Product Platform Overview
The Rexroth IndraDrive C-series drive controller adopts a separate architecture of power segment and control segment: the power segment integrates the control segment and is responsible for grid connection, motor connection (optional brake and motor temperature monitoring), 24V control voltage, DC bus, module bus, and external braking resistor (HCS device) connection; The control section is inserted as an independent component into the power section, pre installed at the factory and configurable. The power spectrum covers two designs: 300mm and 400mm
300mm design: HCS02.1E-W0012/W0028/W0054/W0070;
400mm design: HCS03.1E-W0070/W0100/W0150/W0210.
The control section includes two single axis variants:BASIC OPENLOOP (CSB01.1N-FC) and BASIC PROFIBUS (CSB01.1N-PB). The supporting motor ecosystem covers Rexroth shell motors (MHD/MKD/MKE/MSK/MAL/SF, 2AD/ADF/MAD/MAF) and kit motors (MLF/MBS/MBSx2/MBT/LSF/1MB), and supports parameter validated third-party motors (rotary/linear asynchronous and synchronous motors). In terms of certification, it meets the EC Low Voltage Directive 73/23/EEC and EMC Directive 89/336/EEC, and has a C-UL-US Listing (HCS02.1E document number E 134201).
Working conditions and derating
Protection and temperature: IP20; The ambient temperature is 0...+40 ° C, and when the power is reduced, it is 0...+55 ° C (according to the characteristic curve); Storage -25...+55 ° C, transportation -25...+70 ° C (humidity 5... 95%, condensation and freezing are prohibited);
Altitude: When the nominal data is less than 1000 m and greater than 2000 m, a 1.2/50 µ s overvoltage limiter must be installed to limit the voltage to 1.0 kV between the outer conductor and 2.5 kV between the conductor and ground. The maximum altitude is 4000 m (with the upper limit temperature reduced to 40 ° C);
Reduction and superposition rule: When the environmental temperature and altitude exceed both limits, the two utilization coefficients are multiplied; The altitude is only counted once, and the temperature is calculated separately for the motor and drive controller;
Long term storage: Equipment containing electrolytic capacitors should be powered on and run for at least 1 hour per year;
Material compatibility: New lubricants, cleaning agents, etc. must undergo compatibility testing with the casing materials before use.
Electrical parameters and power supply system
Power segment load capacity (ULN=3AC400V, equipped with HNL/HNK main reactors): HCS02-W0012 rated motor power of 1.5 kW/continuous current of 4 A/peak current of 12 A, reaching 75 kW/145 A/210 A up to HCS03-W0210.
Main power supply: HCS02.1E allows 3AC (200... 500) ± 10% (IT grid 200... 230V, single-phase 200... 250V is also acceptable); HCS03.1E is 3AC (400... 500)+10%/-15%. Grid frequency (50... 60) ± 2 Hz.
Control voltage 24V: 24 ± 20% without brake power supply; When motor brake is required, 24 ± 5% is used for cables<50 m, and 26 ± 5% is used for cables>50 m; The maximum overvoltage is 33 V (1 ms), and the overvoltage must be reduced by the 24V power supply unit or handled by the cabinet inlet overvoltage limiter. The X31/X32 isolated input and output are not powered by 24V through the power segment and require an independent power supply. The power consumption in the power section is 12-30 W, the control section is 7.5 W (FC and PB are the same), and the CP/EN1/EN2/ENS/MA1/MD1/S option module adds an additional 1-6 W.
Motor cable length limit (depending on PWM switching frequency): 2 kHz shielded 100 without filtering m/4 kHz 75 m/8 kHz 38 m/12 kHz 25 m/16 kHz 18 m; When equipped with HMF/HML, the 4 kHz shielding can reach 75 meters, and the HCS03 unshielded can reach 200 meters. IndraDrive must use RKL series shielded motor cables; Third party cables require a ground/phase capacitance of ≤ 0.5 nF/m and an inductance of ≤ 100 nH/m per unit length, otherwise the warranty is invalid.
Peripheral component selection: Main reactor HNL01.1E (feeding type and current compensation type), main filter HNF/HNK (3 * AC 380... 480V ± 10%), braking resistor HLR01.1 (0.30-36 kW continuous power, peak up to 124 kW, U=850V); Minimum cycle time of 120 s), motor filter HMF01.1 (du/dt output<1 kV/µ s). The grounding conductor of the reinforced braking resistor must be ≥ 10 mm ² (EN 50178/61800-5-1).
EMC and Electrical Installation Specification
Installation follows the three zone division:
Zone A (interference free zone): power supply feeder, fuse, main switch, filter grid side - maintain d1=200 mm with Zone B/C, and the distance between magnetic components (transformers, reactors) and interference free devices in Zone A is ≥ 500 mm;
Zone B (susceptible area): main power connection between the drive system and the filter, drive controller interface line - separated from Zone A by a distance of ≥ 200 mm or shielding/isolation board;
C zone (strong interference zone): motor cables (including single core) - kept at d5=100 mm from other wires or separated by grounding isolation plates; The motor cable and power cord can be wired in parallel for a maximum length of 300 mm, and then routed in reverse slots.
