Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

TAIYO LX Series Generator Common Troubleshooting and Maintenance Guide

F: | Au:FANS | DA:2026-05-19 | 56 Br: | 🔊 点击朗读正文 ❚❚ | Share:

TAIYO LX Series Generator Common Troubleshooting and Maintenance Guide

The LX series generator (11.5kVA~2250kVA) is a medium to high power synchronous generator designed for industrial backup power, continuous operation, and islanding power generation scenarios. This series is divided into three excitation architectures: LX-G (basic type), LX-E (auxiliary winding enhanced type), and LX-H (permanent magnet generator excitation type), corresponding to different load characteristics and power quality requirements.

As the "heart" of power plants, the stability and maintenance convenience of generators directly affect power supply safety. This article is based on the technical parameters and common fault modes of the LX series, and summarizes a systematic diagnosis and maintenance process to help on-site engineers quickly troubleshoot problems and extend the life of the unit.


Characteristics and Fault Diagnosis of Excitation System

The core difference of the LX series lies in the excitation method, and the fault phenomena and handling methods of each method are different.

2.1 LX-G type: Main winding self-excited

LX-G takes a portion of the output from the main stator (armature winding) as the power supply and voltage detection signal for the AVR, which adjusts the excitation current according to the load size.

Typical fault: The voltage is normal under light load, but after adding load, the voltage drops significantly or even becomes unstable.

Common reasons: AVR power supply takes autonomous output. When the load contains a large number of harmonic or nonlinear thyristor rectified loads, the main winding voltage waveform is distorted, AVR sampling is distorted, resulting in insufficient excitation.

Troubleshooting steps:

Check the voltage at the AVR input terminal (which should be consistent with the generator output terminal).

Observe the waveform of the AVR power supply with an oscilloscope. If the distortion is severe, consider installing a harmonic filter or replacing it with LX-E/LX-H.

Check if the voltage regulating potentiometer on the AVR is drifting, and if necessary, recalibrate it according to the rated voltage.

Suggested application: LX-G is suitable for applications with linear loads as the main load (such as resistance heating, lighting, and conventional motor loads). If non-linear loads such as frequency converters and UPS are required, LX-E or LX-H should be selected.

2.2 LX-E type: Auxiliary winding excitation

LX-E has added independent auxiliary windings in the stator to provide excitation energy for heavy loads and short-term short-circuit currents, without the need for additional components such as current transformers.

Typical fault: Sudden voltage drop at full load, or slow voltage recovery after continuous short-term short circuit.

Common reasons: Internal open circuit, poor contact, or failure of AVR to switch to auxiliary winding power supply in the auxiliary winding.

Troubleshooting steps:

Measure the output voltage of the auxiliary winding (which should be 5% to 10% of the rated value when unloaded).

Check the connection wires and terminals between the auxiliary winding and AVR.

Simulate heavy loads (such as switching high-power motors), observe whether the response of the AVR lags behind. If the lag is severe, adjust the response time potentiometer of the AVR.

Advantage: The LX-E can provide 250% (50Hz) or 300% (60Hz) short-circuit current for 2 seconds, suitable for applications that require transient overcurrent capability (such as motor starting).

2.3 LX-H type: permanent magnet generator (PMG) excitation

LX-H independently supplies power to AVR through a coaxial mounted permanent magnet generator, completely isolated from the main output.

Typical faults: uncontrolled output voltage (too high or too low), or severe voltage drop when the load is put into operation.

Common reasons: PMG rotor demagnetization, PMG stator winding disconnection, AVR and PMG connection error.

Troubleshooting steps:

Measure the output voltage of PMG (usually 170-220VAC when unloaded, with frequency varying with speed).

If there is no output from the PMG, check if there are any foreign objects or severe magnetic attenuation on the surface of the PMG rotor (which can be measured using a Gaussian meter).

Check the PMG input fuse or circuit breaker protection component of AVR.

Advantages: LX-H provides the most stable voltage waveform and fastest dynamic response for harmonic loads (thyristor rectification, frequency converter, UPS front-end), making it the preferred choice for high reliability applications such as communication base stations and data centers.

