Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Complete Guide to On site Maintenance and Troubleshooting of Honeywell TN3801 Electro Motive Liquid Level

F: | Au:FANS | DA:2026-05-21 | 26 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Complete Guide to On site Maintenance and Troubleshooting of Honeywell TN3801 Electro Motive Liquid Level Measurement Cabinet

In ship operation, the accurate measurement of liquid levels such as service tanks, ballast tanks, and draft depth is directly related to ship stability, cargo loading and unloading safety, and fuel management. Traditional mechanical or purely electronic level gauges often face problems such as scaling, corrosion, and condensate interference in harsh marine environments. The TN3801 Electro pneumatic Level Measuring Cabinet launched by Honeywell Marine adopts the principle of bubble measurement, combining pneumatic sampling with microprocessor data processing to achieve independent and highly reliable liquid level monitoring with up to 24 channels. This product has been certified by major international classification societies and is suitable for installation in safe areas above the main deck of various types of ships.

This article is aimed at ship electrical engineers, engineers, and maintenance personnel. It systematically introduces the working principle, installation and commissioning points, daily maintenance methods of TN3801, and focuses on summarizing common on-site fault phenomena and standardized troubleshooting processes to help users quickly locate gas, circuit, or communication problems and ensure the continuous and reliable operation of ship liquid level monitoring systems.


System Overview and Core Features

1.1 Positioning and Application Scenarios of TN3801

TN3801 is a modular and compact electric liquid level measurement cabinet designed specifically for ship liquid level monitoring. Its typical applications include:

Service cabin: daily fuel, oil, fresh water, seawater and other containers

Ballast tank: ship ballast water management to ensure navigation stability

Draft monitoring: bow, stern, and starboard draft depth of the ship

Each TN3801 cabinet can accommodate 8 to 24 independent pneumatic measurement channels, and the air paths between each channel are completely independent and do not interfere with each other. Each channel is equipped with an automatic non return valve, which automatically closes when the gas supply pressure is below 1 bar, preventing the liquid in the cabin from flowing back into the transmitter through the bubble pipeline, thereby protecting electronic and pneumatic components. This design is extremely critical in on-site maintenance, avoiding liquid contamination and damage caused by gas source interruption.

1.2 Main technical specifications (based on official data)

Parameter indicators

Number of channels 8~24 (configurable)

Measurement accuracy ± 0.3% FS @ 20 ℃

Communication interface 2-channel redundant RS485/422, Modbus protocol

Supply pressure 6/10 bar (recommended)

Gas consumption 15 L/h per channel

Working temperature+5 ℃ to+70 ℃

Storage temperature+5 ℃ to+70 ℃

Pneumatic interface ¼ GAS internal thread

Power supply 230/115 VAC

Electricity consumption 0.5 VA per channel

Protection level IP44

Installation environment safety zone (within the protective area above the main deck)

1.3 Key optional functions

Integrated air filtration unit: ensuring that the gas entering the measurement pipeline is dry and clean

Pressure chamber connector (for measuring pressurized tanks)

Display unit: capable of locally displaying the liquid level values of each channel

8 × 4-20 mA analog input: can be connected to third-party sensors

Self diagnosis and 4-20 mA output: Each channel can output analog liquid level signals to external systems


Detailed explanation of working principle

TN3801 adopts the classic bubble liquid level measurement principle, which is especially applicable to the tank of ships with foam, corrosive liquid or high viscosity medium.

2.1 Bubble measurement process

Each measurement channel works independently:

Air source input: The main air source (6 or 10 bar) passes through the filtering and pressure regulating components inside the cabinet, and after stabilizing, it is supplied to the automatic flow regulators of each channel.

Constant flow bubbles: The flow regulator of each channel stabilizes the airflow at approximately 15 L/h, and continuously releases bubbles into the liquid through a bubbling line immersed in the bottom of the cabinet.

Back pressure measurement: The gas pressure inside the bubble tube is balanced with the static pressure of the liquid column at the nozzle. The back pressure is converted into an electrical signal by a pneumatic sensor.

Liquid level calculation: The microcontroller compensates for the current liquid level height based on back pressure, liquid density, and atmospheric pressure, with an accuracy of ± 0.3% FS.

2.2 Key role of non return valve

At the air outlet of each channel, a normally open automatic non return valve is installed. The action logic is as follows:

Normal gas supply (≥ 1 bar): The valve remains open and bubbles are continuously generated.