Grounding points: The chassis and mounting plate have a large area of low resistance contact; Recommend galvanized/chromate mounting plates (anodized, yellow chrome, black paint surfaces with poor conductivity are prohibited); The cabinet door is connected at the top/middle/bottom three points with a grounding conductor of ≥ 6 mm ² or an equally wide grounding strip. The grounding conductor of the equipment has a total length of ≥ 10 mm ² (leakage current>3.5 mA).
Signal line: Measurement system line with shielded grounding at both ends and uninterrupted shielding; The digital signal line is grounded at both ends, and if necessary, parallel equal conductors of ≥ 10 mm ² are laid; The analog signal line is grounded at one end. 24V power supply adopts star wiring, with independent power supply lines for each group of drive controllers/third-party components; When multiple power supply units are connected with 0V low resistance, the output voltage is within the allowable range, and the switch is synchronized. The wiring from the main reactor to the control section should be as short as possible and twisted in pairs.

Interface and Connection
X1 module bus: 8-pole ribbon cable, allowing data exchange between drive controllers;
X3 main power supply: HCS02 W0012-W0070 are 4-pole screw terminals (0.2-4 mm ²/W0054-70 0.5-10 mm ², torque 0.5-0.6/1.2-1.5 Nm); HCS03 W0070 connector 16 mm ²/1.5 Nm, W0100/W0150 terminal block M6 ring terminal/6 Nm, W0210 M10/25 Nm. During single-phase operation, L1 and N are connected to L1/L2;
X5 motor connection: A1/A2/A3+PE, output to each other and ground short-circuit protection; The torque specification is the same as X3;
X6 motor temperature monitoring+brake: Pin1/2 MotTemp ± Pin3/4 +24V/0VBr; The maximum braking current is 2.0 Aeff (HCS02 and HCS03 are the same), and external contact components must be used to control it when exceeded; Ensure a switch frequency of 250000 times (time constant<50 ms), with a maximum switch frequency of 0.5 Hz. Note that standard brake and drive controller direct control external brake are not sufficient to ensure personal safety, and the vertical axis must be mechanically locked/externally braked/weighted; The motor brake is not a service brake, and it wears out after about 20000 revolutions per minute;
X9 braking resistor: maximum length of 5 meters for bipolar, shielded or twisted pair;
X13 Control voltage:+24V and 0V, with a maximum load capacity of 6 Aeff; 0V is connected to the potential of the casing (insulation monitoring cannot be used); 24V power supply up to X13 maximum allowable inductance of 100 µ H (approximately 2 × 75 m); HCS02 has two designs: * * N (external 24V) and * * * V (integrated 24V). The * * V design requires external power supply for the brake, and the X13 terminal is not allowed to carry load;
XS1/XS2: Shielded connection between control line and motor cable (only applicable to cables without built-in shielding connectors); Recommend HAS02 shielding board attachment - the best solution for large area direct contact equipment, and disable the "pigtail braid" connection method; HCS02 XS2 special screw length of 12 mm, too long will damage the controller;
Control section interface: BASIC OPENLOOP provides X31/X32 digital and analog I/O (24V, 0V input), X11/X12 relays (AC250V/2A, DC30V/1A), X35/X36 analog I/O (0... 20 mA), X2 serial interface (RS232), H1 control panel interface; BASIC PROFIBUS adds X8 encoder evaluation (ENS, DC11V6/300 mA), X41 optional start lock, X30 PROFIBUS master communication (12 MBaud, supporting IEC61158-2 full baud rates of 9.6k-12M and automatic baud rate detection).
Debugging and parameterization process
Control panel: two types: standard panel and comfort panel; The Comfort model only supports V/f control, requires firmware FWA-INDRV * - MPB-04V12 or higher, and supports hot swapping. Menu structure: Main screen (error clearing/language DE/EN/FR/IT/SP/mode selection) → Monitor (single parameter/cycle parameter list/historical and error memory/current configuration) → Motor potentiometer → Bipolar torque/force limit (S-0-0092) → Parameterization (guided parameterization/single parameter modification) → Parameter management (load basic parameters/save/load parameters - parameter set can be copied across drives through VCP01.2BWA).
Guided parameterization is completed sequentially: input motor nameplate data (P-0-4032: rated current/voltage/frequency/speed/power factor/power) → C3200 automatically calculates motor data → displays motor peak current S-0-0109 → selects temperature sensor (P-0-0512: none/PTC150/KTY84/PTC130) and alarm/shutdown temperature (S-0-0201/S-0-0204) → selects switch frequency (P-0-0001:4000/8000 Hz) → speed command value channel (analog input/motor potentiometer/fixed command value) → positive and negative speed limits and ramp → automatic P2 → P3 → P4 switching.
