Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Complete Guide to On site Maintenance and Troubleshooting of Honeywell TN3801 Electro Motive Liquid Level

F: | Au:FANS | DA:2026-05-21 | 482 Br: | 🔊 点击朗读正文 ❚❚ ▶ | Share:

Complete Guide to On site Maintenance and Troubleshooting of Honeywell TN3801 Electro Motive Liquid Level Measurement Cabinet

In ship operation, the accurate measurement of liquid levels such as service tanks, ballast tanks, and draft depth is directly related to ship stability, cargo loading and unloading safety, and fuel management. Traditional mechanical or purely electronic level gauges often face problems such as scaling, corrosion, and condensate interference in harsh marine environments. The TN3801 Electro pneumatic Level Measuring Cabinet launched by Honeywell Marine adopts the principle of bubble measurement, combining pneumatic sampling with microprocessor data processing to achieve independent and highly reliable liquid level monitoring with up to 24 channels. This product has been certified by major international classification societies and is suitable for installation in safe areas above the main deck of various types of ships.

This article is aimed at ship electrical engineers, engineers, and maintenance personnel. It systematically introduces the working principle, installation and commissioning points, daily maintenance methods of TN3801, and focuses on summarizing common on-site fault phenomena and standardized troubleshooting processes to help users quickly locate gas, circuit, or communication problems and ensure the continuous and reliable operation of ship liquid level monitoring systems.


System Overview and Core Features

1.1 Positioning and Application Scenarios of TN3801

TN3801 is a modular and compact electric liquid level measurement cabinet designed specifically for ship liquid level monitoring. Its typical applications include:

Service cabin: daily fuel, oil, fresh water, seawater and other containers

Ballast tank: ship ballast water management to ensure navigation stability

Draft monitoring: bow, stern, and starboard draft depth of the ship

Each TN3801 cabinet can accommodate 8 to 24 independent pneumatic measurement channels, and the air paths between each channel are completely independent and do not interfere with each other. Each channel is equipped with an automatic non return valve, which automatically closes when the gas supply pressure is below 1 bar, preventing the liquid in the cabin from flowing back into the transmitter through the bubble pipeline, thereby protecting electronic and pneumatic components. This design is extremely critical in on-site maintenance, avoiding liquid contamination and damage caused by gas source interruption.

1.2 Main technical specifications (based on official data)

Parameter indicators

Number of channels 8~24 (configurable)

Measurement accuracy ± 0.3% FS @ 20 ℃

Communication interface 2-channel redundant RS485/422, Modbus protocol

Supply pressure 6/10 bar (recommended)

Gas consumption 15 L/h per channel

Working temperature+5 ℃ to+70 ℃

Storage temperature+5 ℃ to+70 ℃

Pneumatic interface ¼ GAS internal thread

Power supply 230/115 VAC

Electricity consumption 0.5 VA per channel

Protection level IP44

Installation environment safety zone (within the protective area above the main deck)

1.3 Key optional functions

Integrated air filtration unit: ensuring that the gas entering the measurement pipeline is dry and clean

Pressure chamber connector (for measuring pressurized tanks)

Display unit: capable of locally displaying the liquid level values of each channel

8 × 4-20 mA analog input: can be connected to third-party sensors

Self diagnosis and 4-20 mA output: Each channel can output analog liquid level signals to external systems


Detailed explanation of working principle

TN3801 adopts the classic bubble liquid level measurement principle, which is especially applicable to the tank of ships with foam, corrosive liquid or high viscosity medium.

2.1 Bubble measurement process

Each measurement channel works independently:

Air source input: The main air source (6 or 10 bar) passes through the filtering and pressure regulating components inside the cabinet, and after stabilizing, it is supplied to the automatic flow regulators of each channel.

Constant flow bubbles: The flow regulator of each channel stabilizes the airflow at approximately 15 L/h, and continuously releases bubbles into the liquid through a bubbling line immersed in the bottom of the cabinet.