Air source interruption or sudden pressure drop (<1 bar): The valve instantly closes, cutting off the passage between the liquid in the cabin and the measuring pipeline.

This design is extremely practical on site: when the ship's air compressor fails or the air supply pipeline leaks, even if the liquid level is higher than the bubble tube mouth, the liquid will not be sucked back into the TN3801 cabinet, thus avoiding contamination and damage to sensors, pipelines, and control boards. After the fault is restored, the valve automatically opens again, and the system can resume normal measurement without manual exhaust.

2.3 Data Processing and Communication

TN3801 is equipped with a microcontroller that is responsible for:

Collect back pressure analog signals from each channel and perform AD conversion

Perform linearization, temperature compensation, and density correction

Manage two redundant RS485/RS422 communication ports using standard Modbus RTU protocol

Redundant communication design means that when the main communication line fails, the system automatically switches to the backup line without manual intervention. This is crucial for ship automation systems such as IAS and AMS - liquid level data can be continuously uploaded to the bridge or engine room monitoring system without being lost due to a single point of failure.


Key points for installation and debugging

3.1 Mechanical installation requirements

Installation location: above the main deck, in a safe and protected area. Avoid direct exposure to ocean waves, high temperature heat sources, or locations with severe vibrations.

Protection level: IP44, splash proof, but not recommended for long-term exposure to high-pressure water jets.

Pneumatic interface: The pneumatic interface of each channel is a ¼ GAS internal thread. It is recommended to use stainless steel or reinforced nylon pipes to connect to the cabin bubble pipes.

Air source quality: An oil-water separator and a 5 μ m level filter should be installed to prevent oil mist or moisture from entering the flow regulator and causing blockage. TN3801 can be optionally equipped with an integrated air filtration unit, strongly recommended for selection.

3.2 Electrical Wiring

Power supply: 230 VAC or 115 VAC, pay attention to terminal labeling. Extremely low power consumption (0.5 VA/channel), the whole machine usually does not exceed 15 VA.

Communication cable: Two RS485/422 channels use shielded twisted pair cables, it is recommended to use AWG 22 or thicker, and the shielding layer should be grounded at one end. The maximum transmission distance can reach 1200 meters (baud rate ≤ 9600).

Analog output (if configured): 4-20 mA active or passive output, maximum load resistance of 500 Ω.

3.3 Debugging steps

Airtightness test: Without connecting the air source, seal the air outlet of each channel with a plug, introduce 6 bar compressed air, and check for leaks in the pipeline joints.

Channel self-test: Activate each channel one by one through the built-in diagnostic mode (see technical manual MT5015 for details), and observe whether the output of the back pressure sensor is linear.

Zero and full calibration: Use a reference chamber or simulated pressure source with known liquid level height to perform two-point calibration on each channel. The official recommendation is to calibrate at 20 ℃ to achieve an accuracy of ± 0.3% FS.

Communication testing: Read the registers of each channel through a Modbus master station (such as PLC or PC debugging software) to verify the address, baud rate, and parity settings.

Common fault phenomena and troubleshooting

Based on years of on-site experience, the faults of TN3801 mainly focus on four aspects: gas source problems, pipeline blockage/leakage, communication interruption, and channel accuracy drift. The following provides a standardized troubleshooting process based on the classification of fault phenomena.

4.1 Fault phenomenon 1: Abnormal low or no change in liquid level reading of one or all channels

Possible reasons:

Air source interruption or insufficient pressure (<1 bar)

The bubble tube in this channel is blocked (due to sludge and crystals in the cabin)

Automatic non return valve mistakenly closes (although rare, if there are foreign objects inside the air path, it can cause the valve core to get stuck)

Back pressure sensor damaged

Troubleshooting steps:

Observe the gas supply pressure gauge on the TN3801 panel (if configured) and confirm if the input pressure is between 6-10 bar. If it is below 1 bar, check the ship's main air system or pressure reducing valve.

Remove the bubble tube connector of the faulty channel, briefly ventilate (3-5 seconds), and feel with your hand whether there is airflow at the tube mouth. If there is no airflow, it indicates that the internal air path is blocked or the flow regulator is malfunctioning.

Alternative method: Connect the gas path of this channel to another known normal cabinet. If the reading is restored, the original bubble tube will be blocked; If the issue persists, it is within TN3801.

Check the automatic non return valve: Use a small screwdriver to lightly press the valve core. If it can rebound normally and open after ventilation, then the valve is normal. Otherwise, the channel module needs to be replaced.