Communication phase (SERCOS specification): P-1 baud rate scan → P0 loop check → P1 slave station scan → P2 complete parameterization (only this phase can change communication parameters and axis control configuration) → P3 operation mode configuration, fault response, motor/encoder/mechanical transmission/scaling parameters → P4 operation mode (only cyclic data). The field bus and parallel/analog interface only support P2-P4. After executing the transition check commands S-0-0127 (C0100) and S-0-0128 (C0200), the driver displays "bb" and outputs A0013 Ready for power on. Switch back to parametric mode using P-0-4023 (C0400).
Motor parameter acquisition path: Rexroth motor - automatic loading when powered on (MHD/MKD/MKE/MSK/MAD/MAF/SF) with encoder data storage (F2008 RL "The motor type has changed" appeared during initial debugging, cleared and automatically executed S-0-0262 C07 Load defaults procedure); Download from DriveBase via IndraWorks D without memory. **Attention: Rexroth motors are strictly prohibited from running C3200/C3600/C4600, otherwise the manufacturer's optimized parameters will be overwritten by the calculated values! **Third party motors - asynchronous motors are calculated from nameplate data using C3200 (P2/P3 phase only), or identified and optimized under test signals using C3600 (P4 phase only) with appropriate initial values; The synchronous motor is calculated from the input motor parameters using C4600. Asynchronous third-party motors cannot use magnetic reluctance characteristics (the corresponding position of P-0-4014 cannot be set); The recommended absolute measurement system for synchronous third-party motors.
Environmental control setting sequence (from inside to outside): Current loop (S-0-0106/S-0-0107, automatically adjusted with PWM frequency) → Speed loop (S-0-0100/S-0-0101+P-0-0004 filter+P-0-1120-1123 four second-order filters suppress typical mechanical resonance at 400-800 Hz) → Position loop (S-0-0104 Kv, only matches outer loop dynamics). Automatic axis control adjustment (C1800, parameters P-0-0163 damping coefficient, P-0-0164 application, P-0-0165 options: speed loop/position loop/acceleration feedforward/load inertia/maximum acceleration) requires mobile drive execution.
Diagnosis and troubleshooting
Warning Category: E1xxx - E7xxx No Drive Response; E8xxx with driven reaction. The behavior of power grid/undervoltage warning is determined by P-0-0118. Warning cannot be cleared externally, it will automatically disappear after the condition disappears.
Error classification and response (based on P-0-0119 Best possible degradation, release of driving torque after reaction completion):
Typical Processing of Message Number Categories
F2xxx Non fatal Error: Press P-0-0119 to decelerate; Complete error response → Clear (S-0-0099/C0500 or panel Esc) → Eliminate cause → Re enable rising edge
F3xxx non fatal security technology error is the same as F2xxx
F4xxx interface error as above, and NC response activation unavailable; To restart, it is necessary to return to the running mode and power on again
F6xxx travel range error closed loop: speed command value reset; Open loop: Shut down according to the maximum stator frequency change of P-0-0569
F7xxx security technology error speed command value reset
F8xxx fatal error immediate torque release; Initialization error (F8201/F8203/F8118/F8120) cannot be cleared and must be completely powered off and restarted
F9xxx/E-xxxx fatal system error: all digital outputs set to 0, ready relay disconnected, output stage locked, and brake output disconnected (self holding brake applied); Must be completely powered off and restarted at 24V, reset to operating mode, and then powered on again
Error Memory: Record the last 50 errors and their occurrence times (mapping P-0-0192/P-0-0193, timestamp P-0-0105); Errors caused by voltage shutdown control (such as F8070+24Volt DC error) are not recorded.
Troubleshooting sequence (according to the recommended action table in 8.2): ① Refer to the Troubleshooting Guide; ② Contact sales service; ③ Check the motor (brake, encoder battery, cooling, cables); ④ Power supply unit/drive controller power off and restart; ⑤ Check the function and installation of the encoder, encoder cables, motor cables, I/O wiring, and 24V; ⑥ Check the communication connection of the main station; ⑦ Check the main circuit; ⑧ Check the mechanical system (rigidity, looseness). Before replacing the controller, the parameter set must be saved first; After replacing the motor, the position reference of the servo shaft (indirect measurement system) will be lost and needs to be re established.
Firmware replacement: Distinguish between Release update (same version upgrade, such as MPH04V06 → V08) and Version upgrade (version upgrade, such as MPH03V20 → MPH04V08). The medium is MMC or IndraWorks D. Before upgrading the firmware version, all parameters must be backed up. After the upgrade, C07_1 Load defaults will be automatically executed, and the parameter files need to be reloaded; The upgrade with the safety module (S1) requires a re execution of the acceptance test (C3000 synchronizes and stores the security technology IDN → inputs the security password → acceptance). Replacing a power outage/disconnection/software crash midway will cause the driver to display "Loader" - this state can only be restored to the control section firmware through the IndraWorks D serial port. The S1/CCD option card must be programmed in the second round after the control section is restored. Only one firmware file is allowed in the MMC firmware folder, otherwise the startup message will be "MMC not correct".