INTERBUS (X2.1/X2.2): Electrical isolation. X2.1 is a Remote bus input (male socket): Pin 1 DO, 2 DI, 3 GND, 6/DO, 7/DI; X2.2 for Remote bus output (female socket): Add Pin 5+5V power supply and Pin 9 RBST (remote bus status). Shielded twisted pair cables (LiYCY TP type) must be used, with the maximum length depending on the application location in the INTERBUS topology. Diagnostic LED: RC green light=remote bus check; +5V green light indicates normal power supply, off indicates no power supply; BA green light=bus activated, off=bus not activated; RD red light indicates that the remote bus is not activated.
PROFIBUS DP (X2): Electrical isolation. 9-pin female socket: Pin 3 RxD/TxD-P, 4 CNTR-P, 5 DGND, 6 VP (powered by the terminal connector), 8 RxD/TxD-N, 9 CNTR-N. Class A PROFIBUS DP certified cables according to EN 50170 can be used: impedance 136-165 Ω, capacitance<30 pF/m, loop resistance 110 Ω/km, wire diameter 0.64 mm. The maximum cable length depends on the baud rate (DIN EN 19245 Part 3): 187.5 kbit/s 1000 m, 500 kbit/s 400 m, 1500 kbit/s 200 m, 3000-12000 kbit/s 100 m. The two ends of the bus must be terminated - when using a dedicated PROFIBUS connector, the termination resistor is usually integrated into the connector. Diagnostic LED: Green=Communication activated.
5.3 D-SUB connector shielding
All D-SUB connectors must be fully shielded: the shielding layer must be folded back and flattened along the cable sheath; When fixing cables with cable clamps, the shielding layer should be in contact with the casing as much as possible and ensure sufficient stress relief.
Display and operation components
6.1 Contrast setting
Set the system variable LcdFntrast in any screen through programming software, with a value range of -25 to+70 and a default value of+25. If this variable is not configured, the default value will be used during device initialization. On site adjustment steps: Press the data release button → enter the new value using 0-9 or plus/minus keys → press Enter to confirm (immediate effect) → press the data release button again; Repeat as necessary until satisfactory.
The recovery process when the contrast cannot be read from the image: Shut down → Set the user mode switches S1 and S4 to ON → Power on → Shut down after a warning appears → Set S4 to OFF → Power on again. The application will not be lost. The default contrast switch position is the same as the "Hardware Activation Download" position, and the reset occurs before the corresponding message is displayed. The warning will be presented in a readable manner.
The screen characters support two attributes, Normal and Flashing, and the font can be Normal, Zoom, or a custom character set.
Safety reminder: When the display screen is damaged, avoid contact, swallowing, or inhaling liquids or gases that may leak (risk of poisoning and corrosion).
6.2 Keyboard Functions
The buttons are located under the environmentally resistant polyester film, and the button operation logic is defined in the programming software:
Edit key: First press the data release key to activate the editing mode (LED lights up). The number keys 0-9 can be used in conjunction with Shift/ShiftCase system variables to input A-Z, parentheses, °,:? Oh! Characters such as<,=,>, , *,/, etc;
Navigation keys: The left/right cursor keys can be programmed to directly select adjacent nodes and I/O screens (move the cursor by one character in the editor); The up/down keys are used for variable selection; The Home button returns the position of the parent node or the first input variable;
Special key: The Help key always displays the current online help (flashing LED indicates the presence of a message); The Print key activates the print job as a soft key; The Quit key is a message confirmation key; Enter to end data input (press in the startup screen to open the settings screen); Switch between menu and editor for Data release (the edit mode LED lights up, press again in edit mode to exit); Delete removes the character under the cursor and removes the selected message from the data storage;
Function keys F1-F12: Functions can be freely assigned (soft key functions), which can be used as menu direct keys or trigger control system functions. A set of identification label strips (F1-F12 label strips+one blank strip) are provided with the device, which can be replaced after disassembly. They can be inserted from the back of the panel without affecting the specified seal. Label method: Handwritten with waterproof pen for individual/prototype, laser printed copy film for small batches, and customized label strips for large batches.
6.3 User Mode Switch
Located on the back of the terminal, the functions of each mode switch position are as follows (I=ON, -=OFF, X=arbitrary):
S1 S2 S3 S4 operating mode
I X - Standard PLC mode (factory default)
I X I - No PLC standard mode
Transparent mode (with button start stop code)
Transparent mode (no button stop code)
I-I activation download (erase application memory)+default contrast
I-II activation upload
Operation, maintenance, and troubleshooting
7.1 General Information
The VCP type operation terminal is maintenance free, with only a few components being vulnerable parts that need to be replaced after running for a certain number of hours. Internal maintenance work of the equipment is only allowed to be performed by skilled personnel - please contact Bosch Rexroth service or ensure that only skilled personnel operate when hardware components need to be replaced. Before using new materials such as cleaning agents, compatibility testing of the casing material must be conducted (see Section 3.7).