Welcome to the Industrial Automation website!

NameDescriptionContent
HONG  KANG
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

DEIF LSU-112DG generator set parallel control unit

来源: | 作者:FAN | 发布时间 :2026-03-04 | 12 次浏览: | Share:

2.3 Self monitoring function

The LSU-112DG is equipped with a built-in microcontroller and a self-monitoring circuit. The green "POWER" LED is constantly on, indicating that the power supply is normal and the program is running correctly; If the LED flashes at 2-3Hz, it indicates that although the power supply is normal, the program is running abnormally, and the status output terminal (17-18) will be disconnected (fault indication). This design greatly facilitates on-site troubleshooting.


Detailed explanation of core functions

3.1 Speed Control Output (SG ▲/SG ▼)

LSU-112DG provides two relay contact outputs, which are respectively used to control the "speed increase" and "speed decrease" of speed regulating motors or actuators. The controller adopts a P controller (proportional control) internally, which generates pulse width modulation signals based on frequency/power deviation. The key parameters include:

T-N (minimum on-time): Within the proportional band, the minimum duration of the control pulse can be adjusted within a range of 25~500ms.

X_P (Proportional Band): Set a deviation range within which the pulse duty cycle is proportional to the deviation. For frequency control, the proportional band is 0~± 2.5Hz; for power control, it is 0~± 50% of the rated power.

T-P (cycle time): The time interval between the starting points of two adjacent pulses, usually 10 times the T-N, but can also be selected as 5, 15, or 20 times the T-N through jumper wires.

Deadband: Set a deviation zone that does not generate adjustment pulses to avoid frequent actions of the governor. The default power dead zone is ± 2%, and the default frequency dead zone is ± 0.1Hz, both of which can be adjusted through jumper wires.

When using a DC servo motor, it must be driven by an external intermediate relay and a transient suppressor must be connected in parallel to the relay coil to protect the contacts.

3.2 Unload Input

Terminals 33-34 can be connected to a passive normally open contact. When the contact is closed, LSU-112DG will control the unit to reduce load to zero power and automatically disconnect its power output (PS line) from the bus. This function is commonly used for preparation before unit disconnection or quick unloading in emergency situations.

3.3 Reference Input (Ref.) and Local Power Control

Terminal 35 is a reference input terminal used for fixed power control mode (such as the unit delivering constant power to the grid). The input signal is+0.5V to+5V DC (for terminal 36 "⊥"), corresponding to 10% to 100% of the rated power. This input is activated at 0.55V and deactivated at 0.45V. When this input is valid, LSU-112DG is still connected to the PS and FS lines, but the PS line only serves as an output (broadcasting the actual power of the machine to other units) and does not participate in the comparison. This means that the local machine no longer responds to load distribution, but instead sets a fixed output power while still participating in frequency synchronization.

Terminal 37 provides a+5V reference voltage output, which can be used to connect an external potentiometer to form a local power setting circuit.

3.4 Derating setting

The front panel of LSU-112DG is equipped with a derating potentiometer, which can adjust the corresponding generator capacity within the range of 50% to 100% (such as derating a 150kW unit to 100kW). After the reduction, load distribution will be based on the reduced capacity. For example, if a 100kW unit is connected in parallel with a 150kW unit that has been downgraded to 100kW, the total load of 125kW will be evenly distributed as 62.5kW+62.5kW. If the capacity is not reduced, it will be allocated as 50kW+75kW according to the actual capacity ratio. The derating function provides great flexibility for mixing different capacity units.

3.5 External frequency and power transmitter

If higher precision is required or to cope with unbalanced loads, LSU-112DG supports external transmitters:

External power input (terminals 31+, 32-): Connect 4-20mA DC signal, corresponding to 0-100% power. Recommend using DEIF TAS-331DG.

External frequency input (not clearly indicated, but the document mentions that external frequency transmitters can be shared): Please refer to the application notes.

When an external power transmitter is connected, the built-in I × cos φ transmitter is automatically disabled.

