Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

Complete Guide to On site Maintenance and Troubleshooting of Honeywell TN3801 Electro Motive Liquid Level

F: | Au:FANS | DA:2026-05-21 | 328 Br: | 🔊 点击朗读正文 ❚❚ | Share:

Complete Guide to On site Maintenance and Troubleshooting of Honeywell TN3801 Electro Motive Liquid Level Measurement Cabinet

In ship operation, the accurate measurement of liquid levels such as service tanks, ballast tanks, and draft depth is directly related to ship stability, cargo loading and unloading safety, and fuel management. Traditional mechanical or purely electronic level gauges often face problems such as scaling, corrosion, and condensate interference in harsh marine environments. The TN3801 Electro pneumatic Level Measuring Cabinet launched by Honeywell Marine adopts the principle of bubble measurement, combining pneumatic sampling with microprocessor data processing to achieve independent and highly reliable liquid level monitoring with up to 24 channels. This product has been certified by major international classification societies and is suitable for installation in safe areas above the main deck of various types of ships.

This article is aimed at ship electrical engineers, engineers, and maintenance personnel. It systematically introduces the working principle, installation and commissioning points, daily maintenance methods of TN3801, and focuses on summarizing common on-site fault phenomena and standardized troubleshooting processes to help users quickly locate gas, circuit, or communication problems and ensure the continuous and reliable operation of ship liquid level monitoring systems.


System Overview and Core Features

1.1 Positioning and Application Scenarios of TN3801

TN3801 is a modular and compact electric liquid level measurement cabinet designed specifically for ship liquid level monitoring. Its typical applications include:

Service cabin: daily fuel, oil, fresh water, seawater and other containers

Ballast tank: ship ballast water management to ensure navigation stability

Draft monitoring: bow, stern, and starboard draft depth of the ship

Each TN3801 cabinet can accommodate 8 to 24 independent pneumatic measurement channels, and the air paths between each channel are completely independent and do not interfere with each other. Each channel is equipped with an automatic non return valve, which automatically closes when the gas supply pressure is below 1 bar, preventing the liquid in the cabin from flowing back into the transmitter through the bubble pipeline, thereby protecting electronic and pneumatic components. This design is extremely critical in on-site maintenance, avoiding liquid contamination and damage caused by gas source interruption.

1.2 Main technical specifications (based on official data)

Parameter indicators

Number of channels 8~24 (configurable)

Measurement accuracy ± 0.3% FS @ 20 ℃

Communication interface 2-channel redundant RS485/422, Modbus protocol

Supply pressure 6/10 bar (recommended)

Gas consumption 15 L/h per channel

Working temperature+5 ℃ to+70 ℃

Storage temperature+5 ℃ to+70 ℃

Pneumatic interface ¼ GAS internal thread

Power supply 230/115 VAC

Electricity consumption 0.5 VA per channel

Protection level IP44

Installation environment safety zone (within the protective area above the main deck)

1.3 Key optional functions

Integrated air filtration unit: ensuring that the gas entering the measurement pipeline is dry and clean

Pressure chamber connector (for measuring pressurized tanks)

Display unit: capable of locally displaying the liquid level values of each channel

8 × 4-20 mA analog input: can be connected to third-party sensors

Self diagnosis and 4-20 mA output: Each channel can output analog liquid level signals to external systems


Detailed explanation of working principle

TN3801 adopts the classic bubble liquid level measurement principle, which is especially applicable to the tank of ships with foam, corrosive liquid or high viscosity medium.

2.1 Bubble measurement process

Each measurement channel works independently:

Air source input: The main air source (6 or 10 bar) passes through the filtering and pressure regulating components inside the cabinet, and after stabilizing, it is supplied to the automatic flow regulators of each channel.

Constant flow bubbles: The flow regulator of each channel stabilizes the airflow at approximately 15 L/h, and continuously releases bubbles into the liquid through a bubbling line immersed in the bottom of the cabinet.

Back pressure measurement: The gas pressure inside the bubble tube is balanced with the static pressure of the liquid column at the nozzle. The back pressure is converted into an electrical signal by a pneumatic sensor.

Liquid level calculation: The microcontroller compensates for the current liquid level height based on back pressure, liquid density, and atmospheric pressure, with an accuracy of ± 0.3% FS.