Back pressure measurement: The gas pressure inside the bubble tube is balanced with the static pressure of the liquid column at the nozzle. The back pressure is converted into an electrical signal by a pneumatic sensor.

Liquid level calculation: The microcontroller compensates for the current liquid level height based on back pressure, liquid density, and atmospheric pressure, with an accuracy of ± 0.3% FS.

2.2 Key role of non return valve

At the air outlet of each channel, a normally open automatic non return valve is installed. The action logic is as follows:

Normal gas supply (≥ 1 bar): The valve remains open and bubbles are continuously generated.

Air source interruption or sudden pressure drop (<1 bar): The valve instantly closes, cutting off the passage between the liquid in the cabin and the measuring pipeline.

This design is extremely practical on site: when the ship's air compressor fails or the air supply pipeline leaks, even if the liquid level is higher than the bubble tube mouth, the liquid will not be sucked back into the TN3801 cabinet, thus avoiding contamination and damage to sensors, pipelines, and control boards. After the fault is restored, the valve automatically opens again, and the system can resume normal measurement without manual exhaust.

2.3 Data Processing and Communication

TN3801 is equipped with a microcontroller that is responsible for:

Collect back pressure analog signals from each channel and perform AD conversion

Perform linearization, temperature compensation, and density correction

Manage two redundant RS485/RS422 communication ports using standard Modbus RTU protocol

Redundant communication design means that when the main communication line fails, the system automatically switches to the backup line without manual intervention. This is crucial for ship automation systems such as IAS and AMS - liquid level data can be continuously uploaded to the bridge or engine room monitoring system without being lost due to a single point of failure.


Key points for installation and debugging

3.1 Mechanical installation requirements

Installation location: above the main deck, in a safe and protected area. Avoid direct exposure to ocean waves, high temperature heat sources, or locations with severe vibrations.

Protection level: IP44, splash proof, but not recommended for long-term exposure to high-pressure water jets.

Pneumatic interface: The pneumatic interface of each channel is a ¼ GAS internal thread. It is recommended to use stainless steel or reinforced nylon pipes to connect to the cabin bubble pipes.

Air source quality: An oil-water separator and a 5 μ m level filter should be installed to prevent oil mist or moisture from entering the flow regulator and causing blockage. TN3801 can be optionally equipped with an integrated air filtration unit, strongly recommended for selection.

3.2 Electrical Wiring

Power supply: 230 VAC or 115 VAC, pay attention to terminal labeling. Extremely low power consumption (0.5 VA/channel), the whole machine usually does not exceed 15 VA.

Communication cable: Two RS485/422 channels use shielded twisted pair cables, it is recommended to use AWG 22 or thicker, and the shielding layer should be grounded at one end. The maximum transmission distance can reach 1200 meters (baud rate ≤ 9600).

Analog output (if configured): 4-20 mA active or passive output, maximum load resistance of 500 Ω.

3.3 Debugging steps

Airtightness test: Without connecting the air source, seal the air outlet of each channel with a plug, introduce 6 bar compressed air, and check for leaks in the pipeline joints.

Channel self-test: Activate each channel one by one through the built-in diagnostic mode (see technical manual MT5015 for details), and observe whether the output of the back pressure sensor is linear.

Zero and full calibration: Use a reference chamber or simulated pressure source with known liquid level height to perform two-point calibration on each channel. The official recommendation is to calibrate at 20 ℃ to achieve an accuracy of ± 0.3% FS.

Communication testing: Read the registers of each channel through a Modbus master station (such as PLC or PC debugging software) to verify the address, baud rate, and parity settings.

Common fault phenomena and troubleshooting

Based on years of on-site experience, the faults of TN3801 mainly focus on four aspects: gas source problems, pipeline blockage/leakage, communication interruption, and channel accuracy drift. The following provides a standardized troubleshooting process based on the classification of fault phenomena.