Analysis and Handling of Voltage Faults

3.1 Steady state voltage deviation exceeds ± 1.0%

When the voltage fluctuation exceeds 1% under the rated load of the generator, the frequency stability of the mechanical or electronic governor should be checked first. Frequency drift can also lead to erroneous adjustment of AVR.

Adjust the "voltage regulation" potentiometer of the AVR under no-load conditions to return the voltage to its rated value.

Check the "stability" or "damping" potentiometer of the AVR to prevent oscillation.

Confirm whether the generator speed is stable (within ± 0.5% of rated frequency).

3.2 Transient voltage exceeding the standard (sudden loading and unloading of load)

Standard requirement: When suddenly adding 100% load (power factor ≤ 0.4), the maximum voltage drop should be ≤ 25%, and it should return to within -3% of the steady-state value within 2 seconds.

Voltage drop exceeding 25%:

Slow response of excitation system: The "gain" or "response" setting of AVR can be adjusted to be higher.

Low load power factor: Try to increase the natural power factor of the load as much as possible.

If the excitation winding of the exciter is broken or the rotating rectifier (diode) is damaged: stop the machine and check the rotating rectifier module (varistor and diode), and measure its forward/reverse resistance.

Recovery time too long (>2s): The AVR integration time constant is too large. You can lower the "integration gain" or set it to a faster recovery mode.

3.3 Insufficient voltage regulation range

The LX series typically allows for voltage adjustment of ± 5% at no-load rated speed. If the rated value cannot be adjusted:

Check if the "upper/lower limit" potentiometer of AVR has been mistakenly activated.

Measure the DC resistance of the stator winding of the exciter to determine if there is a turn to turn short circuit.

For LX-H, check if the output voltage of PMG is too low (possibly due to demagnetization of the magnetic steel).


Waveform distortion and harmonic problems

The distortion rate (deviation factor) of the no-load voltage waveform is specified to be ≤ 10%. If it exceeds the standard, it may cause downstream sensitive equipment to malfunction or overheat.

Reason: Short circuit between turns of stator winding, saturation of iron core, malfunction of rotating rectifier or grounding of rotor winding.

Detection: Use a harmonic analyzer to measure the harmonic content (total harmonic distortion THD) of the line voltage. Focus on the 3rd, 5th, and 7th harmonics.

handle:

If there is slight distortion (<15%) and the load is a regular motor, it can continue to operate.

If the distortion is severe, it is necessary to check whether the stator winding is damp or the inter turn insulation is damaged; High voltage megohmmeter can be used to test insulation.

For LX-G, you can try replacing the AVR to improve waveform feedback.

Mechanical and bearing failures

5.1 Overheating or abnormal noise of bearings

The LX series uses ball or roller bearings, and most models come with a re lubrication device (grease nozzle).

Abnormal noise: Bearing oil shortage, fatigue peeling, or damaged cage. Stop the machine and manually rotate the rotor to feel if there is any jamming or clicking sound.

Overheating: Excessive grease or model mismatch. High temperature lubricating grease of the specified grade (such as Shell Alvania 2, suitable for temperatures ranging from -25 ° C to+120 ° C) should be used, with a filling amount of 1/3 to 1/2 of the bearing chamber.

Maintenance cycle: Add lubricating grease every 2000 hours of operation or every six months; Replace bearings every 3-5 years or when abnormalities occur.

5.2 Excessive vibration

Reason: Poor coupling alignment, rotor dynamic balance failure, fan damage, or loose anchor bolts.

Diagnosis: Measure the horizontal/vertical vibration of the bearing position using a vibration meter (ISO 10816-3 standard). If the vibration exceeds 7.1mm/s (50Hz) or 7.5mm/s (60Hz), the machine needs to be shut down for maintenance.

Solution: Re check the alignment of the SAE adapter and coupling (allowable radial deviation ≤ 0.05mm, angle ≤ 0.1mm/m).


