Features
IEEE802.3 Ethernet standard
Provides 10Base2 compliant communication
32-bit data bus
Transmission rate 10 MBit/s
Direct memory access to main memory, < 4% CPU overhead for operation
Optional battery for redundant battery backup of main memory
Description
These communication modules provide Ethernet communications to the system bus compliant with IEEE802.3 standard.
Communications module, compliant with 10Base2 (Cheapernet) for thin coax cable installations.
LED Displays
State
Off No supply voltage, module is isolated
Green Power supply on, module identified and ready to operate as configured.
Orange Power supply on, module identified and either:
— normal transitory state after module startup
— configuration mode of Boot Loader
Orange flashing Power supply on, module identified; module not connected to proper bus structure.
Red Power supply on and either:
— module not yet identified (normal for short time during module startup)
— error occurred during module test Battery (PM803F)
Off AC 800F is active, EI 811F not active
=>buffering from power supply module
AC 800F is off (no watchdog of the batteries voltage) =>buffering from battery.
Orange During battery recovery or start-up phase
Red Warning: battery low, no battery inserted, insufficient electrical contact etc.
Green battery inserted and data protection provided.
Battery (PM802F)
Off Sufficient buffer battery voltage
Orange Buffer battery not found or low (insufficient Page 12 June 2006 voltage).
Front Panel Connections
Coax connector
Technical Data
Rated voltage 3.3 V / 5 V, ±3%, from CPU board
Power consumption max. 2.0 W
Thin Ethernet 10Base2
RAM and real-time-clock buffering time
PM 803F PM 802F
New battery inserted ≥ 10 days ≥ 1,5 years
After “Low” warning ≥ 5 hours ≥ 10 days
Battery 3.6 V lithium battery, 950 mAh (not in the delivery)
Weight approx. 0.150 kg (without battery)
email:1583694102@qq.com