Lauer 200-V02366 System Panel
The Lauer 200-V02366 System Panel is an advanced operator interface designed for sophisticated industrial control systems. It features a large 12.1-inch TFT display with XGA resolution, providing crisp visualization of process data, alarms, and trends. The unit is equipped with a powerful processor and extensive memory to handle complex graphical applications and real-time communication with multiple controllers.
Technical Specifications
Display: 12.1-inch TFT, 1024 x 768 pixels, 16.2 million colors, LED backlight, 400 cd/m² brightness, 700:1 contrast ratio.
Touchscreen: Projected capacitive, multi-touch support, 2 mm glass cover, anti-glare coating.
Processor: Intel Atom E3845, 1.91 GHz, 2 GB DDR3 RAM, 8 GB eMMC flash.
Interfaces: 2 x RS232/422/485, 2 x Ethernet 10/100/1000, 4 x USB 2.0, 1 x HDMI output, 1 x MicroSD slot.
Power Supply: 24 V DC (18–36 V DC), consumption 25 W maximum.
Operating Temperature: -10 °C to 55 °C; storage: -20 °C to 75 °C.
Humidity: 5 % to 95 % non-condensing.
Protection Rating: Front IP65, rear IP20.
Mounting: Panel mount, cutout 310 x 230 mm, depth 70 mm.
Weight: 3.8 kg.
Functional Features
The system panel supports a wide range of fieldbus protocols including PROFINET, EtherNet/IP, Modbus TCP, and CANopen. It includes an integrated web server for remote monitoring via standard browsers. The unit can store historical data on its internal flash or external USB drive and supports FTP for data export. The capacitive touchscreen enables gesture-based navigation and zoom functions. Lauer Configurator Pro software provides advanced visualization tools, scripting capabilities, and OPC UA client/server functionality.
Installation Guidelines
Install the 200-V02366 in a clean, dry cabinet with adequate airflow. Use M4 screws and clamps to secure the panel. Connect the grounding terminal to the main protective earth. Use shielded cables for all communication ports and keep cable lengths within recommended limits. The Ethernet ports support auto-MDI/MDIX for easy connection to switches or controllers.
Operating Conditions
This system panel is designed for 24/7 operation in industrial settings. It withstands vibration up to 1 g (10–150 Hz) and shock up to 30 g (11 ms). The LED backlight has a rated life of 70,000 hours. The unit includes temperature monitoring and will throttle performance if internal temperature exceeds 70 °C. For outdoor or harsh environments, an optional sun-visible version is available.
Applications
Common applications include process control, supervisory control and data acquisition (SCADA), machine vision integration, and energy management systems. The high-resolution display is particularly suited for detailed schematic views and batch process monitoring. The unit can also serve as a thin client for virtualized automation environments.
Compliance and Certifications
The Lauer 200-V02366 is CE marked and certified to UL 61010-1 and CSA C22.2. It meets FCC Part 15 Class A and EN 55032 emissions standards. RoHS compliant. Additionally, it has been tested for marine applications according to DNV GL standards.
Ordering Variants
Variants include models with additional fieldbus interface cards, extended temperature range, and stainless steel bezel for food and beverage industries. The unit can be ordered with pre-installed runtime licenses for Lauer Configurator or third-party SCADA software.