2.2 Key role of non return valve

At the air outlet of each channel, a normally open automatic non return valve is installed. The action logic is as follows:

Normal gas supply (≥ 1 bar): The valve remains open and bubbles are continuously generated.

Air source interruption or sudden pressure drop (<1 bar): The valve instantly closes, cutting off the passage between the liquid in the cabin and the measuring pipeline.

This design is extremely practical on site: when the ship's air compressor fails or the air supply pipeline leaks, even if the liquid level is higher than the bubble tube mouth, the liquid will not be sucked back into the TN3801 cabinet, thus avoiding contamination and damage to sensors, pipelines, and control boards. After the fault is restored, the valve automatically opens again, and the system can resume normal measurement without manual exhaust.

2.3 Data Processing and Communication

TN3801 is equipped with a microcontroller that is responsible for:

Collect back pressure analog signals from each channel and perform AD conversion

Perform linearization, temperature compensation, and density correction

Manage two redundant RS485/RS422 communication ports using standard Modbus RTU protocol

Redundant communication design means that when the main communication line fails, the system automatically switches to the backup line without manual intervention. This is crucial for ship automation systems such as IAS and AMS - liquid level data can be continuously uploaded to the bridge or engine room monitoring system without being lost due to a single point of failure.


Key points for installation and debugging

3.1 Mechanical installation requirements

Installation location: above the main deck, in a safe and protected area. Avoid direct exposure to ocean waves, high temperature heat sources, or locations with severe vibrations.

Protection level: IP44, splash proof, but not recommended for long-term exposure to high-pressure water jets.

Pneumatic interface: The pneumatic interface of each channel is a ¼ GAS internal thread. It is recommended to use stainless steel or reinforced nylon pipes to connect to the cabin bubble pipes.

Air source quality: An oil-water separator and a 5 μ m level filter should be installed to prevent oil mist or moisture from entering the flow regulator and causing blockage. TN3801 can be optionally equipped with an integrated air filtration unit, strongly recommended for selection.

3.2 Electrical Wiring

Power supply: 230 VAC or 115 VAC, pay attention to terminal labeling. Extremely low power consumption (0.5 VA/channel), the whole machine usually does not exceed 15 VA.

Communication cable: Two RS485/422 channels use shielded twisted pair cables, it is recommended to use AWG 22 or thicker, and the shielding layer should be grounded at one end. The maximum transmission distance can reach 1200 meters (baud rate ≤ 9600).

Analog output (if configured): 4-20 mA active or passive output, maximum load resistance of 500 Ω.

3.3 Debugging steps

Airtightness test: Without connecting the air source, seal the air outlet of each channel with a plug, introduce 6 bar compressed air, and check for leaks in the pipeline joints.

Channel self-test: Activate each channel one by one through the built-in diagnostic mode (see technical manual MT5015 for details), and observe whether the output of the back pressure sensor is linear.

Zero and full calibration: Use a reference chamber or simulated pressure source with known liquid level height to perform two-point calibration on each channel. The official recommendation is to calibrate at 20 ℃ to achieve an accuracy of ± 0.3% FS.

Communication testing: Read the registers of each channel through a Modbus master station (such as PLC or PC debugging software) to verify the address, baud rate, and parity settings.

Common fault phenomena and troubleshooting

Based on years of on-site experience, the faults of TN3801 mainly focus on four aspects: gas source problems, pipeline blockage/leakage, communication interruption, and channel accuracy drift. The following provides a standardized troubleshooting process based on the classification of fault phenomena.

4.1 Fault phenomenon 1: Abnormal low or no change in liquid level reading of one or all channels

Possible reasons:

Air source interruption or insufficient pressure (<1 bar)

The bubble tube in this channel is blocked (due to sludge and crystals in the cabin)

Automatic non return valve mistakenly closes (although rare, if there are foreign objects inside the air path, it can cause the valve core to get stuck)

Back pressure sensor damaged

Troubleshooting steps:

Observe the gas supply pressure gauge on the TN3801 panel (if configured) and confirm if the input pressure is between 6-10 bar. If it is below 1 bar, check the ship's main air system or pressure reducing valve.

