Interface differences between T1 and T5 options
T1 (single ramp): Reserved "internal command value" and "reserved" signal pins, the measurement signal includes the actual value x, command value w, and ramp time t.
T5 (Five Slope+Measurement Point Switching): Added module 10 slope time selection logic (Ramp call ups 1 to 4, 4-quadrant operation 4Q) and module 20 measurement point switching switch; Upgrade the measuring socket to a switchable "v" socket, and read 16 internal measuring points through the panel measuring point selection switch (0-F positions):
Signal gear measurement signal v
Internal command value 0 ± 100% ≙ ± 10 V
Instruction value call 1-4 1-4 ± 100% ≙ ± 10 V
Zero offset "Zw" 5 ± 30% ≙ ± 3 V
Command value synthesis signal 6 ± 100% ≙ ± 10 V
Slope output signal 7 ± 100% ≙ ± 10 V
Zero offset "Zx" 8 ± 30% ≙ ± 10 V
Gear 9 not connected -
Slope time t1 – t5/current t A – E/F 10 mV... 10 V (according to the voltage time conversion table on page 3)
T5 front panel LED adds an additional 4Q (four quadrant operation) and T (reserved); Jumper J4 (step function) defaults to On at the factory (opposite to T1's Off), while the rest of J1/J2/J3 have the same factory settings.
Quick Overview of Technical Data
Project specifications
Working voltage UB 24 VDC+40% -20% (upper limit 35 V/lower limit 18 V)
Power consumption/current<24 VA/<2 A
Delay in fuse 2A, replaceable
Command value 1-4 0... ± 10 V, Re>100 k Ω (with M0 as reference)
Command value 5 (differential) 0... ± 10 V, Re>50 k Ω
Command value 6 (current) 4... 20 mA, load RB=100 Ω
External slope time 0...+10 V, Re=10 k Ω (internal lifting to+15 V)
Digital input threshold 8.5 V... UB → ON; 0... 6.5 V → OFF (Re>100 k Ω)
Set range Zw zero ± 30%; W1-w4 instruction values 0... 110%; Slope t1- t5 20 ms... 5 s (switchable to 0.2... 50 s); Step S ± 0... 50%; Amplitude G ± 0... 110% (corresponding to a step of 0%)
Output command value ± 10 V ± 2%/2 mA; actual value ± 2.5 V ± 2%/2 mA; measurement signal (option 5) ± 10 V ± 2%; Ready>16 V/50 mA (<1 V in case of fault, Ri=10 k Ω); Voltage stabilization ± 10 V ± 2%/25 mA short circuit protection
Connect a 48 pin multi-point plug, DIN 41612 F-type; Euro card 100 × 160 mm, DIN 41494
Temperature operation 0... 50 ° C; storage -25...+85 ° C; net weight 0.17 kg
EMC、 Climate and mechanical load environment simulation testing information can be found in data table 30119-U; project planning and maintenance extension information can be found in document 30119-B.
Panel elements and jumper configuration (debugging core)
Front panel elements (T1/T5 universal):
LED: smiley face=ready (green); Lock shape=Enable (yellow); -1 "=External inversion; T5 also has "4Q" and "T";
Measuring sockets: x (actual value), w (command value), t (ramp time, T1)/v (T5 switchable measuring point), ⊥ (measuring zero point);
Panel potentiometers: Zw (zero calibration), w1-w4 (command values 1-4), t (ramp time); T5 is from t1 to t5);
Adjustable potentiometers on the card: Gw+/Gw − (positive/negative command value amplitude attenuator), S+/S − (positive/negative direction step level), Zx/Gx (board zero point and amplitude).
Jumper function matrix (●=factory settings; solid=closed; hollow=open):
Jumper function status A status B
J1 reverse phase (closed) not reverse phase ● (open)
J2 slope function Off On ●
J3 slope time range 0.2... 50 s (closed) 0.02... 5 s ● (open)
J4 step function T1: Off ●/T5: On ● Another gear
J5 and J6 are reserved (no function), and J7 is reserved for special functions. Once the sealed potentiometer is adjusted, the warranty becomes invalid - it is important to distinguish between panel adjustable potentiometers and factory seals during debugging.
Suggestions for Engineering Debugging Process
Wiring verification: Check the 48 pin DIN 41612 F-type plug according to the diagram; Confirm that the internal command value is 0% when the current input is not connected (to avoid misjudging valve zero drift);
Power supply verification: 24 VDC within the range of 18-35 V, check the 2A fuse and reverse polarity protection; The green "ready" LED lights up;
Zero point calibration: adjust the potentiometer Zw to zero within ± 30% range; T5 can directly read Zw/Zx offset for auxiliary calibration by measuring the switch position 5/8 at the measuring point;
Command value calibration: Check P → A/P → B and signal polarity according to the flow chart; If necessary, close J1 or connect an external inverted signal;
Slope setting: Verify the current slope time by comparing the voltage of the t/v socket with the conversion table; Close J3 to enter the range of 0.2... 50 seconds when slow start stop is required; The automatic rollback of internal default values in disconnected scenarios is a key design for reliability;
Characteristic curve correction: Set the S+/S - step level (0... 50%) and Gw+/Gw - amplitude (0... 110%) according to the hydraulic system requirements to eliminate valve zero dead zone and bilateral asymmetry;
Enable joint debugging: Verify the activation of the enable LED and power output stage, and confirm that the valve opens slowly according to the ramp time;