10.1-inch widescreen model:
XV-303-10-B00-A00-2B/2C (basic interface)
XV-303-10-C00-A00-2B/2C (Dual Ethernet)
XV-313-10-B00-A00-2C (rear installation, 1.5mm panel)
XV-313-10-B00-A11-2C (rear installation, 2.0mm panel)
15.6-inch widescreen model:
XV-303-15-C00-A00-2B/2C (front panel installation, dual Ethernet)

In depth analysis of technical specifications
4.1 Display Performance
Parameter 7.0 inches 10.1 inches 15.6 inches
Resolution 1024 × 600 1024 × 600 1366 × 768
Visible area 153.6 × 90.0mm 222.7 × 125.3mm 344.2 × 193.5mm
Contrast ratio 850:1 500:1 500:1
Brightness 400 cd/m ² 400 cd/m ² 400 cd/m ²
Backlight type LED, software dimmable LED, software dimmable LED, software dimmable LED
Backlight lifespan 50000 hours @ 25 ℃ 50000 hours @ 25 ℃ 50000 hours @ 25 ℃
Approximately 16.7 million colors (24th digit) Approximately 16.7 million colors (24th digit) Approximately 16.7 million colors (24th digit)
4.2 Power Requirements
The XV300 series uses 24 VDC power supply and must meet SELV/PELV safety requirements:
Rated voltage:+24 VDC
Allowable range: 19.2-30.0 VDC (rated voltage -20%/+25%)
Absolute limit: 18.0-31.2 VDC (including ripple)
Battery powered: 18.0-31.2 VDC (-25%/+30%), capable of withstanding 35V peak values of<100ms
Voltage sag tolerance: can withstand ≤ 10ms drop at rated voltage 24VDC, and ≤ 5ms drop at undervoltage 19.2VDC
Power consumption and current:
7.0-inch equipment: maximum 18W, current ≤ 0.6A@24V
10.1-inch equipment: maximum 14.4W, current ≤ 0.75A@24V
15.6-inch equipment: maximum 21.6W, current ≤ 0.9A@24V
The above power consumption includes USB module power consumption (2.5W)
4.3 Environmental adaptability
Work environment:
Temperature: 0 ° C to+50 ° C
Relative humidity: 10-95%, no condensation
Air pressure: 795-1080 hPa (altitude ≤ 2000m)
The influence of installation posture on temperature:
XV-303-70/10 and XV-313 series: When the tilt angle is ≤± 45 °, the maximum operating temperature is 50 ° C
XV-303-15: When the tilt angle is ≤± 10 °, the maximum temperature is 50 ° C; when it is ≤± 45 °, the maximum temperature is 45 ° C
Storage and transportation:
Temperature: -20 ° C to+60 ° C
Relative humidity: 10-95%, no condensation
4.4 Protection level and certification
Protection level: front panel IP65/NEMA 4X/12, rear IP20
UL Certification: Compliant with UL 61010-2-201, Document Number E205091
CE certification: compliant with the EU EMC Directive (2014/30/EU) and ATEX Explosion Protection Directive (2014/34/EU)
Classification society certification: DNV GL type certification, certificate number TAA00000NC (7.0 "and 10.1" models, requiring installation of power filter)
Explosion proof certification: II 3D Ex tc IIIC T70 ° C IP6x, suitable for dusty environments in Zone 22
4.5 Mechanical dimensions and weight
Installation of 7.0-inch front panel:
Dimensions: 196 × 135 × 51mm (width × height × depth)
Weight: 0.74kg
Installation of 10.1-inch front panel:
Dimensions: 269 × 174 × 58mm
Weight: 1.13kg
15.6-inch front panel installation:
Dimensions: 401.7 × 254.9 × 67.6mm
Weight: 3.25kg
7.0-inch rear installation:
Dimensions: 209 × 151 × 51mm
Weight: 0.8kg
10.1 inch rear installation:
Dimensions: 282 × 190 × 58mm
Weight: 1.21kg
Installation and wiring specifications
5.1 Preparation before installation
Installation work must be carried out by qualified electricians and strictly comply with the following safety regulations:
Disconnect the device power and prevent accidental reconnection
Verify equipment and power isolation
Grounding and short circuit
Cover or isolate adjacent live parts
Comply with the requirements of EN 50110-1/-2 (VDE 0105 part 100)
5.2 Hole Requirements
Front panel installation (XV-303):
Installation panel thickness: 2mm ≤ d ≤ 5mm
Hole flatness: ≤ 0.5mm, surface roughness Rz ≤ 120
The opening size needs to be precise to ensure that the sealing ring is uniformly compressed
Rear installation (XV-313):
A00 version: Installation panel thickness d=1.5mm ± 0.1mm
A11 version: d=2.0mm ± 0.1mm
M4 × 12 bolts need to be welded on the panel, with the position referring to the installation dimension diagram
5.3 Ventilation and heat dissipation
XV300 adopts natural convection cooling, and the following minimum spacing should be ensured during installation:
Equipment surroundings: ≥ 30mm
Distance from heating elements (such as heavy-duty transformers): ≥ 150mm
Do not block the ventilation openings above and below the equipment
5.4 Functional grounding
Proper functional grounding is crucial for electromagnetic compatibility and anti-interference performance:
Wire cross-sectional area: ≥ 1.5mm ² (AWG16)
Wire length: ≤ 350mm
Grounding bolt: M4 × 8, tightening torque 1.3Nm
Recommend using M4 perforated terminals with an inner diameter of 4.3mm and an outer diameter of ≤ 8mm
5.5 Power Wiring
The power connector adopts MSTB 2.5/3-ST-5.08 pluggable terminals:
Pin definitions:+(24V), n.c. (empty), - (0V)
Wire specification: 0.75-2.5mm ² (AWG18-12)
Stripping length: 7mm
Tightening torque: 0.6-0.8Nm
The power supply must come from a SELV power supply that complies with IEC 60950 or a low-voltage power supply that complies with UL 61010-2-201.
Interface Explanation and Connection Guide
6.1 SD card interface