4.1 Fault phenomenon 1: Abnormal low or no change in liquid level reading of one or all channels

Possible reasons:

Air source interruption or insufficient pressure (<1 bar)

The bubble tube in this channel is blocked (due to sludge and crystals in the cabin)

Automatic non return valve mistakenly closes (although rare, if there are foreign objects inside the air path, it can cause the valve core to get stuck)

Back pressure sensor damaged

Troubleshooting steps:

Observe the gas supply pressure gauge on the TN3801 panel (if configured) and confirm if the input pressure is between 6-10 bar. If it is below 1 bar, check the ship's main air system or pressure reducing valve.

Remove the bubble tube connector of the faulty channel, briefly ventilate (3-5 seconds), and feel with your hand whether there is airflow at the tube mouth. If there is no airflow, it indicates that the internal air path is blocked or the flow regulator is malfunctioning.

Alternative method: Connect the gas path of this channel to another known normal cabinet. If the reading is restored, the original bubble tube will be blocked; If the issue persists, it is within TN3801.

Check the automatic non return valve: Use a small screwdriver to lightly press the valve core. If it can rebound normally and open after ventilation, then the valve is normal. Otherwise, the channel module needs to be replaced.

Temporary emergency measures: If measurement is urgently needed, the gas path of the adjacent normal channel can be temporarily switched to the faulty cabinet (note that the original channel must be closed), but it needs to be restored after maintenance.

4.2 Fault phenomenon 2: All channel readings fluctuate or jump simultaneously

Possible reasons:

Unstable gas source pressure (such as significant pressure fluctuations caused by the start and stop of an air compressor)

Communication interference (poor grounding of RS485 or parallel wiring with power cables)

Power supply voltage fluctuation (unstable ship power grid)

Troubleshooting steps:

Install a 10 L gas storage tank and pressure regulator valve at the inlet of the gas source, and observe whether the fluctuation disappears.

Use an oscilloscope or multimeter to measure whether there is a common mode voltage (ideal value<2 V) between the communication line and ground. If exceeded, check if the shielding layer is grounded at both ends (should be changed to single ended grounding).

The AC input voltage of TN3801 should be measured within ± 10% of the rated value. If there is a large fluctuation, an online UPS can be added.

4.3 Fault phenomenon three: The reading of a single channel is significantly high (exceeding the actual liquid level)

Possible reasons:

The bubble tube is damaged or detached, causing gas to leak from the middle and increasing back pressure.

Density parameter setting error (the liquid density value stored in the microcontroller is too high).

Zero drift of back pressure sensor.

Troubleshooting steps:

Turn off the gas source of the channel, open the inspection port on the top of the cabinet, remove the bubble tube, and visually inspect for cracks, bends, or detachment.

Use a standard pressure source (such as a piston pressure gauge) to directly input simulated pressure to the back pressure sensor of the channel, and compare the displayed liquid level value. If the deviation exceeds 0.5%, perform the calibration procedure (see maintenance manual MM5015).

Check if the liquid density value in the TN3801 configuration parameters matches the current cabin medium (e.g. fuel density 0.86 kg/L, seawater 1.025 kg/L).

4.4 Fault phenomenon four: Communication interruption (Modbus master station reading timeout)

Phenomenon: The upper computer cannot read any channel data or returns an error code when reading.

Troubleshooting steps:

Physical layer inspection

Confirm that the communication cable is connected to the correct RS485/422 terminal (usually A, B, GND).

Check the terminal resistance: A 120 Ω resistor should be connected at both ends of the bus (TN3801 and the main station). If TN3801 is an end device, has the terminal resistor been enabled internally (refer to manual MT5015 jumper settings).

Measure the resistance between A and B, which should be around 60 Ω (two 120 Ω parallel connections).

