GE IS200JPDDG1A - Power Distribution Board
Part Number IS200JPDDG1A Manufacturer General Electric Country of Manufacture As Per GE Manufacturing Policy Series Mark VIe Function Module Availability In StockThe IS200JPDDG1A is a DC Power Distribution Board developed by GE. It is a part of the Speedtronic Mark VIe control system. The DC power distribution board (JPDD) board is used to distribute a single DC power output to multiple loads. It can be used with a single input of 24 V, 48 V, or 125 V dc. Each load has a switch for maintenance purposes and fuses with local indicator light. JPDDG1A has 15 A 5 x 20 mm (0.20 x 0.79 in) fuses for wire protection.
JPDDG3A has empty fuse holders that accept a 31.75 x 6.35 mm (1.25 x 0.25 in) fuse. Typical applications include DC relay and solenoid control power, and contact wetting. Each output includes a fuse, a switch, and a lamp to indicate the presence of output voltage. JPDD is not intended for power distribution to the I/O packs. IS200JPDDG1A Inputs Multiple JPDD boards can receive power from a single Main Power Distribution Module branch circuit. Power input can be either 125 V dc, 48 V dc, or 24 V dc nominal. Two 2-Pin Mate-N-Lok connectors are provided for 125 V dc power. One connector receives input power and the other can be used to distribute 125 V dc power to another JPDD board in a daisy chain fashion.
Two 4-pin Mate-N-Lok connectors are provided for 24/48 V dc power. These perform functions similar to those of the 2-pin connectors above. The 4-pin connector permits parallel connection of two pin-pairs for increased current capacity. It is expected that neither side of the dc power input is grounded. Outputs Six identical output circuits are provided. Each output circuit includes two fuses, a switch with a pair of isolation contacts on each side of the output, and a green lamp to indicate the presence of voltage across the output terminals. The provision of a fuse and switch contact on each side of the DC path allows the use of this board with floating power sources. Configuration There are no jumpers on JPDD.
Check the position of the six output load switches. It is possible to use other fuse ratings with this board to provide specific branch circuit ratings. A typical series of fuses that work with this board is the Bussmann ABC series of fuses with ratings from 脗录 A through 15 A. Fuses above 15 A shall not be used with this board. If alternate fuse ratings are used, the configuration of the board requires the insertion of the proper fuse in each branch circuit. IS200JPDDG1A Installation JPDD is held in a plastic holder, which mounts on a vertical DIN rail. When installing the JPDD, it is important to provide a ground lead from TB1 to the system ground.
This creates a ground path for the metal switch bodies. Power input can be 24 V dc, 48 V dc, or 125 V dc, but only one voltage level at any given time. Do not mix voltages. For cable destinations, refer to the circuit diagram. TB1 should be connected to the system ground.Module manufactured by General Electric as part of the Mark VI/VIe Series used in gas turbine sppedtronic control systems
The Series 90* -30 CPU374 PLUS provides a built-in enhanced Ethernet interface that provides TCP/IP communications with:
▪ Series 90, PACSystems, and VersaMax PLCs
▪ Host computers running the Host Communications Toolkit or CIMPLICITY software
▪ Computers running the TCP/IP version of the programming software CPU Features
▪ High speed Boolean and non-Boolean processing provided by a 586-class 133MHz processor
▪ Two Ethernet ports: 10/100 Mbytes (one IP address) with a built-in, auto-sensing Ethernet switch
▪ Support for EZ Store Device allows you to download a program without a PC
▪ 240KB of user memory Key Ethernet Features
▪ Full PLC programming and configuration services
▪ Periodic data exchange using Ethernet Global Data (EGD) and EGD commands to read and write PLC and EGD exchange memory over the network
▪ TCP/IP communication services using SRTP
▪ Support for SRTP Client (Channels)
▪ Modbus/TCP Server, supporting Modbus Conformance classes 0, 1, and 2.
▪ Modbus/TCP Client, supporting Modbus Conformance classes 0, 1, and Function Codes 15, 22, 23, and 24 for Conformance class 2.
▪ Remote PLC monitoring from a web browser
▪ Comprehensive station management and diagnostic tools
Features
Single-Slot Module
SNP/SNP-X Protocol (master, slave)
CCM Protocol (master, slave, peer)
RTU Modbus Protocol (slave only)
Supports connection to MS-DOS
or Windows
programming and configuration software package (monitor only)
12 Mhz, 80C186 Microprocessor
Two RS-422/RS-485 or RS-232 Serial Ports
CCM, RTU and SNP/SNP-X Available on Either or Both Ports
Simultaneous Communications on Both Ports (up to 9.6 Kbps, or 19.2 Kbps individually)
High Performance Access to PLC Memory
Three Status LEDs
Reset pushbutton
Soft Switch Configuration (no switches or jumpers)
No Battery Required
email:1583694102@qq.com
wang@kongjiangauto.com