Wiring and Configuration Guide

4.1 Overview of Terminal Functions

Terminal identification function description

1.3 X1/X2 auxiliary power input (AC or DC, depending on the model)

17,18 Sta status output (normally open contacts, closed during normal operation)

28,29 IL1 current transformer input (S1 connected to 28, S2 connected to 29)

31,32 Ext. P external power transmitter input (31+, 32-), short circuit when not in use

33,34 Uni load shedding input (connected to passive normally open contacts)

35 Ref. Reference input (0.5-5V corresponds to 10-100% power)

36 ⊥ public area (internally connected to all ⊥ terminals)

37+5V reference voltage output (for local potentiometer)

38,39 FS, ⊥ frequency sharing line and common terminal

  • EMERSON A6740 Displacement Case Expansion Monitor
  • EMERSON A6312/06 Speed Monitoring Module
  • EMERSON KJ4001X1-BE1 DeltaV Carrier Module
  • EMERSON SE3008 KJ2005X1-MQ2 DeltaV Controller
  • EMERSON KJ4001X1-CA1 DeltaV Terminal Block
  • Emerson PR6423/00R-010 CON031 Eddy Current Probe System
  • Emerson A6824 9199-00090 Operator Workstation
  • Emerson A6410 9199-00005 Operator Workstation
  • Emerson A6110 9199-00001 Operator Workstation
  • Emerson 9199-00002 A6120 Operator Workstation
  • Emerson KJ3002X1-BF1 12P1732X042 FIELDVUE DVC6200
  • Emerson 5X00500G01 Ovation Analog Output Module
  • Emerson VE4001S2T2B4 DeltaV Controller Module
  • Emerson 5X00502G01 Ovation Analog Input Module
  • Emerson A6824R 9199-00098-13 Operator Workstation
  • EMERSON A6140 9199-00058 Dual Channel Monitor
  • EMERSON VE3007 KJ2005X1-BA1 DeltaV Controller
  • EMERSON DB1-1 Connection Termination Block
  • EMERSON PMC-IO-ADAPTER Mezzanine Interface Card
  • EMERSON L0115012 L0115032 Solenoid Valve Components
  • Emerson A6410 Large Operator Workstation
  • Emerson A6210 Operator Workstation
  • Emerson 1C31232G02 Ovation Controller Module
  • Emerson 5X00106G02 Ovation Power Supply Module
  • Emerson 5X00106G01 Ovation Power Supply Module
  • EMERSON PMC-IO-PROZESSOR High-Speed I/O Module
  • EMERSON PMC PROFINET Communication Module
  • EMERSON MVME7100-0171 VMEbus Single Board Computer
  • EMERSON SE3008 KJ2005X1-SQ1 DeltaV MQ Controller
  • EMERSON PR6423/002-041 Eddy Current Displacement Sensor
  • Emerson SE4006P2 Serial Interface Module
  • Emerson KJ2201X1-HA1 Analog Input Module
  • EMERSON CE4001S2T2B4 DeltaV I/O Interface Module
  • EMERSON CE4003S2B1 DeltaV Controller
  • EMERSON KJ2003X1-BA2 DeltaV I/O Carrier
  • Enterasys A4H124-24TX P0973JM 24-Port Fast Ethernet Switch Module
  • Enterasys A2H254-16 P0973BK 16-Port Fast Ethernet Switch Module
  • Enterasys A4H254-8F8T P0973JP Matrix E5 Switch Module
  • Enterasys SSA-T8028-0652 P0973LN SecureStack Gigabit Switch
  • Enterasys A2H124-24FX P0973BJ
  • Enterasys SSA-AC-PS-625W P0973LQ Power Supply
  • Enterasys A2H124-24FX-RH Fiber Fast Ethernet Switch
  • Enterasys A2H254-16-RH Fast Ethernet Switch
  • Enterasys C2G170-24 P0973BL Stackable Gigabit Switch
  • Enterasys STK-RPS-150PS P0973BP Redundant Power Supply
  • ENTERASYS A4H124-24FX P0973JN SecureStack A4 Fiber Switch
  • ENTERASYS A4H124-24TX SecureStack A4 Ethernet Switch
  • ENTERASYS A2H124-24FX SecureStack A2 Fiber Switch
  • ENTERASYS A2H254-16 SecureStack A2 Managed Switch
  • ENTERASYS A4H254-8F8T SecureStack A4 Managed Switch
  • Enterasys C2RPS-CHAS2 Redundant Power System Chassis
  • Enterasys A2H124-24 Managed Ethernet Switch
  • EPRO PR6423/003-030-CN Hazardous Area Sensor
  • EPRO PR6424/012-000 Eddy Current Displacement Probe
  • EPRO PR6424/013-130 + CON021 Eddy Current Sensor System