Temporary emergency measures: If measurement is urgently needed, the gas path of the adjacent normal channel can be temporarily switched to the faulty cabinet (note that the original channel must be closed), but it needs to be restored after maintenance.

4.2 Fault phenomenon 2: All channel readings fluctuate or jump simultaneously

Possible reasons:

Unstable gas source pressure (such as significant pressure fluctuations caused by the start and stop of an air compressor)

Communication interference (poor grounding of RS485 or parallel wiring with power cables)

Power supply voltage fluctuation (unstable ship power grid)

Troubleshooting steps:

Install a 10 L gas storage tank and pressure regulator valve at the inlet of the gas source, and observe whether the fluctuation disappears.

Use an oscilloscope or multimeter to measure whether there is a common mode voltage (ideal value<2 V) between the communication line and ground. If exceeded, check if the shielding layer is grounded at both ends (should be changed to single ended grounding).

The AC input voltage of TN3801 should be measured within ± 10% of the rated value. If there is a large fluctuation, an online UPS can be added.

4.3 Fault phenomenon three: The reading of a single channel is significantly high (exceeding the actual liquid level)

Possible reasons:

The bubble tube is damaged or detached, causing gas to leak from the middle and increasing back pressure.

Density parameter setting error (the liquid density value stored in the microcontroller is too high).

Zero drift of back pressure sensor.

Troubleshooting steps:

Turn off the gas source of the channel, open the inspection port on the top of the cabinet, remove the bubble tube, and visually inspect for cracks, bends, or detachment.

Use a standard pressure source (such as a piston pressure gauge) to directly input simulated pressure to the back pressure sensor of the channel, and compare the displayed liquid level value. If the deviation exceeds 0.5%, perform the calibration procedure (see maintenance manual MM5015).

Check if the liquid density value in the TN3801 configuration parameters matches the current cabin medium (e.g. fuel density 0.86 kg/L, seawater 1.025 kg/L).

4.4 Fault phenomenon four: Communication interruption (Modbus master station reading timeout)

Phenomenon: The upper computer cannot read any channel data or returns an error code when reading.

Troubleshooting steps:

Physical layer inspection

Confirm that the communication cable is connected to the correct RS485/422 terminal (usually A, B, GND).

Check the terminal resistance: A 120 Ω resistor should be connected at both ends of the bus (TN3801 and the main station). If TN3801 is an end device, has the terminal resistor been enabled internally (refer to manual MT5015 jumper settings).

Measure the resistance between A and B, which should be around 60 Ω (two 120 Ω parallel connections).

Protocol parameter matching

Use the PC serial port debugging assistant to set the same baud rate (default 9600), data bits (8), stop bit (1), and no checksum as TN3801. Send Modbus read hold register command (function code 03) and check if there is a correct frame response.

Common error: The main station address does not match the station address set by TN3801. TN3801 corresponds to a Modbus address for each channel, but typically the device itself has a global address. Refer to the manual for confirmation.

Redundant port switching test

TN3801 has two redundant RS485 ports (usually labeled as COM1 and COM2). If COM1 does not respond, switch the main station cable to COM2 and confirm that the main station program has also been switched accordingly. If COM2 is working properly, it indicates that COM1 hardware is damaged. COM2 can be temporarily used and repairs can be arranged.

4.5 Fault phenomenon five: The liquid level reading is normal, but there is no signal output from 4-20 mA

Possible reasons:

Analog output not activated or channel configuration error

External load resistance is too high or short circuited

Open circuit output circuit

troubleshoot

Measure the AO+and AO - terminals of TN3801 directly with a multimeter in mA mode, which should normally be between 4-20 mA as the liquid level changes. If there is no current, check if the internal jumper is set to "active output" mode.

If there is current but the external device displays zero, please check the input impedance of the external receiving device (should be ≤ 500 Ω).


Maintenance and Calibration Plan

To ensure the long-term stable operation of TN3801, it is recommended to perform maintenance tasks according to the following cycle:

5.1 Monthly Inspection

Air path filter: Observe the water cup of the integrated filtration unit, and if the accumulated water exceeds 1/3, discharge it in a timely manner.

Gas supply pressure: Record whether the inlet pressure is stable at 6-10 bar.

Alarm log: Read the system self-test alarm through the display unit or Modbus. If there is a record of "Low Air Pressure" or "Channel Failure", handle it in a timely manner.

