Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

SIEMENS SIMATIC HMI Basic Panels Operating Manual

来源: | 作者:FAN | 发布时间 :2025-11-27 | 325 次浏览: | Share:

1. Preparation before connection

Tools and accessories: Prepare a No. 2 Phillips screwdriver, a No. 3 Phillips screwdriver, a TX20 Phillips screwdriver, a crimping tool, power terminals, and a 24VDC power supply (current must meet equipment specifications, refer to the "Power supply" section).

Connection sequence: Strictly follow the order of "equipotential connection → power connection → configuration PC connection → PLC connection", do not reverse, and provide sufficient strain relief for all cables to avoid contact breakage or wire detachment.

2. Equipotential connection

Connection necessity: There may be potential differences between equipment components separated by space. If the shielding layer of the data cable is grounded at both ends and connected to different equipment components, it may generate large balanced currents and damage the interface; Systems powered by different power sources may also generate potential differences, and the risk needs to be reduced through equipotential connections.

Connection requirements:

Conductor requirements: The equipotential bonding conductor should be made of copper or galvanized steel, with a cross-sectional area of not less than 16mm ² (to ensure maximum balanced current), and should establish a large surface area contact with the grounding/protective conductor to prevent corrosion.

Shielding treatment: The shielding layer of the data cable needs to be clamped flat and clamped onto the equipotential rail near the HMI device using a suitable cable clamp.

Wiring requirements: The equipotential bonding conductor and data cable should be laid in parallel with minimal gap.

Prohibited items: The cable shielding layer shall not be used for equipotential connection. MPI and PROFIBUS DP networks must use cables with sufficient cross-section, otherwise it may damage the interface module.

Operation steps:

Connect the functional grounding of the HMI device with a grounding wire with a cross-sectional area of 4mm ².

Connect the grounding wire to the equipotential rail.

3. Power connection

Cable requirement: Use power cables with a maximum cross-sectional area of 1.5mm ².

Cable handling:

Strip the ends of the two power cables by 6mm.

Install cable conduit at the exposed end of the cable.

Secure the cable conduit at the end of the cable using crimping pliers.

Connection steps:

Insert two power cables into the power terminals using a Phillips screwdriver and secure them in place.

Connect the HMI device to the power terminal and ensure correct polarity (distinguish between+24VDC and GND).

Turn off the power supply.

Insert the remaining two cable ends into the power terminal and secure them, then confirm the polarity again.

Safety warning: Only 24VDC power supply can be used, and the power supply current must comply with the equipment specifications (refer to the "Specifications" section). Incorrect specifications of power supply may cause equipment damage.

4. Programming equipment and configuration PC connection

Programming Device Connection (Basic Panel DP):

Function: Can be used for project transfer and device image transfer, but cannot be used to restore factory settings.

Step: Turn off the HMI device, confirm that the DIP switch on the back of the device is in the designated position, and connect the RS485 PROFIBUS connector to the device.

Configure PC connection:

Function: Supports project transfer, device image transfer, and factory reset.

Basic Panel DP Connection: Use PC/PPI cable or USB/PPI cable for connection, and configure the DIP switch of the cable to set the transmission rate (such as 115.2kbps corresponding to DIP1=1, DIP2=1, DIP3=0). If the connection is lost during operating system updates, the bit rate needs to be reduced; When using high bit rates, PC/PPI cable version 3 or above is required (version number printed on the cable, such as "E stand 3").

Basic Panel PN Connection: Use the "IE FC RJ45 Plug 2x2" RJ45 plug (order number 6GK1901-1BB10-2AA0) and connect it with a standard CAT-5 Ethernet cable; Attention should be paid to Ethernet data network security, and users need to ensure network security themselves to avoid risks such as device overload.

5. PLC connection

Connection prerequisite: The HMI device must have an installed operating system and executable projects.

Connection specification: When wiring, the data line should be parallel to the equipotential connecting conductor, and the shielding layer of the data line should be grounded.

Basic Panel DP Connection:

Direct connection: Connect SIMATIC S7-200, S7-300/400, S7-1200 through RS422/RS485 interface.

Converter connection: Connect third-party PLCs such as Modicon Modbus and Allen Bradley DF1 through the converter in the accessory (such as RS422 to RS232).

Interface configuration: There is a DIP switch on the back of the device for RS422/RS485 interface configuration. The factory default setting is to communicate with SIMATIC PLC through RS485, which needs to be adjusted according to the DIP switch setting diagram on the back of the device (such as RTS signal position).

