Detailed explanation of interfaces and DIP switches
List of connection panel interfaces: X1S1 (3-pin MC1.5/3-G-3 STHT socket, DC 24V power supply, equipped with FK-MCP 1.5/3-ST-3.5 docking terminals), XUSB1/2 and XUSB3/4 (USB-A female socket × 4), XSER (RJ45 female socket, CDI data interface, purple identification), XVID (RJ45 female socket, CDI image interface, black identification), XUSBIN (USB-B female socket, USB2.0 connected to control cabinet PC, maximum wire length of 5 m, requiring high-speed USB2.0 cable in Chapter 5), functional grounding FE (M5 thread, circular wire nose). Insufficient shielding can lead to malfunctions - only shielded cables and metal/conductive connector shields with large-area shielding support can be used.
X1S1 pin definition: 1 pin+24 V, 2 pins 0 V (GND), 3 pins N.C. Only copper wires can be used for wiring terminals.
S1 DIP switch is only valid for S1/2 (S1/1 has no function): OFF=control cabinet PC cable length ≤ 30 m; ON=cable length>30 m.
The linkage relationship between USB speed and XSER cable length (core configuration logic):
XSER cable length S1/2 status USB speed note
≤ 5 m OFF 12 Mb/s or 480 Mb/s (USB 2.0) 480 Mb/s requires an additional USB cable between the control cabinet PC and XUSBIN
5-30 m OFF 12 Mb/s Ensure that the connected device does not include a USB hub
>30 m ON 12 Mb/s does not support USB hub
The interference free USB 2.0 connection is only feasible for wires with a length of less than 5 meters. Warning: When the total current of all USB connectors exceeds 1 A, the VDP power supply will automatically shut off. A single port of 500 mA and a total of 1 A are the hard upper limits. Only devices that comply with USB specifications can be connected.

Installation and disassembly process
Installation prerequisite: Leave 50mm of space around the equipment to ensure heat dissipation and wiring; LED display cannot be covered; All cables are looped and secured with stress relief components; Try to stay as far away from noise sources as possible; Can only be installed vertically, with a maximum deviation of ± 45 ° from the vertical position; CDI cables must not be laid parallel to motor cables or other noise sources, otherwise the CDI connection may be disturbed.
IP65 protection retention conditions: The chassis for installing the monitor must be free of burrs, have sufficient mechanical strength and flatness - these conditions directly affect the actual protection level, and if necessary, measures such as reinforcing the installation frame must be taken.
Four step installation: ① Make 8 openings with a diameter of 5mm according to the installation size diagram; ② Remove the paper lining from the sealing strip on the back of the front panel; ③ Insert the monitor from the front to the back through the opening, and insert the M4 mounting bolt into the drilled hole; ④ Tighten the nut on the back to secure it.
Tightening torque (excessive torque is strictly prohibited from damaging the mechanism): M2.5=0.4 Nm, M3=0.7 Nm, M4=1.4 Nm, M5=2.8 Nm. After maintenance and disassembly, tighten according to this table.
Dismantling: Disconnect the display terminal → Remove all connected cables → Remove all installation nuts → Carefully push the monitor out of the installation hole from the back to the front.
Key rules for electrical wiring and functional grounding
230 V/400 V wiring level (overvoltage category I/II/III zones): The main line entering the control cabinet (16 mm ² green and yellow line connected to the cabinet body, 14 mm ² connected to the equipment, 6 mm ² connected to the functional ground of all casing components) passes through a fuse (recommended motor protection switch) → Transformer according to EN 60742 → Overvoltage category II zone 230 V power supply service terminal → VAP01 power supply unit outputs DC 24 V to X1S1, with a maximum length of 24 V output line of 4 m. Danger warning: Power supply units designed for overvoltage category III can be connected to category II or III power grids; But power units designed as Class II can only connect to Class II power grids - misconnecting a protective extra low voltage (+24 V) power source to a mismatched grid can endanger life due to electric shock.
The lack of functional grounding (FE) leads to damage to electronic components - this is the most critical rule in the wiring of this device: if the functional grounding between VDP and control cabinet PC is not connected, once the voltage supply is interrupted and only one device is powered on again, the potential difference between VDP and PC will burn out the electronic components. The best solution is to directly connect the VDP and the control cabinet PC to the functional ground; If the functional ground is connected to the neutral point, the control cabinet PC must also be connected to that neutral point.
CDI connection three-step: ① Grounding the connection function; ② Display purple XSER → XSER of control cabinet PC; ③ Monitor black XVID → Control cabinet PC XVID.
CDI cable bending radius (diameter 7.4 mm): one-time installation bending 4 x wire diameter; Frequently move the minimum wire diameter of 8 times; Regularly move the optimal 12.5 x wire diameter. Avoid applying tensile, compressive, torsional, and lateral mechanical stress to the RJ45 female connector - mechanical stress can cause operational interruption; Cables should be clearly marked with wire markers or clamps to prevent accidental replacement and potential malfunctions.