5.2 Quarterly maintenance

Accuracy verification: Select 1-2 representative cabinets and compare the readings of TN3801 using a manual ruler (such as a depth gauge). If the deviation exceeds ± 0.5% FS, perform online two-point calibration.

Bubble tube inspection: For tanks with scaling risks (such as sewage tanks and crude oil tanks), check whether the bubble tube opening is blocked and remove sediment.

Tightening of wiring terminals: In vibration environments, electrical terminals may become loose. Use a torque screwdriver to tighten them again.

5.3 Annual in-depth maintenance

Sensor calibration: Use a high-precision pressure source (0.05 level) to perform full-scale linearity calibration on all channel back pressure sensors.

Cleaning of flow regulator: Remove the flow regulator from each channel and use anhydrous alcohol ultrasonic cleaning to remove oil sludge.

Communication redundancy test: Manually disconnect COM1, confirm that the system automatically switches to COM2 and the data is continuous without interruption.

Backup channel test: If the cabinet is not fully equipped, a backup bubble tube can be pre installed using the backup channel to quickly replace the faulty channel.

5.4 Recommended spare parts

Automatic non return valve component (1 piece for every 8 channels)

Flow regulator (1 piece for every 16 channels)

Back pressure sensor (1 piece per cabinet)

Air filter cartridge (matching filter unit)


Key points of communication integration and software configuration

As a slave station of the ship automation system, TN3801 needs to be correctly integrated with the main station (such as PLC, HMI, AMS). The following are details that are easily overlooked in actual projects:

6.1 Modbus Register Mapping

By default, TN3801 stores the liquid level value for each channel as a 16 bit integer, measured in 0.1% FS or centimeters (depending on the configuration). For example:

Register Address 40001: Channel 1 Liquid Level (Floating Point or Integer)

Register address 40002: Channel 2 liquid level, and so on

Please refer to Chapter 4 of Technical Manual MT5015 for a detailed address table.

6.2 Baud rate and communication parameter settings

It can be set through the TN3801 internal DIP switch or display unit menu:

Optional baud rates: 2400, 4800, 9600, 19200, 38400

Data format: 8N1 (default), 8E1, 8O1

Station address: 1-247

Attention: After modifying communication parameters, it is necessary to power on again or perform a soft reset to take effect.

6.3 Redundant Port Wiring Example

Two RS485 ports can be connected to two different main stations (such as the main PLC and backup PLC) using a "daisy chain", or one to the local display and the other to the upper computer. When wiring:

Port A: T+/R+connected to main station A (+)

Port B: T -/R-connected to main station B (-)

The common terminal (GND) must be connected to the main station signal ground to avoid common mode voltage damaging the interface.


Selection and replacement upgrade suggestions

Upgrading to TN3801 can bring significant benefits to ships that are still using early electrical level measurement systems, such as single channel pneumatic transmitters and old models without Modbus communication

Reduce the risk of leakage by replacing multiple pneumatic pipelines with a single multi-core cable.

Digital integration: directly connected to ship Ethernet or fieldbus without the need for additional signal converters.

Redundant communication: Improve the availability of monitoring systems.

Low maintenance: Automatic flow regulation and self diagnostic functions significantly reduce manual inspections.

Attention should be paid when replacing:

The original bubble tube can continue to be used by simply connecting the gas outlet of TN3801 to the existing pipeline.

The power supply voltage must match: TN3801 supports 115/230 VAC switching, please confirm when ordering.

If the original system uses 4-20 mA analog signals to the alarm panel, TN3801's analog output module (4-20 mA per channel) can be optionally equipped to achieve seamless replacement.


Case study: No reading of the whole machine caused by gas source pressure loss

Background: A 100000 ton oil tanker reported that the liquid level displayed in all channels of TN3801 was 0 (the lowest value), and the ship was in a ballast state but the actual ballast tank was full.

Troubleshooting process:

Step 1: Check the air supply pressure gauge of the cabinet, the pointer is at 0 bar. Inquired about the engine room and found that the main air compressor of the ship had tripped and the backup air compressor had not automatically started.

Step 2: Restore power to the air compressor, wait for the air pressure to rise to 7 bar, and gradually restore the TN3801 liquid level reading to normal within 30 seconds.

Step 3: Check the non return valve status, all valves are open normally and there is no backflow phenomenon.