Protocol parameter matching

Use the PC serial port debugging assistant to set the same baud rate (default 9600), data bits (8), stop bit (1), and no checksum as TN3801. Send Modbus read hold register command (function code 03) and check if there is a correct frame response.

Common error: The main station address does not match the station address set by TN3801. TN3801 corresponds to a Modbus address for each channel, but typically the device itself has a global address. Refer to the manual for confirmation.

Redundant port switching test

TN3801 has two redundant RS485 ports (usually labeled as COM1 and COM2). If COM1 does not respond, switch the main station cable to COM2 and confirm that the main station program has also been switched accordingly. If COM2 is working properly, it indicates that COM1 hardware is damaged. COM2 can be temporarily used and repairs can be arranged.

4.5 Fault phenomenon five: The liquid level reading is normal, but there is no signal output from 4-20 mA

Possible reasons:

Analog output not activated or channel configuration error

External load resistance is too high or short circuited

Open circuit output circuit

troubleshoot

Measure the AO+and AO - terminals of TN3801 directly with a multimeter in mA mode, which should normally be between 4-20 mA as the liquid level changes. If there is no current, check if the internal jumper is set to "active output" mode.

If there is current but the external device displays zero, please check the input impedance of the external receiving device (should be ≤ 500 Ω).


Maintenance and Calibration Plan

To ensure the long-term stable operation of TN3801, it is recommended to perform maintenance tasks according to the following cycle:

5.1 Monthly Inspection

Air path filter: Observe the water cup of the integrated filtration unit, and if the accumulated water exceeds 1/3, discharge it in a timely manner.

Gas supply pressure: Record whether the inlet pressure is stable at 6-10 bar.

Alarm log: Read the system self-test alarm through the display unit or Modbus. If there is a record of "Low Air Pressure" or "Channel Failure", handle it in a timely manner.

5.2 Quarterly maintenance

Accuracy verification: Select 1-2 representative cabinets and compare the readings of TN3801 using a manual ruler (such as a depth gauge). If the deviation exceeds ± 0.5% FS, perform online two-point calibration.

Bubble tube inspection: For tanks with scaling risks (such as sewage tanks and crude oil tanks), check whether the bubble tube opening is blocked and remove sediment.

Tightening of wiring terminals: In vibration environments, electrical terminals may become loose. Use a torque screwdriver to tighten them again.

5.3 Annual in-depth maintenance

Sensor calibration: Use a high-precision pressure source (0.05 level) to perform full-scale linearity calibration on all channel back pressure sensors.

Cleaning of flow regulator: Remove the flow regulator from each channel and use anhydrous alcohol ultrasonic cleaning to remove oil sludge.

Communication redundancy test: Manually disconnect COM1, confirm that the system automatically switches to COM2 and the data is continuous without interruption.

Backup channel test: If the cabinet is not fully equipped, a backup bubble tube can be pre installed using the backup channel to quickly replace the faulty channel.

5.4 Recommended spare parts

Automatic non return valve component (1 piece for every 8 channels)

Flow regulator (1 piece for every 16 channels)

Back pressure sensor (1 piece per cabinet)

Air filter cartridge (matching filter unit)


Key points of communication integration and software configuration

As a slave station of the ship automation system, TN3801 needs to be correctly integrated with the main station (such as PLC, HMI, AMS). The following are details that are easily overlooked in actual projects:

6.1 Modbus Register Mapping

By default, TN3801 stores the liquid level value for each channel as a 16 bit integer, measured in 0.1% FS or centimeters (depending on the configuration). For example:

Register Address 40001: Channel 1 Liquid Level (Floating Point or Integer)

Register address 40002: Channel 2 liquid level, and so on

Please refer to Chapter 4 of Technical Manual MT5015 for a detailed address table.

6.2 Baud rate and communication parameter settings

It can be set through the TN3801 internal DIP switch or display unit menu:

Optional baud rates: 2400, 4800, 9600, 19200, 38400

Data format: 8N1 (default), 8E1, 8O1

Station address: 1-247

Attention: After modifying communication parameters, it is necessary to power on again or perform a soft reset to take effect.