Remove the bubble tube connector of the faulty channel, briefly ventilate (3-5 seconds), and feel with your hand whether there is airflow at the tube mouth. If there is no airflow, it indicates that the internal air path is blocked or the flow regulator is malfunctioning.

Alternative method: Connect the gas path of this channel to another known normal cabinet. If the reading is restored, the original bubble tube will be blocked; If the issue persists, it is within TN3801.

Check the automatic non return valve: Use a small screwdriver to lightly press the valve core. If it can rebound normally and open after ventilation, then the valve is normal. Otherwise, the channel module needs to be replaced.

Temporary emergency measures: If measurement is urgently needed, the gas path of the adjacent normal channel can be temporarily switched to the faulty cabinet (note that the original channel must be closed), but it needs to be restored after maintenance.

4.2 Fault phenomenon 2: All channel readings fluctuate or jump simultaneously

Possible reasons:

Unstable gas source pressure (such as significant pressure fluctuations caused by the start and stop of an air compressor)

Communication interference (poor grounding of RS485 or parallel wiring with power cables)

Power supply voltage fluctuation (unstable ship power grid)

Troubleshooting steps:

Install a 10 L gas storage tank and pressure regulator valve at the inlet of the gas source, and observe whether the fluctuation disappears.

Use an oscilloscope or multimeter to measure whether there is a common mode voltage (ideal value<2 V) between the communication line and ground. If exceeded, check if the shielding layer is grounded at both ends (should be changed to single ended grounding).

The AC input voltage of TN3801 should be measured within ± 10% of the rated value. If there is a large fluctuation, an online UPS can be added.

4.3 Fault phenomenon three: The reading of a single channel is significantly high (exceeding the actual liquid level)

Possible reasons:

The bubble tube is damaged or detached, causing gas to leak from the middle and increasing back pressure.

Density parameter setting error (the liquid density value stored in the microcontroller is too high).

Zero drift of back pressure sensor.

Troubleshooting steps:

Turn off the gas source of the channel, open the inspection port on the top of the cabinet, remove the bubble tube, and visually inspect for cracks, bends, or detachment.

Use a standard pressure source (such as a piston pressure gauge) to directly input simulated pressure to the back pressure sensor of the channel, and compare the displayed liquid level value. If the deviation exceeds 0.5%, perform the calibration procedure (see maintenance manual MM5015).

Check if the liquid density value in the TN3801 configuration parameters matches the current cabin medium (e.g. fuel density 0.86 kg/L, seawater 1.025 kg/L).

4.4 Fault phenomenon four: Communication interruption (Modbus master station reading timeout)

Phenomenon: The upper computer cannot read any channel data or returns an error code when reading.

Troubleshooting steps:

Physical layer inspection

Confirm that the communication cable is connected to the correct RS485/422 terminal (usually A, B, GND).

Check the terminal resistance: A 120 Ω resistor should be connected at both ends of the bus (TN3801 and the main station). If TN3801 is an end device, has the terminal resistor been enabled internally (refer to manual MT5015 jumper settings).

Measure the resistance between A and B, which should be around 60 Ω (two 120 Ω parallel connections).

Protocol parameter matching

Use the PC serial port debugging assistant to set the same baud rate (default 9600), data bits (8), stop bit (1), and no checksum as TN3801. Send Modbus read hold register command (function code 03) and check if there is a correct frame response.

Common error: The main station address does not match the station address set by TN3801. TN3801 corresponds to a Modbus address for each channel, but typically the device itself has a global address. Refer to the manual for confirmation.

Redundant port switching test

TN3801 has two redundant RS485 ports (usually labeled as COM1 and COM2). If COM1 does not respond, switch the main station cable to COM2 and confirm that the main station program has also been switched accordingly. If COM2 is working properly, it indicates that COM1 hardware is damaged. COM2 can be temporarily used and repairs can be arranged.

4.5 Fault phenomenon five: The liquid level reading is normal, but there is no signal output from 4-20 mA

Possible reasons:

Analog output not activated or channel configuration error

External load resistance is too high or short circuited

Open circuit output circuit

troubleshoot

Measure the AO+and AO - terminals of TN3801 directly with a multimeter in mA mode, which should normally be between 4-20 mA as the liquid level changes. If there is no current, check if the internal jumper is set to "active output" mode.

