CDI maximum line length is distinguished by resolution: 1280 × 1024 pixels (VDP 60.3 only) up to 60 m; 1024 × 768 pixels (VDP 40.3 and 60.3) up to 70 m; 800 × 600 pixels (all VDP xx. 3) up to 80 m. Longer line lengths can be achieved through Y allocator.
Resolution and hot swappable constraints: The display resolution can only be detected after the control cabinet PC restarts - when inserting or unplugging VDP during VDP operation or connecting VDP during PC startup, only VDP with the same resolution as the current PC can be reconnected to ensure that the screen output of connected and disconnected devices can automatically switch without keyboard operation.
UPS power supply scheme and overall connection
The core value of the UPS solution is that if the display terminal is directly connected to a 24V power supply without going through UPS, the display will immediately turn black when the power is cut off, and users will not be able to perform any operations during the shutdown process of the control cabinet PC; When the monitor and control cabinet PC are connected to the external UPS's "24 V Out", users can still operate the display terminal during the power-off process.
Recommended wiring scheme (VAU 01.1, X1S1 in/X1S2 out): 24V power supply unit → UPS 24V IN → UPS 24V OUT → Phoenix UK6-FSI/6 automatic fuse connection terminals (control cabinet PC branch TCP 10A, display terminal branch TCP 4A) → to control cabinet PC X10 and display terminal X1S1 respectively; The 16A incoming line, 6mm ² (blue) 0V line, and PE row 10/6/6/10mm ² green and yellow lines are respectively connected to the display terminal FE, control cabinet PC FE, UPS FE, and power supply unit. The downgrade plan of only connecting the PC to UPS and not connecting the monitor to UPS is also supported. The USB cable is connected from the UPS to the control cabinet PC for communication, and the control cabinet PC is connected to the display via USB (XUSBIN, maximum 5m).
The debugging process is extremely simple: the product can be used directly without any configuration.
Button system and LED diagnosis
The membrane keyboard is designed to be language independent and comes pre installed with English keyboard drivers for use in other language user interfaces. The factory delivery settings cannot be changed; When connecting an external USB keyboard (such as VAK), the corresponding keyboard driver needs to be selected.
Key partition: The left L1-L8 and right R1-R8 are eight machine function keys (M-keys); The allocation of F2-F9 function keys and OP2-OP9 operation keys is determined by the application software. The OP key transmits combination key codes to the operating system (OP2-OP9=<CTRL>+<SHIFT>+<ALT>+<F2... F9>, Prog=<Ctrl+Q>, INFO=<Ctrl+I>). M-keys have three reading paths: ① as a USB keyboard signal transmitted to the PC (when UpperClassFilter is activated, L1-L8 maps<Ctrl>+<Alt>+<LShift>+<1... 8>, R1-R8 maps<Ctrl>+<Alt>+<RShift>+<1... 8>); Map F13-F20 and F21-F24 with four OEM special characters when not activated - if using a USB dedicated keyboard, insert the corresponding Ctrl combination code into the data stream upon detecting the M-key code); ② The CDI interface serial connection bit encoding is transmitted to the control cabinet PC, which can be output from the station card (including GSD files) via Profibus DP, and a wiring terminal block is provided to transfer to the expansion card; The transmission protocol is guaranteed by hardware, and when the connection is disrupted or interrupted, the M-key bit that arrives is disabled after 10 ms; ③ Output by byte via Profibus DP (Byte 0=Bit7-0 corresponds to R8 – R1, Byte 1=Bit7-0 corresponds to L8 – L1), key=1, not pressed=0.
Four LED status diagnosis (top of panel):
Disposal of LED status meaning
Power green is always on and running normally (this VDP is the active end under the Y distributor) -
Green flashing and no serial connection to the control cabinet PC → Check the cable; Inactive VDP under Y allocator → No action required
Turn off the DC 24V power supply and check the power supply voltage
HDD Yellow Always Bright Hard Disk Access -
Yellow flashing SMART analysis found error in replacing hard drive
Temp red flashing control cabinet PC fan does not rotate or the speed is too low. Check the control cabinet PC fan
Red constant brightness temperature>50 ℃ reduces the surrounding air temperature!
UPS red constant light control cabinet PC is running in UPS mode, power supply is unavailable, restore power supply, execute controlled restart of control cabinet PC
Note: Not all LEDs are activated with the connected control cabinet PC, so not all warnings and information will be displayed - supplementary information must be consulted in the corresponding documentation of the control cabinet PC.
Troubleshooting and Maintenance
Typical fault handling table:
Troubleshooting measures
No image display connection power supply voltage and check X1S1; Correctly connect the CDI cable and check XVID and XSER; Set the screen output to "VDP" in the graphics card driver; Power on VDP before or simultaneously with the control cabinet PC