6.3 Redundant Port Wiring Example

Two RS485 ports can be connected to two different main stations (such as the main PLC and backup PLC) using a "daisy chain", or one to the local display and the other to the upper computer. When wiring:

Port A: T+/R+connected to main station A (+)

Port B: T -/R-connected to main station B (-)

The common terminal (GND) must be connected to the main station signal ground to avoid common mode voltage damaging the interface.


Selection and replacement upgrade suggestions

Upgrading to TN3801 can bring significant benefits to ships that are still using early electrical level measurement systems, such as single channel pneumatic transmitters and old models without Modbus communication

Reduce the risk of leakage by replacing multiple pneumatic pipelines with a single multi-core cable.

Digital integration: directly connected to ship Ethernet or fieldbus without the need for additional signal converters.

Redundant communication: Improve the availability of monitoring systems.

Low maintenance: Automatic flow regulation and self diagnostic functions significantly reduce manual inspections.

Attention should be paid when replacing:

The original bubble tube can continue to be used by simply connecting the gas outlet of TN3801 to the existing pipeline.

The power supply voltage must match: TN3801 supports 115/230 VAC switching, please confirm when ordering.

If the original system uses 4-20 mA analog signals to the alarm panel, TN3801's analog output module (4-20 mA per channel) can be optionally equipped to achieve seamless replacement.


Case study: No reading of the whole machine caused by gas source pressure loss

Background: A 100000 ton oil tanker reported that the liquid level displayed in all channels of TN3801 was 0 (the lowest value), and the ship was in a ballast state but the actual ballast tank was full.

Troubleshooting process:

Step 1: Check the air supply pressure gauge of the cabinet, the pointer is at 0 bar. Inquired about the engine room and found that the main air compressor of the ship had tripped and the backup air compressor had not automatically started.

Step 2: Restore power to the air compressor, wait for the air pressure to rise to 7 bar, and gradually restore the TN3801 liquid level reading to normal within 30 seconds.

Step 3: Check the non return valve status, all valves are open normally and there is no backflow phenomenon.

Conclusion: After the gas source is interrupted, the non return valve closes to protect the internal sensor. After the gas supply is restored, the system automatically returns to normal. Suggest adding an independent small gas storage tank (20 L) to TN3801 to cope with short-term gas source fluctuations.

