Bus coupler (fieldbus)
Model (order number) bus characteristics
IBS IL 24 BK-T/U-PAC (2861580) INTERBUS supports branch bus terminals, Inline plug bus connection, 48.8 mm
IBS IL 24 BK-LK/45-PAC (2862165) INTERBUS fiber optic connection 45 ° outgoing line, 85 mm
IBS IL 24 BK RB-LK-PAC (2861506) INTERBUS with remote bus branch, fiber optic
IL PB BK DI8 DO4/EF-PAC (2692322) PROFIBUS DP/V1, PROFIsafe compatible, IO Link calls, EF output
IL PB BK DP/V1-PAC(2862246) PROFIBUS DP/V1 2 A @ UL,D-SUB
IL DN BK DI8 DO4-PAC (2897211) DeviceNet TWIN-COMBICON connection, including CLIPFIX 35 end gear
IL CAN BK-TC-PAC(2718701) CANopen 2 A @ UL
IL MOD BK DI8 DO4-PAC(2878696) Modbus RTU (ASCII) D-SUB,80 mm
The corresponding Block IO (ILB) version covers combinations such as DI16/DI32/DO16/DO32/DI8 DO8/DI16 DO16/AI4 AO2, with 2/3 line connections and bus connections through Inline plugs or D-SUB/TWIN-COMBICON.
Power supply and segmented terminals
Power terminals (12.2 mm): IB IL 24 PWR IN-PAC (8 A), PWR IN/2-F (with fuse 6 A), PWR IN/2-F-D (with fuse+diagnostic 4 A); IB IL 120/230 PWR IN series (120/230 V AC, including isolation terminals, 36.6 mm);
Potential distribution terminals: IB IL PD 24V-PAC (US → 8 contacts), IB IL 24 PD GND-PAC (GND → 8 contacts);
Boost terminal: IB IL 24 PWR IN/R-PAC is used to boost the communication power supply and I/O voltage (logic maximum 2 A, 8 A @ UM/US, 48.8 mm); PWR IN/R/L-0.8A-PAC is specifically designed for communication power supply;
Segmented terminals: IB IL 24 SEG (8 A), SEG/F (fuse 6 A), SEG/F-D (fuse+diagnostic), SEG-ELF (electronic fuse+diagnostic 2.5 A) - the hardware foundation for implementing selective segmented protection.
Digital I/O terminals (12.2mm basic width, 48.8mm high-density version)
Digital input: 1 channel 120/230 V AC; 2-channel NPN; 4 channels; 8-channel single/4-wire (IB IL 24 DI 8/T2-PAC compliant with EN 61131-2 Type 2); 16/32 channel HD version (single wire connection);
Digital output: 1 channel 12-253 V AC 500 mA; 2-channel 24 V DC 2 A/NPN/EDO (parameterized output behavior); 4/8 channel 500 mA single or 4-wire, 8-channel 2 A, 8-channel NPN 1 A; 16/32 channel version;
Relay terminals: IB IL 24/230 DOR1/W (lamp load 3 A), DOR1/W-PC (inductive and capacitive load 2.6 A), DOR2/W (2 x SPDT, 5-50 V AC/5-120 V DC 2 A), DOR4 series (4 x SPDT), DOR4/HC-PAC (4 contacts 5-253 V AC maximum 10 A, high turn-on current); DOR LV-SET provides isolation terminals for relay output terminals.
Analog quantity and temperature terminal
Analog inputs: AI 2/SF (2-channel 16 bit universal), AI 2-HART (2-channel isolated, supporting HART sensors), AI 4/U (differential voltage 12 bit), AI 4/I (differential current 13 bit), AI 4/EF (with actuator power supply, overload protection, bus synchronization ≥ 1 ms, 16 bit), AI 8/SF and AI 8/IS (8-channel, including 0-25 V/± 25 V/0-50 V, 0-40 mA/± 40 mA range, multiplexing mode);
Analog outputs: AO 1/SF and AO 2/SF (16 bit, 500 Ω load, short circuit protection), AO 2/U/BP (± 10 V 16 bit), AO 2/UI (12 bit short circuit protection), AO 4/8/U/BP (4 or 8 output, short circuit protection, defined fast turn off behavior);
Temperature terminals: IB IL 24 TC (motor PTC thermistor evaluation, 1 input 1 output), TEMP2 RTD (2-channel 16 bit), TEMP2 UTH (2-channel thermocouple), TEMP4/8 RTD (2/3-wire or 4-wire connection, high-precision version with 4-wire connection).
Measurement and open-loop control terminals
Strain gauge measurement: IB IL SGI 2/F (extremely fast ≥ 1 ms, bus synchronization), SGI 2/P (high precision, RS-485 external display), SGI 1/CAL (can be calibrated by EC type approval, up to 3000 spacing values, matched with SGI EU CALSET calibration kit);
Power measurement: IB IL PM 3P/N/EF (3-phase+neutral wire, direct current acquisition of 1 A or 5 A, maximum outer conductor voltage of 690 V AC L-L);
Power level terminals: IB IL 400 MLR 1-8A (electromechanical load relay direct starter, 3.7 kW/400 V AC), ELR 1-3A (electronic load relay direct starter 1.5 kW), ELR R-3A (electronic reversible starter);
Positioning/Counting/PWM: IB IL SSI (single axis point-to-point absolute value SSI positioning, fast/slow motion principle), SSI-IN (SSI absolute value position reading, maximum 25 bit resolution), CNT (counter, 100 kHz, 24 bit binary counting, pulse generator), DI 8/S0 (8-channel S0 pulse encoder counter, 32-bit counting range), INC-IN (incremental encoder position, 25 bit actual value), IMPULSE-IN (magnetostrictive length measurement system position reading, 5 μ m position resolution), PWM/2 (2-channel PWM, pulse/direction interface control stepper motor power stage, maximum 50 kHz @ 5 V/500 Hz @ 24 V).
Communication terminal
Serial interface: IB IL RS UNI (configurable RS-232 or RS-485/422, process data only, 250 kbaud), RS 232/RS 232-PRO (38.4 kbaud), RS 485/422 and RS 485/422-PRO;
Special protocol: IB IL DALI/PWR (single channel DALI master station+integrated DALI power supply, safe electrical isolation, 61mm) and DALI/PAC extension terminals; IB IL MBUS (single channel M-bus master station, up to 30 M-bus devices, 19.2 kbaud); SRC-RS485 EVC EnOcean wireless receiver is used in conjunction with RS 485/422-PRO;