Basic Panel PN Connection:

Connecting devices: Connect SIMATIC S7-200, S7-300/400, and S7-1200 with PROFINET interface via PROFINET/LAN.

  • EPRO MMS6120 Dual Channel Speed Monitor 9100-00002-10
  • EPRO MMS6120 Dual Channel Overspeed Protection Monitor 9100-00002C-08
  • EPRO PR6423 and PR6424 Eddy Current Displacement Probes
  • EPRO PR9268/300-000 Seismic Velocity Sensor
  • EPRO MMS3120/022-000 Dual Channel Vibration Monitor 9100-03047-01
  • EPRO MMS6823R 9100-00001-06 Dual Channel Module
  • EPRO PR6423/10R-030-CN Displacement Sensor
  • EPRO PR6423 Eddy Current Displacement Sensor
  • EPRO PR6423/002-030-CN+CON021 Eddy Current Sensor
  • EPRO PR9376/20 Contactless Speed Sensor
  • EPRO PR6423/002-001-CN Eddy Current Probe
  • EPRO RSM020 Relay Output Module
  • EPRO SDM010 Signal Distribution Module
  • EPRO PR6423/010-010-CN Eddy Current Sensor
  • FANUC A81L-0001-0165 Servo Motor Cable
  • FANUC A05B-2452-C900 Teach Pendant Cable
  • FANUC A90L-0001-0422#50 Cooling Fan 9WF0624H7D05
  • FANUC A860-0326-T103 Alpha iA64 Pulse Coder
  • FANUC A860-0315-T101 Alpha i Pulse Coder
  • FANUC A860-0302-T001 Alpha Series Pulse Coder
  • FANUC A230-0604-X003 Operator Panel
  • FANUC A20B-8200-0927 I/O Link Module
  • FANUC A20B-2902-0290/08C Communication PCB
  • FANUC A20B-2901-0763/02A I/O PCB Module
  • FANUC A20B-2901-066 Main PCB Board
  • FANUC A20B-2002-0040/07DR Servo Control PCB
  • FANUC A16B-2203-0073/02A Power Supply PCB
  • FANUC A06B-6114-H106 Alpha i Servo Amplifier
  • FANUC A06B-6089-H104 Alpha Servo Amplifier SVM1-80
  • FANUC A06B-6079-H208 Alpha Servo Amplifier Module
  • FANUC A06B-6079-H106 Servo Amplifier
  • FANUC A06B-6077-H106 Servo Amplifier
  • FANUC A06B-0116-B203#0100 Servo Motor
  • HIMA F3DIO20/802 Digital I/O Module 982200442
  • HIMA 80105 Power Supply Module 984080105
  • HIMA X-DO2401 Digital Output Module 985210203
  • HIMA X-DI3201 Digital Input Module 985210201
  • HIMA F-PWR02 Power Supply Module for F-Series
  • HIMA K1412B / H51q-HRS Safety Controller 996141261 / 997205233
  • HIMA K7214 Power Supply Module 996721402
  • HIMA TM202-A00-B00-C00-D00-E00-G00 Analog Termination
  • HIMA TM521 Digital Input Termination Module
  • HIMA TM591-B00-G00 Termination Module HIMax System
  • HIMA KFD2-STC4-Ex1 SMART Transmitter Power Supply
  • HIMA KFD2-VR4-Ex1.26 Voltage Repeater Isolated Barrier
  • HIMA SB3073-EX Intrinsically Safe Barrier Module
  • HIMA H6200A Terminal Module for Safety I/O
  • HIMA Z7130 Power Supply Distribution Module
  • HIMA F8652E 984865264 Central Module HIQuad H51q
  • HIMA F8627 984862702 Communication Module HIQuad System
  • HIMA H41q-HS High-Speed Safety Controller B4237-1 997104237
  • HIMA F8652X Central Processing Unit 984865265
  • HIMA H4135 Safety Logic Solver 992413502
  • HIMA H51q-H High-Integrity Safety Controller B5233-2 997235233
  • HIMA F6217 Safety Controller 984621702
  • HIMA F3330 984333002 Digital Output Module
  • HIMA F7553 984755302 Communication Module
  • HIMA F7131 Power Supply Module
  • HIMA X-DO1201 985210204 Digital Output Module
  • HIMA H51q-HRS B5233-2 Safety Controller Module
  • HIMA F3231 16-Channel Digital Input Module
  • HIMA K9203A (996920360) Safety Relay Module