Conclusion: After the gas source is interrupted, the non return valve closes to protect the internal sensor. After the gas supply is restored, the system automatically returns to normal. Suggest adding an independent small gas storage tank (20 L) to TN3801 to cope with short-term gas source fluctuations.

  • Fanuc A20B-8100-0137 PCB I O Board
  • D0-06DD2-D PLC Module DL06 PLC
  • Kepco BOP100-4M Power Supply Amplifier
  • Allen-Bradley 1785-L60B PLC-5 60 Module
  • Siemens 7MH4900-3AA01 Weighing Module
  • Pilz 773100 PNOZ m1p Safety Controller
  • Omron NS12-TS00B-V2 Graphic Operation Panel
  • EC20-4040BTA Programmable Controller PLC
  • Fanuc A16B-1212-0100-01 Power Unit CNC
  • Siemens 6ES7151-3BB23-0AB0 ET200S Interface Module
  • ATTO Control DU-01 PLC Display System
  • Keyence KV-RC8BXR Programmable Controller
  • Lenze GST04-1GVCK-063C22 Servo Motor
  • CKD AX9000GH AX9210H Control Unit
  • ABB PG6310 DC Trigger Control Board
  • Cutler Hammer 10316H621C Type L Device
  • TAIYO AA-277 EM CY TRIP PCB Card
  • Schneider BMXCPS2010 PLC Power Supply
  • Schneider TSXMRPC007M PLC PCMCIA Card
  • 101182218 Safety Stop Relay SSW301HV-230V
  • Cutler Hammer 9-1875-3 Size 6 Contactor 480V
  • Nidec UNI3401 Drive Module Control Board
  • Delta AS06XA-A PLC Module Analog Mixed IO
  • Lenze EPL 10201 13408978 Servo Drive 24V DC
  • Sigmatek CCP612-K PLC Module DI DO Module
  • Schneider ATS48D38Q Soft Starter Altistart 48
  • Fanuc A20B-3300-0472 Main CPU Board Series 30i
  • Mitsubishi A171SCPU-S3 Servo CPU Module PLC
  • ABB 1SFL597001R7011 700A 100-250V Soft Starter
  • Yaskawa JANCD-YCP21-E DX200 CPU Control Board
  • Schneider NS630N Circuit Breaker 3P 630A
  • Honeywell DPCB21010002 Rack Slot PCB
  • Mitsubishi RJ71EIP91 PLC Module
  • Siemens 3VL5763-1DC36-0AA0 Circuit Breaker
  • Siemens 6GK7542-1AX00-0XE0 Communication Module
  • Siemens 6SL3130-6AE15-0AB1 Smart Line Module
  • HMS Anybus AB7646-F Gateway
  • Honeywell 621-0020 Analog Input Module
  • Siemens 6ES7212-1HF40-0XB0 PLC Controller
  • MAK 1.00.7-36.21.00-40 PCB Module
  • ABB 3BSE006503R1 PFSA140 Power Supply
  • SAACKE F-GDSA 143303 Burner Controller
  • ABB PFSC230 25m Cable Set
  • GE HYDRAN 201Ci-1 Controller
  • ABB NINT-42C main circuit interface board
  • B&R 3AT660 6 Thermocouple Input Module
  • Honeywell EC7850A1080 Programmable Logic Controller
  • Mitsubishi A2ACPU21 CPU Module MELSEC A Series
  • Mitsubishi R60ADH3FR Analog Input Module iQ R
  • ELMO WLWHIA20 100 Servo Drive Whistle Series
  • Omron CJ1W-MAD42 Analog I O Module PLC
  • Siemens A5E03894525 SINAMICS S120 Power Module
  • Omron K3HB-HTA-DRT1 Temperature Panel Meter
  • Keyence KV-8000SO Programmable Controller CPU Unit
  • Harris 8800-00002-02 PLC Power Control Center
  • Siemens 3TY7480-0A Auxiliary Contact Block
  • Omron 3G3MX2-AB022-ZV1 Inverter
  • ABB ACS380-040S-12A6-4 VFD
  • ATTO controlSYS ATTO-CPU44 PLC System
  • Allen‑Bradley 5069-L330ERMS3 CompactLogix PLC
  • Emerson VE4003S2B2 Terminal Module