  • EPRO PR6424/014-040 11mm Eddy Current Probe
  • EPRO PR6423/001-000 Eddy Current Sensor Probe
  • EPRO PR6423/010-000-CN Eddy Current Probe
  • EPRO MMS6823 9100-00001-05 Output Module
  • EPRO CON011 9200-00001N Signal Converter
  • EPRO MMS6120 Dual Channel Speed Monitor 9100-00002-10
  • EPRO MMS6120 Dual Channel Overspeed Protection Monitor 9100-00002C-08
  • EPRO PR6423 and PR6424 Eddy Current Displacement Probes
  • EPRO PR9268/300-000 Seismic Velocity Sensor
  • EPRO MMS3120/022-000 Dual Channel Vibration Monitor 9100-03047-01
  • EPRO MMS6823R 9100-00001-06 Dual Channel Module
  • EPRO PR6423/10R-030-CN Displacement Sensor
  • EPRO PR6423 Eddy Current Displacement Sensor
  • EPRO PR6423/002-030-CN+CON021 Eddy Current Sensor
  • EPRO PR9376/20 Contactless Speed Sensor
  • EPRO PR6423/002-001-CN Eddy Current Probe
  • EPRO RSM020 Relay Output Module
  • EPRO SDM010 Signal Distribution Module
  • EPRO PR6423/010-010-CN Eddy Current Sensor
  • FANUC A81L-0001-0165 Servo Motor Cable
  • FANUC A05B-2452-C900 Teach Pendant Cable
  • FANUC A90L-0001-0422#50 Cooling Fan 9WF0624H7D05
  • FANUC A860-0326-T103 Alpha iA64 Pulse Coder
  • FANUC A860-0315-T101 Alpha i Pulse Coder
  • FANUC A860-0302-T001 Alpha Series Pulse Coder
  • FANUC A230-0604-X003 Operator Panel
  • FANUC A20B-8200-0927 I/O Link Module
  • FANUC A20B-2902-0290/08C Communication PCB
  • FANUC A20B-2901-0763/02A I/O PCB Module
  • FANUC A20B-2901-066 Main PCB Board
  • FANUC A20B-2002-0040/07DR Servo Control PCB
  • FANUC A16B-2203-0073/02A Power Supply PCB
  • FANUC A06B-6114-H106 Alpha i Servo Amplifier
  • FANUC A06B-6089-H104 Alpha Servo Amplifier SVM1-80
  • FANUC A06B-6079-H208 Alpha Servo Amplifier Module
  • FANUC A06B-6079-H106 Servo Amplifier
  • FANUC A06B-6077-H106 Servo Amplifier
  • FANUC A06B-0116-B203#0100 Servo Motor
  • HIMA F3DIO20/802 Digital I/O Module 982200442
  • HIMA 80105 Power Supply Module 984080105
  • HIMA X-DO2401 Digital Output Module 985210203
  • HIMA X-DI3201 Digital Input Module 985210201
  • HIMA F-PWR02 Power Supply Module for F-Series
  • HIMA K1412B / H51q-HRS Safety Controller 996141261 / 997205233
  • HIMA K7214 Power Supply Module 996721402
  • HIMA TM202-A00-B00-C00-D00-E00-G00 Analog Termination
  • HIMA TM521 Digital Input Termination Module
  • HIMA TM591-B00-G00 Termination Module HIMax System
  • HIMA KFD2-STC4-Ex1 SMART Transmitter Power Supply
  • HIMA KFD2-VR4-Ex1.26 Voltage Repeater Isolated Barrier
  • HIMA SB3073-EX Intrinsically Safe Barrier Module
  • HIMA H6200A Terminal Module for Safety I/O
  • HIMA Z7130 Power Supply Distribution Module
  • HIMA F8652E 984865264 Central Module HIQuad H51q
  • HIMA F8627 984862702 Communication Module HIQuad System
  • HIMA H41q-HS High-Speed Safety Controller B4237-1 997104237
  • HIMA F8652X Central Processing Unit 984865265
  • HIMA H4135 Safety Logic Solver 992413502
  • HIMA H51q-H High-Integrity Safety Controller B5233-2 997235233
  • HIMA F6217 Safety Controller 984621702
  • HIMA F3330 984333002 Digital Output Module
  • HIMA F7553 984755302 Communication Module
  • HIMA F7131 Power Supply Module
  • HIMA X-DO1201 985210204 Digital Output Module
  • HIMA H51q-HRS B5233-2 Safety Controller Module
  • HIMA F3231 16-Channel Digital Input Module
  • HIMA K9203A (996920360) Safety Relay Module
  • HIMA H51q-HS B5233-1 Safety Control System
  • HIMA F7131 Power Supply Monitoring Module
  • HIMA F8620/11 Central Module for HIQuad Systems
  • HIMA X-FAN 18 03 Redundant Fan Module for Safety Systems
  • HITACHI LYD000A Digital Input Module 8-Channel
  • HITACHI PS6000 Heavy-Duty Power Supply 24VDC 10A