If there is current but the external device displays zero, please check the input impedance of the external receiving device (should be ≤ 500 Ω).


Maintenance and Calibration Plan

To ensure the long-term stable operation of TN3801, it is recommended to perform maintenance tasks according to the following cycle:

5.1 Monthly Inspection

Air path filter: Observe the water cup of the integrated filtration unit, and if the accumulated water exceeds 1/3, discharge it in a timely manner.

Gas supply pressure: Record whether the inlet pressure is stable at 6-10 bar.

Alarm log: Read the system self-test alarm through the display unit or Modbus. If there is a record of "Low Air Pressure" or "Channel Failure", handle it in a timely manner.

5.2 Quarterly maintenance

Accuracy verification: Select 1-2 representative cabinets and compare the readings of TN3801 using a manual ruler (such as a depth gauge). If the deviation exceeds ± 0.5% FS, perform online two-point calibration.

Bubble tube inspection: For tanks with scaling risks (such as sewage tanks and crude oil tanks), check whether the bubble tube opening is blocked and remove sediment.

Tightening of wiring terminals: In vibration environments, electrical terminals may become loose. Use a torque screwdriver to tighten them again.

5.3 Annual in-depth maintenance

Sensor calibration: Use a high-precision pressure source (0.05 level) to perform full-scale linearity calibration on all channel back pressure sensors.

Cleaning of flow regulator: Remove the flow regulator from each channel and use anhydrous alcohol ultrasonic cleaning to remove oil sludge.

Communication redundancy test: Manually disconnect COM1, confirm that the system automatically switches to COM2 and the data is continuous without interruption.

Backup channel test: If the cabinet is not fully equipped, a backup bubble tube can be pre installed using the backup channel to quickly replace the faulty channel.

5.4 Recommended spare parts

Automatic non return valve component (1 piece for every 8 channels)

Flow regulator (1 piece for every 16 channels)

Back pressure sensor (1 piece per cabinet)

Air filter cartridge (matching filter unit)


Key points of communication integration and software configuration

As a slave station of the ship automation system, TN3801 needs to be correctly integrated with the main station (such as PLC, HMI, AMS). The following are details that are easily overlooked in actual projects:

6.1 Modbus Register Mapping

By default, TN3801 stores the liquid level value for each channel as a 16 bit integer, measured in 0.1% FS or centimeters (depending on the configuration). For example:

Register Address 40001: Channel 1 Liquid Level (Floating Point or Integer)

Register address 40002: Channel 2 liquid level, and so on

Please refer to Chapter 4 of Technical Manual MT5015 for a detailed address table.

6.2 Baud rate and communication parameter settings

It can be set through the TN3801 internal DIP switch or display unit menu:

Optional baud rates: 2400, 4800, 9600, 19200, 38400

Data format: 8N1 (default), 8E1, 8O1

Station address: 1-247

Attention: After modifying communication parameters, it is necessary to power on again or perform a soft reset to take effect.

6.3 Redundant Port Wiring Example

Two RS485 ports can be connected to two different main stations (such as the main PLC and backup PLC) using a "daisy chain", or one to the local display and the other to the upper computer. When wiring:

Port A: T+/R+connected to main station A (+)

Port B: T -/R-connected to main station B (-)

The common terminal (GND) must be connected to the main station signal ground to avoid common mode voltage damaging the interface.


Selection and replacement upgrade suggestions

Upgrading to TN3801 can bring significant benefits to ships that are still using early electrical level measurement systems, such as single channel pneumatic transmitters and old models without Modbus communication

Reduce the risk of leakage by replacing multiple pneumatic pipelines with a single multi-core cable.

Digital integration: directly connected to ship Ethernet or fieldbus without the need for additional signal converters.

Redundant communication: Improve the availability of monitoring systems.

Low maintenance: Automatic flow regulation and self diagnostic functions significantly reduce manual inspections.

Attention should be paid when replacing:

The original bubble tube can continue to be used by simply connecting the gas outlet of TN3801 to the existing pipeline.

The power supply voltage must match: TN3801 supports 115/230 VAC switching, please confirm when ordering.

