Product Platform Overview
The Rexroth IndraDrive C-series drive controller adopts a separate architecture of power segment and control segment: the power segment integrates the control segment and is responsible for grid connection, motor connection (optional brake and motor temperature monitoring), 24V control voltage, DC bus, module bus, and external braking resistor (HCS device) connection; The control section is inserted as an independent component into the power section, pre installed at the factory and configurable. The power spectrum covers two designs: 300mm and 400mm
300mm design: HCS02.1E-W0012/W0028/W0054/W0070;
400mm design: HCS03.1E-W0070/W0100/W0150/W0210.
The control section includes two single axis variants:BASIC OPENLOOP (CSB01.1N-FC) and BASIC PROFIBUS (CSB01.1N-PB). The supporting motor ecosystem covers Rexroth shell motors (MHD/MKD/MKE/MSK/MAL/SF, 2AD/ADF/MAD/MAF) and kit motors (MLF/MBS/MBSx2/MBT/LSF/1MB), and supports parameter validated third-party motors (rotary/linear asynchronous and synchronous motors). In terms of certification, it meets the EC Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC, and has a C-UL-US Listing (HCS02.1E document number E 134201).
Working conditions and derating
Protection and temperature: IP20; The ambient temperature is 0...+40 ° C, and when the power is reduced, it is 0...+55 ° C (according to the characteristic curve); Storage -25...+55 ° C, transportation -25...+70 ° C (humidity 5... 95%, condensation and freezing are prohibited);
Altitude: When the nominal data is less than 1000 m and greater than 2000 m, a 1.2/50 µ s overvoltage limiter must be installed to limit the voltage to 1.0 kV between the outer conductor and 2.5 kV between the conductor and ground. The maximum altitude is 4000 m (with the upper limit temperature reduced to 40 ° C);
Reduction and superposition rule: When the environmental temperature and altitude exceed both limits, the two utilization coefficients are multiplied; The altitude is only counted once, and the temperature is calculated separately for the motor and drive controller;
Long term storage: Equipment containing electrolytic capacitors should be powered on and run for at least 1 hour per year;
Material compatibility: New lubricants, cleaning agents, etc. must undergo compatibility testing with the casing materials before use.
Electrical parameters and power supply system
Power segment load capacity (ULN=3AC400V, equipped with HNL/HNK main reactors): HCS02-W0012 rated motor power of 1.5 kW/continuous current of 4 A/peak current of 12 A, reaching 75 kW/145 A/210 A up to HCS03-W0210.
Main power supply: HCS02.1E allows 3AC (200... 500) ± 10% (IT grid 200... 230V, single-phase 200... 250V is also acceptable); HCS03.1E is 3AC (400... 500)+10%/-15%. Grid frequency (50... 60) ± 2 Hz.
Control voltage 24V: 24 ± 20% without brake power supply; When motor brake is required, 24 ± 5% is used for cables<50 m, and 26 ± 5% is used for cables>50 m; The maximum overvoltage is 33 V (1 ms), and the overvoltage must be reduced by the 24V power supply unit or handled by the cabinet inlet overvoltage limiter. The X31/X32 isolated input and output are not powered by 24V through the power segment and require an independent power supply. The power consumption in the power section is 12-30 W, the control section is 7.5 W (FC and PB are the same), and the CP/EN1/EN2/ENS/MA1/MD1/S option module adds an additional 1-6 W.
Motor cable length limit (depending on PWM switching frequency): 2 kHz shielded 100 without filtering m/4 kHz 75 m/8 kHz 38 m/12 kHz 25 m/16 kHz 18 m; When equipped with HMF/HML, the 4 kHz shielding can reach 75 meters, and the HCS03 unshielded can reach 200 meters. IndraDrive must use RKL series shielded motor cables; Third party cables require a ground/phase capacitance of ≤ 0.5 nF/m and an inductance of ≤ 100 nH/m per unit length, otherwise the warranty is invalid.
Peripheral component selection: Main reactor HNL01.1E (feeding type and current compensation type), main filter HNF/HNK (3 * AC 380... 480V ± 10%), braking resistor HLR01.1 (0.30-36 kW continuous power, peak up to 124 kW, U=850V); Minimum cycle time of 120 s), motor filter HMF01.1 (du/dt output<1 kV/µ s). The grounding conductor of the reinforced braking resistor must be ≥ 10 mm ² (EN 50178/61800-5-1).
EMC and Electrical Installation Specification
Installation follows the three zone division:
Zone A (interference free zone): power supply feeder, fuse, main switch, filter grid side - maintain d1=200 mm with Zone B/C, and the distance between magnetic components (transformers, reactors) and interference free devices in Zone A is ≥ 500 mm;
Zone B (susceptible area): main power connection between the drive system and the filter, drive controller interface line - separated from Zone A by a distance of ≥ 200 mm or shielding/isolation board;
C zone (strong interference zone): motor cables (including single core) - kept at d5=100 mm from other wires or separated by grounding isolation plates; The motor cable and power cord can be wired in parallel for a maximum length of 300 mm, and then routed in reverse slots.