Insulation and environmental maintenance

6.1 Insulation level and temperature rise

The LX series standard insulation level is F level (allowing a temperature rise of 105K and a maximum operating temperature of 155 ° C). If there is long-term overload or poor ventilation, the insulation will accelerate aging.

Inspection: Use an infrared thermal imaging device to monitor the hotspots of the winding; Measure insulation resistance (with a 500V megohmmeter, not less than 5M Ω in cold state and not less than 1M Ω in hot state).

Prevention: Clean the ventilation openings (inlet/outlet hoods) of the casing every six months. LX-G and LX-E are self ventilated (IP20), ensuring free circulation of surrounding air.

6.2 High humidity, salt spray, and low temperature environments

Optional protective measures include:

Anti condensation heater: put into operation during long-term shutdown to prevent the winding from absorbing moisture.

Special treatment for coil wrapping (anti high humidity/salt spray): Used for seaside or chemical plants.

Low temperature measures (-5 ° C to -20 ° C): Replace the low-temperature grease, install a heater, and adjust the low-speed protection threshold of the AVR.

If there is no optional installation on site and the environment is harsh, the insulation resistance should be measured frequently. If it drops, hot air or low current heating should be used for dehumidification.


Overload and short circuit protection

7.1 Continuous overload capacity

The generator can withstand 1.5 times the rated current (cos φ not less than 0.8) for 30 seconds without damage. If frequent overload tripping occurs, the load calculation should be checked or the unit should be upgraded.

7.2 Unbalanced load capacity

Allow 20% negative sequence current (relative to rated current). Negative sequence current can cause rotor heating and vibration. When the three-phase voltage imbalance is greater than 5%, the load distribution or stator winding should be checked.

7.3 Short circuit current capability

LX-E and LX-H: 250% rated current for 2 seconds at 50Hz; 300% at 60Hz for 2 seconds.

LX-G: Does not have the ability to sustain short circuits.

Fault handling: If the generator cannot rebuild voltage after a short circuit, the possible reasons may be that the rotating rectifier is burnt out or the residual magnetism of the exciter disappears. A 12V battery can be used to instantly apply direct current (positive and negative polarity to be confirmed) to the stator of the exciter for magnetization.


Daily maintenance checklist

Every 100 hours of operation:

Check and clean the ventilation openings and heat sinks.

Check the insulation of the output cable and the torque of the connecting bolts.

Check the appearance of AVR and rotating rectifier for signs of overheating.

Every 250 hours or every month:

Measure the insulation resistance and record it.

Check the temperature and vibration of the bearings.

Test the voltage regulation range of AVR (rotate the voltage regulation potentiometer when unloaded and observe whether the voltage change is linear).

Every 2000 hours or year:

Replace the bearing grease (for models with oil injectors).

Calibrate the voltmeter, frequency meter, and protective relay.

Record the no-load and full load waveforms with an oscilloscope and establish a benchmark file.

Every 5 years or during major repairs:

Disassemble and inspect the stator winding ends and binding straps.

Check the diodes and varistors of the rotating rectifier.

Evaluate the magnetic properties of the PMG rotor (if it is LX-H).


Selection and Fault Prevention

If the on-site load contains a large number of frequency converters, UPS or rectifiers, LX-H should be preferred to avoid AVR loss of control due to harmonic waveguides.

If only conventional industrial motor loads are needed and the budget is limited, LX-G or LX-E are sufficient. However, it should be noted that LX-G cannot be used in situations where continuous short-circuit current is required (such as anti islanding protection in parallel with the power grid).

In high altitude (over 1000m) or high temperature (over 40 ° C) environments, it is necessary to reduce the capacity for use and consult the manufacturer for correction factors.

Parallel running generators must use AVR with droop or reactive power regulation function, and the LX series models of each unit should be consistent.