If the original system uses 4-20 mA analog signals to the alarm panel, TN3801's analog output module (4-20 mA per channel) can be optionally equipped to achieve seamless replacement.


Case study: No reading of the whole machine caused by gas source pressure loss

Background: A 100000 ton oil tanker reported that the liquid level displayed in all channels of TN3801 was 0 (the lowest value), and the ship was in a ballast state but the actual ballast tank was full.

Troubleshooting process:

Step 1: Check the air supply pressure gauge of the cabinet, the pointer is at 0 bar. Inquired about the engine room and found that the main air compressor of the ship had tripped and the backup air compressor had not automatically started.

Step 2: Restore power to the air compressor, wait for the air pressure to rise to 7 bar, and gradually restore the TN3801 liquid level reading to normal within 30 seconds.

Step 3: Check the non return valve status, all valves are open normally and there is no backflow phenomenon.

Conclusion: After the gas source is interrupted, the non return valve closes to protect the internal sensor. After the gas supply is restored, the system automatically returns to normal. Suggest adding an independent small gas storage tank (20 L) to TN3801 to cope with short-term gas source fluctuations.

  • Atlas Copco PF3000-C-HW Tensor S4 S7 RBU Controller
  • Atlas Copco PPBE0613 24VAC Control Panel
  • Atlas Copco PF3000-C-HW Tensor S4 S7 Controller
  • Atlas Copco Neos ARC-D130-S+ Inverter Drive
  • Atlas Copco Power Focus SL PF4002-G-HW Controller
  • Atlas Copco 8436 6770 00 ILT Base Station
  • Atlas Copco 1900520400 Air Compressor Control Panel
  • Atlas Copco 1900-0711-51 Display Keypad Unit
  • Atlas Copco 1900-0710-52 Communication Control Board
  • Atlas Copco 1900-0701-04 Control Interface Module
  • Atlas Copco 8092 1143 40 SRTT Transducer 180Nm
  • Atlas Copco MT Focus 6000 Controller with Pump and Screwdriver
  • Atlas Copco Elektronikon GraphicPlus Controller PPBE0622 PPBE0633
  • Atlas Copco PF3109-G-DN-HW Tensor 8-9 Power Focus Nutrunner Control
  • Atlas Copco Elektronikon P1900520440 Touch Controller
  • Atlas Copco Power Focus 8 Controller 8436280002
  • Atlas Copco 8436 1500 03 FlexCarrier 3-Slot Torque System Component
  • Atlas Copco Power Focus 6000 PF6000 Industrial Controller
  • Atlas Copco TC-4000-P-PB-ES Power Macs Controller
  • Atlas Copco 8433-0015-20 8433001520 Cable Assembly
  • Atlas Copco 49X10301AB Pressure Transducer Sensor
  • Atlas Copco 8436180002 Replacement Filter Element
  • Atlas Copco C4700A01V216 Compressor Control Module
  • Alcatel-Lucent 3HE01019AAAA01 High-Speed Interface Module
  • Alcatel-Lucent 111381 Power Distribution Module
  • Alcatel TN 2523 1:1 CDN III Module – MRPQAE3
  • Alcatel-Lucent 3he06151aaac01 8-Port Interface Module – IPUIBKB3AA
  • Alcatel-Lucent LNW46 DMX Metro OC12 Interface Module – 108694878
  • Alcatel-Lucent 41A12C FT-2000 Optical Transponder Unit – 108188053
  • Alcatel-Lucent 8DG02607AA POW100 DC-DC Converter Module
  • Alcatel-Lucent LambdaXtreme WWBQ21 40G Optical Transponder