  • Lust LTi Drives CDA34.010 W3.0 Frequency Inverter
  • LTi SO22.003.0010.0000.0 ServoOne Junior Drive
  • LUST LTi Drives CDA32.008 Servo Drive
  • LUST LTi DRIVES LSH-074 Servo Motor
  • Lti CDB32.004.C2.4.SH AC Servo Drive
  • Lust LTi Drives VF1202S Frequency Inverter
  • Lust LTI Drives CDB32.004.C3.0.SH Servo Controller
  • LUST SO84.012.0030.1700.2 Servo Drive
  • Lust LTi CDB32.004 Servo Drive
  • LUST LTI Drives CDA34.006 Servo Drive
  • LTi DRiVES BR-090.03.540-UR Braking Resistor
  • Lust LTI Drives CDA34.017 Servo Controller
  • Lust LTi Drives CDE34.010.D2.4 Positioning Controller 10A
  • LTi Drives LSH-050-3-30-48/T1 PM Servo Motor
  • LTI CDD34.005.C2.1 Servo Drive Controller
  • LUST LTI Drives CDB32.003.C2.4 Servo Drive
  • LTI D-35633 Drive Servo Drive Controller
  • LTI Drives GmbH SO22.003.0042.0000.0 Servo Controller
  • LTi Drives SO84.006.1030.0000.2 Servo Controller
  • LUST LTi Drives CDA32.008 C1.4 HF V180.15 1.5 kW
  • LTI Drives Servo One SO84.045.0010.0001.2-W 22 kW
  • Lust LTI CDE32.003.C2.4 Servo Drive Controller
  • LUST LTI Drives CDA34.003 Servo Controller
  • LUST LTI Drives CDA32.006 Servo Controller
  • Lust LTi Drives CDE32.004 Servo Drive
  • LUST LTi Drives SO84.012 Servo Controller
  • LTI DRIVES LSH-060 Servo Motor
  • LUST LTI Drives CDE32.004 with CM-DPV1
  • LTi DRiVES SO84.016 Servo Drive
  • LTI Drive CM-DPV1 Communication Module
  • LTi DRiVES DSM4-05.4-20R82-400 Servo Motor
  • LUST LTI Drives CDA34.003 Servo Controller
  • LTI Drives Servo One SO84.045.0010.0001.2-W 22 kW
  • LUST LTI Drives CDB32.008 W2.4 BR PC1 Servo Drive
  • LTi Drives SO84.006.1030.0000.2 Servo Controller
  • LTI DRIVES CDE34.010D2.4 Servo Drive Controller
  • Hettich Rotanta 46 RSC Control Board VF1204S
  • Lust LTI Drives CDA34.017.C2.CP Servo Controller 7.5 kW
  • LUST LTI Drives CDA34.003.C3.0 Servo Controller 0.75 kW
  • Lust LTI Drives CDA34.008.C1.3 Servo Controller 3 kW
  • Lust LTi Drives CDB22.004.0111.00.0 Servo Drive
  • LTi Drives SO84.032.0030.1000.2 Servo Controller
  • LUST LTi CDA32.004 C1.4 H08 B0 Servo Controller
  • LTI DRIVES CDB34.010 C2.4 Servo Drive
  • LUST LTi Drives CDA32.008 C1.4 Servo Controller
  • LTI Motion CDE32.003.C3.0 Servo Positioning Controller
  • LTI DRIVES CDE34.010 D2.4 Servo Drive Unit
  • LUST LTi Drives CDD34.005.C2.1 Servo Drive
  • LTi Drives SO84.012.0002.0100.2 Servo Controller
  • LUST LTi Drives CDE34.010.D2.4 Servo Drive
  • LUST LTI Drives CDF30.008 Servo Drive
  • LTi Drives SO CM-P.0010.11.00.0 Power Module
  • LTi DRiVES SO84.008.0002.0100.2 Servo Controller
  • LTI MOTION Servo Drive SO22.006.0040.1000.1
  • LTi DRiVES SO24.007.0030.1000.0 ServoOne Junior
  • LTi DRiVES LUST BC1300 Braking Module
  • LUST LTI DRIVES CDE34.010 Variable Frequency Drive
  • LUST LTI DRIVES CDA32.004 Servo Drive
  • LTi DRiVES LST-074-2-30-560/T1 Servo Motor
  • LUST LTI DRIVES CDB32.008 Servo Drive Module
  • Lust Antriebstechnik LTI Drives VF1204S Inverter
  • Lust LTI Drives CDE32.008 C3.0 Positioning Controller
  • LTI Drives LUST Servo One C-5633 D-35633
  • Lust LTI Drives CDA34.008.C1.3 Servo Controller 3kW
