Product positioning and application objects
VT-VRPA2 is an analog Euro card format proportional valve amplifier (component series 1X) launched by Bosch Rexroth, designed specifically for 4/3 proportional directional valves with live feedback, compatible with two valve types:
4WRE 6... -2X (order code 02nd digit=1);
4WRE 10... -2X (order code 02=2).
The complete ordering code structure is * * VT-VRPA2 – 1X/V0/T1 or T5/* *: V0 is the standard version; Option T1 represents a single ramp time, while T5 represents five sets of ramp times (with switchable measurement points). In terms of attachments, an open card clamp VT 3002-1-2X/48F is required (see data sheet 29928).
List of core features:
Differential input (± 10 V)+four sets of callable command value inputs (± 10 V)+current input (4... 20 mA);
Internal command value signal inversion is achieved through 24V input or jumper;
Select the ramp time through quadrant recognition (24V input) or ramp time call (24V input of T5);
Characteristic curve correction: The step level and maximum value can be independently adjusted in both positive and negative directions;
Enable input and "ready" output signals;
The power supply is equipped with a DC/DC converter and does not raise the zero point, and has reverse polarity protection for the power supply.
Detailed explanation of functional links (refer to block diagram 1-20 modules)
Power supply unit [1]: Built in current limiting power supply unit, providing power to all positive and negative power sources inside the card. The DC/DC converter outputs multiple isolated voltages of+15 V/+7.5 V/+5 V/M0/-5 V/-7.5 V/-15 V, which are stabilized by a 100 µ F capacitor.
Instruction value synthesis path: Internal instruction value=differential input [2] signal+current input [3] signal+call signal [4]+zero offset [5] (zero potentiometer "Zw") sum (summation [6]). Corresponding relationship of standard values:
Standard value current input differential input command value measurement socket flow direction
−100 % 4 mA −10 V −10 V P→B, A→T
0 % 12 mA 0 V 0 V —
100 % 20 mA 10 V 10 V P→A, B→T
0 % < 1 mA¹ 0 V 0 V —
When the current input is not connected or the command value cable is disconnected, the internal command value is 0%. There is no switching mechanism between current and voltage inputs, and both sets of inputs are permanently available simultaneously.
Command value call [4]: Four sets of signals from w1 to w4 can be called, and the external command value voltage can be directly defined by the+10 V/-10 V regulated output, or introduced through an external potentiometer - when directly connected to the regulated source, the command value is set by the internal potentiometers w1 to w4; The internal potentiometer is only used as an attenuator/limiter when using an external potentiometer. Only one call is allowed at a time; If multiple actions are taken simultaneously, "1" has the lowest priority and "4" has the highest priority. The activated call is indicated by the yellow LED on the front panel.
Instruction value inversion [7]: The internal instruction value synthesized from the input signal, call, and zero offset can be inverted through an external signal or jumper J1, and the front panel LED ("-1") indicates the inversion state.
Enable function [8]: Enable the signal to turn on the power output stage and send the internal command value to the ramp generator, indicated by the LED on the front panel. After enabling, the internal command value changes according to the set ramp time - the controlled valve will not suddenly open.
Slope generator [9]: limits the rate of rise of the control output; The downstream step function and amplitude attenuator do not prolong or shorten the ramp time. When jumper J2 is closed, the ramp time is set to the minimum value (<2 ms, i.e. the ramp is closed). External slope time setting: The internal setting value can be extended through an external potentiometer, and the setting value can be verified through a measuring socket; Automatically revert back to the internal default value when the cable is disconnected.
Slope time setting and measurement conversion table:
Measure socket value Ut/V (T1 uses "t", T5 uses "v") 5 3 2 1 0.5 0.3 0.2 0.1 0.05 0.03 0.02
Current slope time t/ms (± 20%) 20 33 50 100 200 333 500 1000 2000 3333 5000
After closing jumper J3, the ramp time on the upper table can be increased tenfold.
Characteristic curve generator [11]: adjustable step level and maximum value are set for positive and negative signals according to hydraulic requirements; The actual characteristic curve at the zero crossing point is linear rather than step like. The amplitude limiter [12] limits the internal command value to approximately ± 110% of the nominal range. The oscillator [14] generates control signals for the inductive position sensor (± 5 VSS/output, 10 mA, 5.6 kHz ± 10%); The demodulator [15] extracts the actual value of the valve core position (100% ≙ 10 V) from the position sensor signal; Position controller [17] optimized according to valve type; The power output stage [18] generates a clock modulated proportional valve solenoid current (approximately 5 kHz clock, 0... 2.5 A), with a current limit of 2.5-2.8 A per output. The output is protected against short circuits, and the output stage is powered off in the event of an internal fault or failure to enable. Fault identification [19] monitors position sensor cable breakage, primary short circuit, and output stage overcurrent.