoring of circuit integrity)

Circuit breaker closing circuit monitoring

Vacuum circuit breaker leakage monitoring (residual current monitoring during circuit breaker opening)

Programmable Logic:

6 programmable logic gates (AND, OR, NAND, NOR)

2 latches (triggers)

6 timer gates (adjustable delay ON/OFF)

Up to 4 sets of protection setting groups, which can be switched online

Mother Union Transfer Logic (Used for Master Mother Union Master Scheme)

Through these logics, users can implement complex control schemes, such as automatic backup power supply activation and load shedding.


Communication and Software

FP-4000 supports multiple communication methods, making it easy to integrate into monitoring systems:

Front panel RS-232 port: used for local PC connection, running PowerPort software (free), can read/set settings, monitor data, and retrieve records.

Rear panel RS-485 port: Supports Modbus RTU protocol, used to connect SCADA or power monitoring systems.

Rear panel FSK port: Supports INCOM protocol and seamlessly integrates with Eaton's PowerNet system.

Communication software:

PowerPort: A free tool for on-site debugging and maintenance of a single relay, providing a Windows graphical interface.

PowerNet: A comprehensive energy management software that supports advanced features such as remote monitoring, billing, trend analysis, and event alerts for multiple devices.


Technical specifications and certification

power control

Optional voltage range:

48~125 Vac/dc

100~240 Vac/dc

Operating range: 55~264 Vac, 38~300 Vdc

Interruption tolerance: 20 cycles (rated AC)

Power consumption: maximum 20 VA

current input

Rated value: 1A or 5A

Continuous overload: 2 × In

Short term overload: 50 × In for 1 second

Burden:<0.25 VA @ 5A; <0.05 VA @1A

voltage input

Rated: 120 Vac

Scope of work: 69~150 Vac

Burden:<0.015 VA @ 120 Vac

input

Discrete input: 8 channels, 48Vdc wet contact (provided internally)

Output contacts: 5-way Form A (normally open), 2-channel Form C (conversion)

Contact capacity:

Instantaneous: Close 30A ac/dc (0.25s), disconnect 0.25A @ 250Vdc (resistive), 5A @ 120/240Vac

Continuous: 5A @ 120/240Vac, 5A @ 30Vdc

environmental parameters

Working temperature: -40 ° C~+60 ° C (-40 ° F~+140 ° F), tested to+85 ° C

Storage temperature: -40 ° C~+85 ° C

Humidity: 5%~95% RH (without condensation)

Altitude: 0-2500 meters

Size and weight

Height: 10.15 inches (257.9mm)

Width: 7.62 inches (193.5mm)

Depth behind panel: 7.48 inches (190.0mm)

Weight: 9 pounds (approximately 4.1kg)

certification

UL Certification (Document Number E154862), UL 1053

ANSI C37.90

EN 55011(CISPR 11 Class A)

FCC Part 15 Subpart B Class A

Multiple EMC immunity tests (ESD 8kV, fast transient 2kV, surge, etc.)


Selection Guide

FP-4000 offers multiple models, distinguished by current rating, communication protocol, and control power supply. The following table shows some typical models:

Describe catalog number

5A,INCOM,48-125 Vac/dc, Fixed chassis FP4201-0166D2120G41

1A,INCOM,48-125 Vac/dc, Fixed chassis FP4301-0066D2120G42

5A,INCOM,100-240 Vac/dc, Fixed chassis FP4201-1066D2120G44

1A,INCOM,100-240 Vac/dc, Fixed chassis FP4301-1066D2120G45

5A,Modbus,100-240 Vac/dc, Fixed chassis FP4201-1166D2120G46

1A,Modbus,100-240 Vac/dc, Fixed chassis FP4201-0166D2120G47

5A,Modbus,48-125 Vac/dc, Fixed chassis FP4201-0166D2120G48

1A,Modbus,48-125 Vac/dc, Fixed chassis FP4301-0166D2120G49

  • National Instruments cRIO-9112 Chassis
  • National Instruments PXIe-1078 Chassis
  • National Instruments PCIe-6536 DIO Board
  • National Instruments NI-9425 Input Module
  • National Instruments PCI-5122 Digitizer Card
  • National Instruments 779072-01 Relay Module
  • National Instruments 783703-01 DAQ Module
  • National Instruments PXI-6515 Digital Module
  • National Instruments 781099-01 DAQ Device
  • National Instruments PXI-8183 PXI Controller
  • National Instruments sbRIO-9626 Single-Board RIO Controller
  • National Instruments PXIe-1435 Camera Link Frame Grabber
  • National Instruments NI 9237 Strain Bridge Input Module
  • National Instruments PXIe-4353 Thermocouple Input Module
  • National Instruments PCIe-6320 X Series DAQ Card
  • National Instruments NI 1454 Compact Vision System
  • National Instruments PCIe-6321 X Series DAQ Card
  • National Instruments PXIe-5172 PXI Oscilloscope Module
  • National Instruments cDAQ-9134 CompactDAQ Controller
  • National Instruments cRIO-9063 CompactRIO Controller
  • National Instruments PXI-4070 DMM Card
  • National Instruments cFP-BP-4 Backplane
  • National Instruments 779521-01 Bridge Module
  • National Instruments cDAQ-9172 Chassis
  • National Instruments NI 9236 Strain Module
  • National Instruments PXI-1042Q Chassis
  • National Instruments SCXI-1102 Input Module
  • National Instruments 776990-01 Input Module
  • National Instruments PXI-1045 PXI Chassis
  • National Instruments PCIe-6251 DAQ Device
  • National Instruments NI 9219 Universal Analog Input Module
  • National Instruments NI 9215 BNC Analog Input Module
  • National Instruments PXIe-6570 Digital Pattern Instrument
  • National Instruments NI-9477 Digital Output Module
  • National Instruments NI 9145 EtherCAT Chassis
  • National Instruments PCI-6521 Industrial Digital I/O Card
  • National Instruments NI 9239 BNC Voltage Input Module
  • National Instruments NI 9265 Current Output Module
  • National Instruments NI 9212 Thermocouple Input Module
  • National Instruments PXI-6229 Multifunction DAQ Module
  • National Instruments NI-9146 Chassis
  • National Instruments PXIe-5622 Digitizer
  • National Instruments PXI-6704 Output Module
  • National Instruments 782362-01 Input Module
  • National Instruments 779068-01 Digital Module
  • National Instruments 781063-01 Output Module
  • National Instruments PCI-7356 Motion Controller
  • National Instruments 779787-01 Input Module
  • National Instruments PXIe-1071 System
  • National Instruments NI 9219 Input Module
  • National Instruments NI 9214 Thermocouple Input Module
  • National Instruments PXIe-1085 18-Slot Chassis
  • National Instruments PCIe-6320 Multifunction DAQ Card
  • National Instruments USB-6211 Multifunction I/O Device
  • National Instruments USB-6341 X Series DAQ Device
  • National Instruments NI 9205 Analog Input Module
  • National Instruments NI 9149 8-Slot Chassis
  • National Instruments PXIe-2569 Relay Module
  • National Instruments NI 9230 Sound and Vibration Module
  • National Instruments cRIO-9047 CompactRIO Controller
  • National Instruments PCI-6534 Digital IO Card
  • National Instruments PXI-5122 Digitizer Module
  • National Instruments cDAQ-9188XT Chassis
  • National Instruments cDAQ-9184 Ethernet Chassis
  • National Instruments USB-6225 OEM DAQ Device
  • National Instruments NI 9205 Input Module
  • National Instruments NI 9207 Input Module
  • National Instruments NI-9862 CAN Module
  • National Instruments 781156-01 CAN Module
  • National Instruments FP-AO-200 Output Module
  • National Instruments NI 9264 Output Module
  • National Instruments IC-3173 Controller
  • National Instruments NI 9234 Vibration Module
  • National Instruments SMB-2163 DIO Accessory
  • National Instruments PXIe-1062Q DSA System
  • National Instruments USB-6289 DAQ Device
  • National Instruments NI 9233 Vibration Module
  • National Instruments PXIe-5840 VST
  • National Instruments PXI-1033 and PXI-6132 System
  • National Instruments GPIB-USB-HS+ Controller
  • National Instruments NI 9231 Sound and Vibration Module
  • National Instruments cRIO-9074 CompactRIO Controller
  • National Instruments 782536-01 DAQ Module
  • National Instruments 779781-01 DAQ Module
  • National Instruments PXIe-8388 MXI Express Controller
  • National Instruments SCXI-1520 Strain Bridge Module
  • National Instruments PCIe-6320 Multifunction DAQ Card
  • National Instruments NI 9234 Sound and Vibration Module
  • National Instruments USB-4431 Sound and Vibration Device
  • National Instruments NI 9227 Current Input Module
  • National Instruments PXI-1033 PXI Chassis
  • National Instruments NI 9213 Thermocouple Module
  • National Instruments PXI-1042 PXI Chassis
  • National Instruments PXI-6229 DAQ Card
  • National Instruments cRIO-9075 Controller
  • National Instruments PCI-6033E DAQ Card
  • National Instruments PCIe-6363 DAQ Card
  • National Instruments cDAQ-9174 Chassis
  • National Instruments PXIe-8880 PXI Controller
  • National Instruments NI 9242 Analog Input Module
  • National Instruments USB-6221 BNC DAQ Device
  • National Instruments NI 9220 Analog Input Module
  • National Instruments cRIO-9068 CompactRIO Controller
  • National Instruments PXI-4130 Source Measure Unit
  • National Instruments USB-6251 Multifunction DAQ Device
  • National Instruments PXI-8106 Embedded Controller
  • National Instruments USB-6218 Multifunction DAQ Device
  • National Instruments PCIe-1473R Camera Link Frame Grabber
  • National Instruments PXIe-4341 DSA Module
  • National Instruments PXI-8102 Embedded Controller
  • National Instruments cDAQ-9178 Chassis
  • National Instruments USB-6210 DAQ Device
  • National Instruments USB-6212 DAQ Device
  • National Instruments NI 9485 Relay Output Module
  • National Instruments NI 9208 Current Input Module
  • National Instruments PXIe-4141 SMU
  • National Instruments PCI-6154 DAQ Card
  • National Instruments cRIO-9038 Controller
  • National Instruments PCI-6133 DAQ Card
  • National Instruments LabVIEW RIO Kit 501684G
  • National Instruments PXIe-6396 Embedded Controller
  • National Instruments USB-8502 CAN Interface Device
  • National Instruments NI 9264 Spring Terminal Output Module
  • National Instruments NI 9213 Thermocouple Input Module
  • National Instruments NI-9205 Analog Input Module
  • National Instruments NI 9264 Analog Output Module
  • National Instruments USB-6212 Multifunction I/O Module
  • National Instruments PXI-4071 FlexDMM Multimeter Module