During installation, a gap of at least 30mm must be left around the operating terminal to ensure air circulation. When installing horizontally, attention should be paid to other heat sources below the terminal that may cause heat accumulation. Adequate heat dissipation must be provided and the allowable temperature range specified in the technical data must be followed.
To maintain the specified level of protection, it is necessary to ensure that the sealing ring is evenly attached to the installation surface, and the hex nut is tightened evenly, with a maximum torque not exceeding 1.2 Nm. Installation steps: Thread the terminal through the installation opening from the front, and then fix it with the hex nut from the back. This method is particularly recommended for distribution cabinet panels with a thickness of approximately 1 mm to 8 mm. Fasteners include press in M4 × 18 mm bolts, DIN 127 Form B B4 spring lock washers, and M4 DIN 934 nuts (the latter two are not provided with the equipment).
4.2 Power Supply Connection
Power is supplied through connector X1 (Phoenix COMBICON MSTBV 2,5/3-GF, randomly provided MSTB 2,5/3-STF female plug):
Pin 1: Low Noise Ground
Pin 2:0 V
Pin 3:24 VDC
The device has reverse polarity protection - the device does not work when the polarity is reversed. The power cable must use thin stranded wire with a minimum cross-sectional area of 0.75 mm ² (18 AWG) and a maximum cross-sectional area of 2.5 mm ² (14 AWG). Wiring steps: Peel off the outer layer by about 30 mm and the core wire by about 5 mm, install a wire end sleeve, and connect it to the connector; If shielded power cables are used, the shielding layer should be connected to Pin 1; Insert the female plug into X1. A and lock it with screws to prevent slipping.
4.3 Protection Grounding
The protective grounding bolt must always provide an independent conductor with a minimum cross-sectional area of 1.5 mm ² (16 AWG) and as short as possible - meeting this requirement can enhance operational safety.
4.4 Panel Cleaning
Only use a damp cloth to remove panel stains.

Detailed explanation of interface system
The equipment is divided into two categories: standard type and bus type. The universal interface X3 integrates multiple interface standards into one connector, divided into two channels: the communication channel (SER1) is independent of the upload/download/record printer/scanner channel (SER2). SER1 only allows one of the three interface standards.
Model code RS232c (X3-SER2) TTY/20mA, RS485, RS232c (X3-SER1) DeviceNet INTERBUS PROFIBUS DP
VCPxx.xxxx-xxxRS-xx-xx X X - - -
VCPxx.xxxx-xxxDN-xx-xx X - X - -
VCPxx.xxxx-xxxIB-xx-xx X - - X -
VCPxx.xxxx-xxxPB-xx-xx X - - - X
5.1 Standard Interface
TTY/20 mA current loop (X3-SER1): It can be wired as an active or passive current loop, with independent 20 mA power supplies for each transmitting and receiving line, and a compliant voltage of approximately 24 VDC. The 20 mA power supply should be provided by the transmitter unit to significantly reduce signal line crosstalk. When in idle state (logic 1), a current of 20 mA can be measured in the cable. 25 pin D-SUB female socket, passive mode key pins: Pin 10 T+, 13 R+, 14 R -, 19 T -; Active mode adds Pin 12 S1+, 16 S2+, 21 S1-, 24 S2-. The RS485 terminal must be set to OFF in current loop mode.
RS485 (X3-SER1): Suitable for point-to-point and multi-point connections. Logic 1: UA-UB ≤ -0.3V (UA<UB); Logic 0: UA-UB ≥+0.3V (UA>UB). Key pins: Pin 8 T (A), 9 T (B), 11 SGND, 22 R (A), 23 R (B). Terminating resistors R1/R3=510 Ω, R2=150 Ω, R4=120 Ω. The point-to-point connection must activate the termination; Multi point connection only activates termination at the end of the cable. The termination switches S1-S4 are all ON for effective termination, and all OFF for closed. Only specified switch positions are allowed.
RS232c (X3-SER1): point-to-point connection, pins 6 TD, 15 CTS, 17 RTS, 18 RD, 25 SGND; RS485 termination must be turned off in RS232 mode.
RS232c (X3-SER2): Only for downloading, uploading, scanning, or recording printers, as this interface does not have electrical isolation. Pin: 1 low-noise ground, 2 TD, 3 RD, 4 RTS, 5 CTS, 7 SGND, 20 DTR.
5.2 Bus interface
DeviceNet (X2.1/X2.2): Compliant with ISO 11898, electrically isolated. 9-pin D-SUB (with the same allocation of male and female pins), key pins: Pin 2 CAN_L, 3/6 CAN_GND, 7 CAN_S. All signal lines should be looped from X2.1 to X2.2, and the connecting cables should be connected to every pin, including reserved pins, so that the cables can still be used when future bus specifications are expanded. DeviceNet certified cables must be used: 2 × 1.1 mm type loop resistance<22.6 Ω/km, 2 × 0.6 mm type<91.8 Ω/km, surge impedance of 120 Ω, unit length capacitance<39.4 pF/m. The longest branch line is 6 meters; The bus length varies with baud rate: a 2 × 1.1 mm cable can reach 500 m at 125 kBit/s, and only 100 m at 500 kBit/s. The two ends of the bus are terminated with 120 Ω resistors. Diagnostic LED: green off=terminal disconnected from bus, green on=communication activated, green flashing=occasional bus error.