  • LTI CDF30.008 C2.6 Servo Drive 10962161
  • LUST LTi Drives CDB32.004 C2.3 SH Servo Drive
  • Lust LTi Drives CDE34.010 D2.0 Servo Drive
  • LTi Motion CDA32.006 Servo Drive with CM-CAN1
  • Lust LTI Drives CDB32.008 C2.3 Servo Controller
  • LTi CDE34.017.W3.0 Servo Drive
  • LUST LTI LST-074-2-30-320/T1 Servomotor
  • Lust LTi CDF30.002 C3.0 Positioning Controller
  • LTi DRIVES CDF30.008.C2.4 Drive
  • LUST LTI CDB32.008 W2.4 BR PC1 Drive
  • LTi SO84.004.0002.0100.2 Servo Controller
  • LTi SO84.012.0030.0011.2 ServoOne Drive
  • LTI Drives LUST Servo One C-5633 D-35633
  • LTi DRiVES c-line Smart Card A028.V01.1
  • LUST LTI CD A34.008 W1.4 BR Drive
  • LUST LTI LSH-097-2-30-560/T1 Servomotor
  • LUST LTI LST-074-2-30-320/T1 Servomotor
  • LUST LTi CDB32.004 C2.4.SH Servo Drive
  • LTI Drives PM-E40.2DRA054P Pitch Inverter
  • Lust LTI Drives CDF30.008 Servo Drive 8673548
  • LTI Drives CDF30.002.C0.7 Servo Controller
  • Lust LTI Drives CDB32.008.W2.4 Servo Drive
  • Lust LTI Drives CDB34.003 Servo Motor Driver
  • Lust LTI Drives CDA32.004 Servo Drive 3084456
  • Lust LTI Drives CDE34.005.W2.2 Servo Drive
  • Lust LTI Drives CDA34.006.W3.0 Servo Drive
  • LTI Drives CDF30.008.C2.4 Servo Controller
  • LTI Drives Lust CDB32.004.C2.4.SH Servo Drive
  • Delta Design 1666339-501 Micro Stepper PCB 114970
  • APEXEL 100X Microscope Mobile LED Pocket Lens
  • Micro Innovation XV-152-D4-10TVR-10 Touch Screen
  • Micro Innovation XVH330-57MPI-1-10 Touch Screen Glass
  • Delta Design 1666339-501 Micro Stepper PCB 114967
  • Micro Design MC100-MA V3 Board
  • Delta Design 1666339-501 Micro Stepper PCB 114968
  • Delta Design 1666339 PCB Micro Stepper ITR 116487
  • Micro Innovation XV-440-10TVB-1-10 Panel
  • Sterling 9B21-3 Micro Switch Durable Design
  • ATTINY104-XNANO Microchip AVR Prototype Board
  • Delta Design 1666339 Micro Stepper PCB ITR 116539
  • Super Micro X7SBJ Industrial Main Board
  • Delta Design NMS BD 1698437-501 Stepper Board
  • Micro Innovations Turbo Track Keyboard KB420BL
  • Micro Design PC-1 PC-1-H-DU010 Operator Panel
  • TCI MICRO MD 250mA 7W Dimmable LED Driver
  • Delta Design 1666339 Micro Stepper PCB ITR 116485
  • Delta Design NMS BD 1698437-501 Stepper Board
  • Life Instruments 714-1120-1U Micro Curette
  • Delta Design 1657925-501 Micro Processor PCB
  • Micro 100 RTC-125-2 Carbide Engraving Tool
  • Micro Design Inc. 2106022 Liquid Level Sensor PCB
  • Periodontal Micro Surgical Full Kit 20pc Blue Titanium K1004
  • Micro Innovation XN-2DO-24VDC-0.5A Module
  • Wide Innovative Technology PS-01 Micro Positioner Set
  • HU FRIEDY NH5020 Castroviejo Needle Holder Set
  • Moeller Micro Innovation XV-232-57BAS-1-10 Touch Screen
  • Micro Design System MCVP-300VR Control Module 24VDC
  • Scanlan 3003-234-1 Titanium Jacobson Needle Holder
  • Micro Innovation XV-102-B0-35TQR-10-PLC Panel
  • Promot Micro Design 3x8 Output 2187F
  • Micro Innovation LIC-SW-Galileo 91 30 000600 License Certificate
  • Micro Design AI0486.A4-50 Control Module Board
  • Micro Innovation XN-2DO-24VDC-0.5A Output Module
  • Micro Design Not-Aus Relais AE 8.96 AE 896