  • Alcatel-Lucent TN1891 5ESS Protocol Handler PHV5 Commcode 108747064
  • Alcatel-Lucent 300-0303-900 T1D3PDL1AE Digital Matrix Card
  • Alcatel-Lucent G-821M-A Module
  • Alcatel Lucent MPT-GC Eth 1G+ARM TX 81-86GHz 3DB80005AAAAO1
  • Nokia 3KC48990AB 1830PSS 16FAN2 Fan Unit
  • Alcatel 3EC17041AA PSPC-G4 PCB CP011200552
  • Alcatel 300-0437-906 Rev F DEXCS DMC T1D1L0S Module
  • Alcatel-Lucent 3DW03697ABBA01 TFD64A Module
  • Alcatel-Lucent AWR12 S1-1 UN Interface T3PQAC3AAA
  • ALCATEL LUCENT 9500-MPR ODU RADIO MPT-HC V2 9558HC 3DB20914BAAA03 6GHZ
  • Alcatel-Lucent 9500-MPR ODU 300 11GHz Microwave Radio MPT 3DB23035AEAA01
  • Alcatel 2C7-1005-000 Teflon Bell Jar Holder Ring – 146111
  • Alcatel-Lucent BNJ118 S1:4 Circuit Board – Interface Module
  • Alcatel-Lucent 9500-MPR ODU 300 6GHz Microwave Radio MPT 3DB23215AFAA01
  • Alcatel 3EM04001AA Signal Processing Unit with Accessory Cards
  • Alcatel VAUCAL5KAB AA1418FE2BG 3FE67437AAD02 Interface Card
  • Alcatel-Lucent 1642 Edge Multiplexer N1217P YF – Access Node
  • Alcatel-Lucent 3HE07158BA 7750 SR-12 12-Port 10GIGE MultiCore IMM IPUCA741AA
  • Alcatel 101200429000 Power Divider 746-776 MHz with Heatsinks
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215ADAA01 High Power Radio
  • Alcatel-Lucent 9500-MPR MPT-HC 23GHz 2/2P ODU Radio 3DB20474BA
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215AAAA01 Low Power Radio
  • Alcatel 3BA52126ABAA OmniPCX 4400 Compact Cabinet
  • Alcatel-Lucent 3HE12300AA 7750 SR-1 Subrack with Licenses
  • Alcatel 300-1368-903 Rev C DEXCS SPA-1 T1PQAC1 Line Card
  • Alcatel-Lucent 408977981 WOWUAB6HAA 10G XPR OTU2 XPonder Card
  • Alcatel-Lucent-Nokia 3HE08423AARC01 7750 SR Control Processor Module IPUCBGZ1AA
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 6GHz 3DB23215ABAA01 Low Power Radio
  • Alcatel-Lucent CPU7-2 3BA23259ABJE 05 Control Processor Module
  • Alcatel WTM11AD 3DW03915DABA01 Optical Transponder Module
  • Alcatel-Lucent 1340FMPK Card Chip BA5IVY6BAA – Processor Module
  • Alcatel-Lucent 3HE06151ACAC01 Control Fabric Module
  • Alcatel-Lucent 9500-MPR 18GHz 1P-1 Protection ODU Radio 3DB20433BA AA04
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 18GHz Radio 3DB20433BAAA04
  • Alcatel-Lucent SM269 LMPQ04KAXX Circuit Pack – Interface Module
  • Alcatel OME25HP Filter Cartridge – 107494
  • Alcatel-Lucent ALU-BZ74 99BC-4 –48V Battery Cabinet
  • Alcatel-Lucent WWAA37 Optical Amplifier WMAPZNZAAB – CP Series
  • ALCATEL LUCENT 9500-MPR ODU RADIO MPT-HC V2 9558HC MPT-XP 3DB20476BAAA04 23GHZ
  • Alcatel Tyco Yukon ES760A Rectifier
  • Alcatel-Lucent 9500-MPR ODU 300 MPT 23GHz 3DB23045HMAA02 Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 11GHz 3DB20548ACAA01 Microwave Radio
  • Alcatel Lucent 3DH03173AKAA Module
  • Alcatel-Lucent 76-0300-02 CSM-V2 PCB
  • Alcatel 9400 UX ODU Module 3CC06729ABAA
  • Alcatel-Lucent 408981363 Jigsaw A Band Block 24/-48V KS24624L58
  • Alcatel 3BA53095 PCB Card
  • Alcatel 2C7-1005-000 Bell Jar Holder Ring Teflon PC7-1005-000
  • Alcatel-Lucent ES640 PWDQAGKUAA 5ESS 48V DC Alarm Control Unit
  • Alcatel-Lucent 9500-MPR ODU 300 23GHz Microwave Radio MPT 3DB23045HM