  • GE 151X1235DB15SA01 SPEEDTRONIC Mark VI High Performance Turbine Control Module
  • GE DS3800HIOC High-Level Input Output Board
  • GE DS3800NHVG High-Voltage Gate Driver Board
  • GE DS3800NB1A Power Supply Regulator Board
  • GE DS3815PAHB1A1A Processor Interface Board
  • Allen-Bradley 100-D300EA11 IEC Contactor 300A
  • Omron BY50S 500VA 300W Uninterruptible Power Supply
  • Mitsubishi NF630-CW 3P 600A Molded Case Circuit Breaker
  • CLA-2 4L PLC Control Electric Lubricating Oil Pump
  • Pilz 6Z000002 PSEN enc sincos 4096 hs Encoder
  • Siemens 6ES7317-2FK14-0AB0 CPU 317F-2PN/DP
  • Fuji NP1AYH8V-MR Analog Output Module MICREX-SX
  • Kistler DMF-P A300 NCF 4734AWDY2X400S1 Force Displacement Monitor
  • ABB Pluto S20 v2 CFS Safety PLC
  • Parker IQAN-XS2 Expansion Controller Module
  • ABB CI867AK01 PLC Module
  • FANUC A20B-2002-0520 Main Board
  • Mitsubishi A6BR10 Repeater Module
  • Siemens 3TY6480-0A Contact Kit
  • Servax CDD34.008 Servo Drive
  • Renesas R5F2134CXJFP Microcontroller
  • Siemens 6SL3210-1SE31-0AA0 Power Module
  • Mitsubishi LE-40MTA-E Tension Controller
  • B&R 4PP035.0300-01 Operation Panel
  • HRTL 96B M666.01S-S12 Inductive Proximity Sensor
  • Mitsubishi GT1455HS-QTBDE GOT1000 Touch Screen
  • Braids PLC-24/30/E2UK 25m PLC Connection Cable
  • Omron NX-PD7001 NX Series Power Supply Unit
  • Pro-face FP3900-T41-U PFXFP3900TA Operating Panel
  • Siemens 6GK5204-2BB10-2AA3 Industrial Ethernet Switch
  • Mitsubishi GT2310-VTBA GT2310-VTBD Graphic Operation Panel
  • PILZ 774400 PNOZ 24VDC 2NO 2NC Safety Relay
  • Siemens 6ES7315-2EH14-0AB0 CPU 315-2 PN/DP
  • ABB PLUTO B42 AS-i Safety Relay 2TLA020070R1400
  • Applied Materials 0010-12123 PLC Controller
  • Pilz 774595 PZE X5 Safety Relay
  • Siemens 6GA2 490-0A AVR
  • Keyence KV-10T Micro PLC
  • Siemens 6ES7331-7PF01-0AB0 Analog Input
  • Siemens 6SN1145-1BA02-0CA1 PLC
  • FANUC A16B-3200-0521 Main Board
  • Siemens 6SL3120-2TE21-0AD0 Motor Module
  • Pilz 828010 S1IM Safety Relay
  • TRICONEX 3601E Digital Output
  • TRICONEX 8312 Power Module
  • TRICONEX MA2211-100 Media Adapter
  • TRICONEX 3720 Analog Input Module
  • TRICONEX 7400213-100 Extender Module
  • TRICONEX 3000602-100 Chassis Assembly
  • TRICONEX 3722X Analog Input Module
  • Triconex 7400322-100 Trident CIM Base Plate
  • TRICONEX 3721 Analog Input Module
  • TRICONEX 3005 Processor Module
  • ABB 3BUS208720-001 Industrial Power Signal Interconnection Module
  • TMEIC KPAD-3122A LCD Display Keypad
  • Siemens 6SN1145-1BA02-0CA1 PLC
  • LAM 2004365 TURBO BYPASS PLC ASM
  • Omron CJ1W-CORT21 PLC Module
  • Euchner MGB-L2B-PNA-L-121853 Safety Switch
  • XPSMC32ZP Safety Controller
  • Schneider 9070T3000D33 PLC
  • Omron C200H-MAD01 AD DA Module
  • Omron NJ501-1320 CPU Controller