  • HIMA H51q-HS B5233-1 Safety Control System
  • HIMA F7131 Power Supply Monitoring Module
  • HIMA F8620/11 Central Module for HIQuad Systems
  • HIMA X-FAN 18 03 Redundant Fan Module for Safety Systems
  • HITACHI LYD000A Digital Input Module 8-Channel
  • HITACHI PS6000 Heavy-Duty Power Supply 24VDC 10A
  • HITACHI LBT010A Profibus-DP Communication Module
  • HITACHI LPD250A Power Supply Module 24VDC 5A
  • Hitachi LPT020A Industrial Power Module
  • Hitachi LPF240F Industrial Power Module
  • Hitachi LPU100A Industrial Power Unit
  • Hitachi PS6515 Industrial Power Supply Module
  • Hitachi PS6548 Power Supply Module
  • Hitachi LCE250B Communication Module
  • Hitachi LCE250A Communication Module
  • Hitachi LPA302P-1 Analog Input Module
  • Hitachi LPA210A Analog Input Interface
  • Hitachi LPA302A Analog Input Module
  • HITACHI PS6524 Switching Power Supply
  • HITACHI MPD310A Color Touch Screen HMI
  • HITACHI MPD110A Graphic Operator Terminal
  • HITACHI MPD060A Operator Interface Display
  • HITACHI LPP100A Power Supply Module
  • Hitachi LPD200A AC Drive Inverter
  • Hitachi LUD060A AC Drive Inverter
  • Hitachi LPD350A AC Drive Inverter
  • Hitachi LPD220A AC Drive Inverter
  • Hitachi LPA220A AC Drive Inverter
  • Hitachi LPA245A Analog Input Module
  • Hitachi LPU100H Central Processing Unit
  • Hitachi LYT000A Output Module
  • Hitachi LPF240A Power Filter Module
  • Hitachi LUD700A Display and Interface Unit
  • HITACHI LYA100A Analog I/O Module
  • HITACHI LYA220A Analog Input Module
  • HITACHI TD000A Temperature Controller
  • HITACHI LYA210A Analog Output Module
  • HITACHI LYD105A Digital Input Module
  • Hitachi LYA010A AC Drive Inverter
  • HITACHI 2-822037-A Servo Motor Controller
  • Honeywell CC-TAIM01 Analog Input Module
  • Honeywell 2104B2131 Temperature Transmitter
  • Honeywell 05704-A-0146 Industrial Pressure Transmitter
  • Honeywell 05701-A-0351 & 05701-A-0302 Control System Components
  • Honeywell 05701-A-0327 System 57 Interface Module
  • Honeywell S2024-2POS-SW2 Spring Return Actuator
  • Honeywell XFR824A Transformer Module 24VAC 40VA
  • Honeywell 05701-A-0284 & 05701-A-0302 System 57 Control Card
  • Honeywell SC-UCMX02 Universal Controller Module 51307198-276
  • Honeywell ISC-UCMX01 Safety Controller Module 51307195-175
  • Honeywell FC-SCNT02 Field Control Scanner Module
  • Honeywell FC-SCNT01 Field Control Scanner Module
  • Honeywell CC-TUIO41 Universal Input/Output Module
  • Honeywell CC-TUI041 Universal Input Module
  • Honeywell CC-PLAIH51 Analog Input HART Module
  • Honeywell XNX-UTAV-RNIF1 XNX Universal Transmitter
  • Honeywell FTA-T-02 Field Termination Assembly
  • Honeywell LG1093AA24 261A1812P012 Flame Amplifier Module
  • Honeywell CC-TCNT01 51308307-175 ControlNet Interface Module
  • Honeywell CC-TUI041 51306873-176 Universal Input Module
  • Honeywell 1569905-6131140220 Specialized Industrial Component
  • Honeywell QPP-0001 Quad Processor Pack Safety Manager
  • Honeywell PSU-240516 Power Supply Unit 24VDC 5A/16A
  • Honeywell CPB-0001 CPCHAS-0001 Control Processor Chassis
  • Honeywell SDO-0824 CCV1.3 Supervised Digital Output Module
  • Honeywell SDI-1624 CCV1.1 Digital Module