  • Alcatel-Lucent KFA720 WMOTCMVLAB Optical System Interface Carrier
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 15GHz Microwave Radio 3DB20373BAAB04
  • Alcatel-Lucent AKM70 S1-7 SMUX1 Sub-Multiplexer – T3PQWAEAAH
  • Alcatel-Lucent 107486490 DDM-2000 SONET DS3 Circuit Pack – BBG4B
  • Alcatel-Lucent SBEVM BNJ82 1:12 Module – AV950-01168
  • Alcatel-Lucent 938A Optical Loss Set – Test & Measurement Kit
  • Alcatel-Lucent MS1025-25O16-ED Fiber Optic Unit – 48VDC
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 23GHz 1/1P Microwave Radio 3DB20473BA AA04
  • Alcatel-Lucent bCEM-U Control Module – 3BK28676ABAC01
  • Alcatel ASI20 Detector Control Module
  • Alcatel Lucent 130B S-1 PWPQ08B Power Unit
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC 6GHz 3DB20441BBAA02
  • Alcatel-Lucent 9500-MPR ODU MPT-MC 15GHz 3DB20824AAAA02 Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-MC 15GHz 3DB20822AAAB02 Microwave Radio
  • Alcatel-Lucent 3AL92111AA 1P10GSO Interface Module
  • Alcatel 8220 CTT 450 Turbo Pump Controller 127821
  • Alcatel-Lucent 3AL78823AAAE 02 Module
  • Alcatel-Lucent 90-0413-01 Universal Card
  • Alcatel-Lucent BRMA 10Base-T/100Base-TX Connecting Box 3BA56170ACAB010842
  • Woodward Micronet 5453-279 Rev E Chassis Rack for TMR Control
  • Alcatel-Lucent KFA632 WMOTBUKLAA 10G Optical Interface Carrier
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 3DB20474BAAB04 23GHz Microwave Radio
  • Alcatel-Lucent KFA720 WMOTCMVLAB SFP/XFP Optical Interface Carrier
  • Alcatel-Lucent 3AL00114AB Universal Interface Module
  • Alcatel-Lucent BBG9 S1:1 OHCTL Optical Hardware Control Module
  • Alcatel-Lucent FB16401-A-I03 GTD-5 Analog Master/Slave Control Board
  • Alcatel-Lucent MCR1721B Control Module
  • Alcatel-Lucent 9500-MPR 3DB20547ACAA01 ODU MPT-HC 11GHz Microwave Radio
  • Alcatel-Lucent 3HE01014AAAA02 Interface Module
  • Alcatel-Lucent 244-2091-005 High Density Digital Line Card V1.5
  • Alcatel-Lucent LAMBDAXTREME WWAA36 Optical Amplifier Module
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 6GHz 2P-2 Radio 3DB20444BAAA05
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC MPT-XP 6GHz 3DB20442BBAA02
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 23GHz 3DB20476ABAA01 Microwave Radio
  • Alcatel Lucent 3HE01019AAAA01 Module
  • Alcatel CPU5 3BA23071 PCB Card with IO2 3BA23050 Set
  • Alcatel-Lucent 9500-MPR ODU MPT-HC V2 9558HC 6GHz 3DB20443BBAA02
  • Alcatel Lucent 500-1113-211 Rev H Channel Bank Assembly
  • Alcatel Lucent 89-0419-B-2 BA9ATS0FAB Frontal Compute Module
  • Alcatel-Lucent LambdaXtreme 1625 WWAF31 Optical Amplifier CP Module
  • Alcatel Z24 3BA53065 Analog Extension Card 3BA52065 AAAA KAZZB-01
  • Alcatel 3EH08263AAXX000448 OmniPCX Office Large PBX System
  • Alcatel Lucent VSEM-C 3FE62453 XA VAUCAJZKAA 7330 DSLAM Line Card
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 3DB20432BAAA04 18GHz Microwave Radio
  • Alcatel-Lucent 9500-MPR ODU MPT-HC 3DB20546ACAA01 11GHz Microwave Radio
  • Alcatel-Lucent 3DB04823AAAA Circuit Board
  • Alcatel-Lucent 3DB04530AAAA Circuit Board