  • Honeywell C36TR1UA1000 Thermostat
  • Honeywell TC-RPDXX1 Power Supply Module
  • Fuji NW0E32-3 PLC Programmable Controller
  • ASM 2004219 Turbo Bypass ASM 107864 Module
  • Future IHDW-BLA4S-IM CNC MPG Handwheel
  • Wieland R1.180.0080.0 SA-OR-S1-4RK-A Safety Module
  • Reliance Electric 57C493 AutoMax Power Supply 376W
  • Siemens 3VT8563-2AA03-2KA2 MCCB 3VT8
  • B&R X20IF1072 CAN Bus Interface Module
  • Mitsubishi OSE253S2 Rotary Encoder
  • Mitsubishi NV630-SW 4P 500A Earth Leakage Breaker
  • Euchner MGB-L1B-PNA-R-121857 Safety Switch
  • Honeywell 900A01-0102 Analog Input Module
  • OMRON C500-ID219 Input Unit
  • Westinghouse EL3030R Current Limiter
  • CLA-2 3L Electric Lubrication Pump
  • Proface GP2501-TC41-24V HMI
  • Omron KM-N1-FLK Small Power Monitor
  • HPM 1D703-0040 Command 9000 Console Card
  • Siemens 3RW5074-6AB14 SIRIUS Soft Starter
  • Genie 75032 Limit Switch
  • OMRON C200H-SP001 Space Module
  • OMRON C200H-PS211 Power Supply Unit
  • OMRON C200H-OC222 Relay Output Unit
  • Keyence KV-8000SO 4221 CPU Module
  • Cincinnati Milacron 3-542-1079A Circuit Board
  • Beckhoff EL3124 Analog Input EtherCAT Terminal
  • KRONES BWU1703 0900853537 ASi PROFIBUS Gateway
  • Radio Energie RE0444 R1S 0.06 CA Tachogenerator
  • Mitsubishi GT1685M-STBA GOT1000 HMI
  • Siemens 6GK7342-5DA03-0XE0 CP 342-5 PROFIBUS
  • Allen Bradley 8520-PX-ASM3-EXEC2-63M Servo Module
  • Delta AH10PM-5A Programmable Controller
  • Siemens 3TK2805-0BB4 Safety Contactor Combination
  • EUCHNER HBA-079827 Pendant Station
  • CLC-2 4L PLC Lubrication Pump
  • KEYENCE GS-51P5 Safety Switch
  • AB 442G-MABH-R Safety Switch
  • GE Fanuc VersaMax PLC Module Set
  • Siemens 6ES7214-1HF40-0XB0 CPU 1214FC
  • Microchip DSPIC30F4011-30I/P DSC
  • FANUC A20B-2102-0081 I/O Link Module
  • Endress Hauser CLS15-B1M2A Conductivity Sensor
  • B&R 3AM050.6 Analog I/O Module
  • Fanuc A16B-2201-0320 MAIN-B CPU Board
  • Pilz 475650 PNOZ 1 Safety Gate Relay
  • Omron NSH5-AL001 Handheld HMI Terminal
  • Allen-Bradley 1756-OF8 Analog Output 8 Ch
  • Siemens 6SL3210-1SE31-0AA0 45kW Power Module
  • PMA TB45-110-00000-000 Temperature Limiter
  • PSR-SCP-24DC-ESD-5x1-1x2-300 Safety Relay
  • Pilz 774140 PZE 9 24V AC Safety Relay
  • Telemecanique TSXRKN82F 8 Slot Rack
  • Mitsubishi R16CPU iQ-R PLC CPU
  • Mitsubishi A2ACPU-R21-S1 PLC CPU
  • Omron NX-AD4208 Analog Input Unit
  • Schneider LMC802CAA10000 PacDrive 3 Controller
  • Reliance Electric 0-51874 Static Sequence Card
  • Pilz 787310 PNOZ X3P C Safety Relay
  • B&R X20CP1684 CPU Module
  • Siemens 6SN1145-1BB00-0FA1 Power Module
  • Beckhoff EL3174 Analog Input EtherCAT Terminal
  • CLC-2P 4L PLC Lubrication Pump System
  • Omron CJ1W-DA08C Analog Output Unit
  • Metso Automation D201776 ACN PO DC PLC Control Server Computer