  • SND ATS48D38Q Soft Starter
  • Omron CJ1W-MCH71 Motion Control Module
  • Siemens 3TK28060BB4 24VDC Contactor
  • Mitsubishi FR-D740-160-NA Inverter
  • PILZ 312070 PSSuniversal PLC Head Module
  • Omron CJ2M-CPU35 SYSMAC CJ Series PLC CPU
  • KISTLER 4734AWDY2X400S1 Force Displacement Indicator
  • Beckhoff CX2100-0904 Power Supply UPS Module
  • Siemens 6ES7 194-4AD00-0AA0 ET 200PRO IM 154-1 DP Module
  • Siemens 6FC5110-0DB02-0AA2 SINUMERIK MMC CPU Module
  • EDWAR 3-SDDC2CF Dual Circuit Card Control Module
  • ABB CI856K01 S100 I O Communication Module
  • Omron C200HW-PCS01-V2 PC Card Unit Module
  • Pilz 777150 PZE X5P 24VDC Safety Relay
  • Siemens 6SE6430-2AD31-1CA0 Inverter
  • Pilz 774340 Safety Relay
  • Kübler 8.5868.1231.3112 Encoder
  • Stromag 51 NE 451 DV MS Switch
  • Mitsubishi Q20UDEHCPU CPU Unit
  • CON-MAL P86402251-00 PCB Board
  • Panasonic MDMA102A1D Servo Motor
  • Omron OS32C-SN-4M Safety Scanner
  • Mitsubishi LD-30FTA Tension Controller
  • Siemens 7SP8014 Genop 23 S Relay
  • GE 151X1235DB15SA01 SPEEDTRONIC Mark VI High Performance Turbine Control Module
  • GE DS3800HIOC High-Level Input Output Board
  • GE DS3800NHVG High-Voltage Gate Driver Board
  • GE DS3800NB1A Power Supply Regulator Board
  • GE DS3815PAHB1A1A Processor Interface Board
  • Allen-Bradley 100-D300EA11 IEC Contactor 300A
  • Omron BY50S 500VA 300W Uninterruptible Power Supply
  • Mitsubishi NF630-CW 3P 600A Molded Case Circuit Breaker
  • CLA-2 4L PLC Control Electric Lubricating Oil Pump
  • Pilz 6Z000002 PSEN enc sincos 4096 hs Encoder
  • Siemens 6ES7317-2FK14-0AB0 CPU 317F-2PN/DP
  • Fuji NP1AYH8V-MR Analog Output Module MICREX-SX
  • Kistler DMF-P A300 NCF 4734AWDY2X400S1 Force Displacement Monitor
  • ABB Pluto S20 v2 CFS Safety PLC
  • Parker IQAN-XS2 Expansion Controller Module
  • ABB CI867AK01 PLC Module
  • FANUC A20B-2002-0520 Main Board
  • Mitsubishi A6BR10 Repeater Module
  • Siemens 3TY6480-0A Contact Kit
  • Servax CDD34.008 Servo Drive
  • Renesas R5F2134CXJFP Microcontroller
  • Siemens 6SL3210-1SE31-0AA0 Power Module
  • Mitsubishi LE-40MTA-E Tension Controller
  • B&R 4PP035.0300-01 Operation Panel
  • HRTL 96B M666.01S-S12 Inductive Proximity Sensor
  • Mitsubishi GT1455HS-QTBDE GOT1000 Touch Screen
  • Braids PLC-24/30/E2UK 25m PLC Connection Cable
  • Omron NX-PD7001 NX Series Power Supply Unit
  • Pro-face FP3900-T41-U PFXFP3900TA Operating Panel
  • Siemens 6GK5204-2BB10-2AA3 Industrial Ethernet Switch
  • Mitsubishi GT2310-VTBA GT2310-VTBD Graphic Operation Panel
  • PILZ 774400 PNOZ 24VDC 2NO 2NC Safety Relay
  • Siemens 6ES7315-2EH14-0AB0 CPU 315-2 PN/DP
  • ABB PLUTO B42 AS-i Safety Relay 2TLA020070R1400
  • Applied Materials 0010-12123 PLC Controller
  • Pilz 774595 PZE X5 Safety Relay
  • Siemens 6GA2 490-0A AVR
  • Keyence KV-10T Micro PLC
  • Siemens 6ES7331-7PF01-0AB0 Analog Input
  • Siemens 6SN1145-1BA02-0CA1 PLC
  • FANUC A16B-3200-0521 Main Board
  • Siemens 6SL3120-2TE21-0AD0 Motor Module
  • Pilz 828010 S1IM Safety Relay