Motor parameter acquisition path: Rexroth motor - automatic loading when powered on (MHD/MKD/MKE/MSK/MAD/MAF/SF) with encoder data storage (F2008 RL "The motor type has changed" appeared during initial debugging, cleared and automatically executed S-0-0262 C07 Load defaults procedure); Download from DriveBase via IndraWorks D without memory. **Attention: Rexroth motors are strictly prohibited from running C3200/C3600/C4600, otherwise the manufacturer's optimized parameters will be overwritten by the calculated values! **Third party motors - asynchronous motors are calculated from nameplate data using C3200 (P2/P3 phase only), or identified and optimized under test signals using C3600 (P4 phase only) with appropriate initial values; The synchronous motor is calculated from the input motor parameters using C4600. Asynchronous third-party motors cannot use magnetic reluctance characteristics (the corresponding position of P-0-4014 cannot be set); The recommended absolute measurement system for synchronous third-party motors.
Environmental control setting sequence (from inside to outside): Current loop (S-0-0106/S-0-0107, automatically adjusted with PWM frequency) → Speed loop (S-0-0100/S-0-0101+P-0-0004 filter+P-0-1120-1123 four second-order filters suppress typical mechanical resonance at 400-800 Hz) → Position loop (S-0-0104 Kv, only matches outer loop dynamics). Automatic axis control adjustment (C1800, parameters P-0-0163 damping coefficient, P-0-0164 application, P-0-0165 options: speed loop/position loop/acceleration feedforward/load inertia/maximum acceleration) requires mobile drive execution.
Diagnosis and troubleshooting
Warning Category: E1xxx - E7xxx No Drive Response; E8xxx with driven reaction. The behavior of power grid/undervoltage warning is determined by P-0-0118. Warning cannot be cleared externally, it will automatically disappear after the condition disappears.
Error classification and response (based on P-0-0119 Best possible degradation, release of driving torque after reaction completion):
Typical Processing of Message Number Categories
F2xxx Non fatal Error: Press P-0-0119 to decelerate; Complete error response → Clear (S-0-0099/C0500 or panel Esc) → Eliminate cause → Re enable rising edge
F3xxx non fatal security technology error is the same as F2xxx
F4xxx interface error as above, and NC response activation unavailable; To restart, it is necessary to return to the running mode and power on again
F6xxx travel range error closed loop: speed command value reset; Open loop: Shut down according to the maximum stator frequency change of P-0-0569
F7xxx security technology error speed command value reset
F8xxx fatal error immediate torque release; Initialization error (F8201/F8203/F8118/F8120) cannot be cleared and must be completely powered off and restarted
F9xxx/E-xxxx fatal system error: all digital outputs set to 0, ready relay disconnected, output stage locked, and brake output disconnected (self holding brake applied); Must be completely powered off and restarted at 24V, reset to operating mode, and then powered on again
Error Memory: Record the last 50 errors and their occurrence times (mapping P-0-0192/P-0-0193, timestamp P-0-0105); Errors caused by voltage shutdown control (such as F8070+24Volt DC error) are not recorded.
Troubleshooting sequence (according to the recommended action table in 8.2): ① Refer to the Troubleshooting Guide; ② Contact sales service; ③ Check the motor (brake, encoder battery, cooling, cables); ④ Power supply unit/drive controller power off and restart; ⑤ Check the function and installation of the encoder, encoder cables, motor cables, I/O wiring, and 24V; ⑥ Check the communication connection of the main station; ⑦ Check the main circuit; ⑧ Check the mechanical system (rigidity, looseness). Before replacing the controller, the parameter set must be saved first; After replacing the motor, the position reference of the servo shaft (indirect measurement system) will be lost and needs to be re established.
Firmware replacement: Distinguish between Release update (same version upgrade, such as MPH04V06 → V08) and Version upgrade (version upgrade, such as MPH03V20 → MPH04V08). The medium is MMC or IndraWorks D. Before upgrading the firmware version, all parameters must be backed up. After the upgrade, C07_1 Load defaults will be automatically executed, and the parameter files need to be reloaded; The upgrade with the safety module (S1) requires a re execution of the acceptance test (C3000 synchronizes and stores the security technology IDN → inputs the security password → acceptance). Replacing a power outage/disconnection/software crash midway will cause the driver to display "Loader" - this state can only be restored to the control section firmware through the IndraWorks D serial port. The S1/CCD option card must be programmed in the second round after the control section is restored. Only one firmware file is allowed in the MMC firmware folder, otherwise the startup message will be "MMC not correct".