Welcome to the Industrial Automation website!

NameDescriptionContent
XING-Automation
E-mail  
Password  
  
Forgot password?
  Register
当前位置:

MITSUBISHI A-series PLC Troubleshooting Replacement

F: | Au:FANS | DA:2026-05-28 | 18 Br: | 🔊 点击朗读正文 ❚❚ | Share:

MITSUBISHI MELSEC A-series PLC: Complete Guide to Replacing and Troubleshooting Discontinued Controllers

In the field of industrial automation, Mitsubishi MELSEC A-series (especially AnS series) programmable controllers have long occupied an important position in medium-sized control systems due to their compact structure, high reliability, and rich I/O expansion capabilities. However, as the product lifecycle changes, many A-series models (such as A1SHCPU, A2SHCPU, etc.) have gradually been discontinued, making it difficult to obtain spare parts. When the old controller in the on-site equipment malfunctions or requires functional upgrades, engineers face two major challenges: how to seamlessly replace it with existing or alternative models while ensuring safety and performance; And how to quickly diagnose and eliminate various errors that occur during operation. This article combines the core content of the A-series hardware manual, providing a systematic engineering solution from installation specifications, EMC compliance, wiring points, fault safety design to common error code analysis.


Product Overview and Key Points for Replacement Selection

The MELSEC AnS series includes multiple sub series such as A1S, A2S, A1SH, A2SH, etc. Its CPU module, power module, I/O module, and expansion substrate all adopt a unified structure. When replacing, the following points should be noted:

CPU performance difference: The processing speed of A1SH CPU is 0.33 μ s/step, much faster than A1SCPU's 1 μ s; A2SHCPU is also faster than A2SCPU. If the original system is sensitive to scanning time during replacement, a CPU of the same level or higher performance should be selected.

I/O points: The maximum actual I/O points for A1SHCPU are 256 points, A2SHCPU are 512 points, while A1SCPU only has 256/512 points. When replacing, it is necessary to confirm whether the I/O capacity of the new CPU meets the existing configuration.

File register capacity: A1SHCPU supports a maximum of 8192 points (R0~8191), while A1SCPU only has 4096 points. If the original program uses a large number of file registers, a larger capacity CPU should be selected.

CC Link specific instructions: A1SHCPU and A2SHCPU support 11 CC Link specific instructions (such as RLPA, RRPA, RIRD, etc.), while early A1SCPU did not support them. If a CC Link network has been deployed on site, a CPU with the suffix "H" or A2ASCPU series must be selected.

Memory card compatibility: There are compatibility differences between traditional memory (such as A1SNMCA-2KE) and new models (such as A1SNMCA-2KE), as detailed in Appendix 1 and 2.


Environment and mechanical installation: avoid "hidden" failure

1. Environmental specification requirements

According to Chapter 1 of the manual, A-series PLCs must be installed in the following environment:

Working temperature: 0~55 ℃ (temperature inside the control cabinet)

Storage temperature: -20~75 ℃

Humidity: 10~90% RH, no condensation

Anti vibration: Complies with JIS B 3501 (10~57Hz: amplitude 0.075mm; 57~150Hz: 4.9m/s ²)

Impact resistance: 147m/s ² (15G), 3 times in each of the X/Y/Z directions

Altitude: ≤ 2000m

Pollution level: ≤ 2 (inside the control cabinet, IP54 protection level)

Installation location: inside the control cabinet (open equipment)

Key reminder: If the on-site environment is humid or there is conductive dust, the PLC must be installed in a closed control cabinet with a protection level of not less than IP54, otherwise the insulation performance may decrease and cause short circuits or misoperations.

2. Dimensions and spacing for substrate installation

Substrate mounting hole spacing: Depending on the model, the width ranges from 155mm (A1S52B) to 430mm (A1S38B), and the height is uniformly 130mm.

Heat dissipation gap: Leave at least 30mm (1.18 inches) between the top and bottom of the module and the cabinet or other components. If using A5 | B or A6 | B expansion substrate, the gap must be ≥ 80mm.

Left and right clearance: at least 50mm between the device that generates noise (such as contactors, frequency converters).

Installation direction: It must be installed horizontally (face up), and it is strictly prohibited to install vertically or upside down, otherwise it will affect heat dissipation.

3. Substrate fixation and DIN rail installation

Secure with M4 screws, tightening torque: 78~118 N · cm (8~12 kg · cm). Attention: Screws that are too long may damage the internal circuit board.

If using DIN rails (TH35-7.5Fe/TH35-7.5Al/TH35-15Fe), the spacing between the rail mounting screws should be ≤ 200mm to prevent deformation.

Practical lesson: In a certain automotive parts production line, A2SHCPU frequently experiences "WDT ERROR" (watchdog timeout). Upon inspection, it was found that the substrate was installed next to a highly vibrating compressor and the fixing screws were loose. After re reinforcing and adding vibration damping pads, the fault disappeared.


EMC compliant installation: key measures to meet CE certification

To comply with the EU EMC Directive (89/336/EEC), A-series PLCs need to be installed according to the following requirements:

1. Control cabinet processing

Use conductive metal cabinets to maintain good electrical contact between panels (remove paint).

Flat braided wires are used to connect multiple points between the cabinet door and the main body, reducing high-frequency impedance.

The cross-sectional area of the cabinet grounding wire should be ≥ 22mm ², and the length should be as short as possible.

Cabinet opening diameter ≤ 10cm to prevent high-frequency noise radiation.

2. Connection between power supply and grounding wire

Set up a grounding point near the power module and connect the LG and FG terminals with the shortest wire (≤ 30cm).

For A1S61P/A1S62P/A1S63P, a noise filter needs to be installed at the input end (recommended SCHAFFNER FN343-3/01 or TDK ZHC2203-11).

For CE compatible models (A1S61PEU, A1S62PEU, A1S61PN, A1S62PN), no external filter is required, but LG and FG must be short circuited (unless otherwise specified).

Twist the power cord and ground wire together to enhance common mode noise discharge.

3. Signal cable shielding

All I/O signal lines and communication lines (RS-232C, RS-422, etc.) leading out of the control cabinet must use shielded cables.

The shielding layer contacts the cabinet grounding through a large area of metal clips (welding leads cannot be used due to high high-frequency impedance).

For MELSECNET/II modules (such as A1SJ71AR21), a three coaxial cable must be used and a ferrite magnetic ring (TDK ZCAT3035 is recommended) must be installed at the cable outlet.

The AUI cable of Ethernet module A1SJ71E71-B5 needs to be stripped of insulation and grounded extensively.

Attention: If shielded cables are not used or shielded grounding is poor, the immunity will decrease from 2kV (IEC801-4) to below 1kV, which may cause false signals.

Selection and replacement of power module and I/O module

1. Power module replacement guide

Prototype Number Recommended Replacement (CE Compatible) Remarks

A1S61P (100-120VAC) A1S61PN (100-240VAC) 5V/5A output, requires an external filter

A1S62P (200-240VAC) A1S62PN (100-240VAC) 5V/3A + 24V/0.6A

A1S63P (24VDC input) without CE compatibility model requires external SELV power supply

Replacement precautions:

Overcurrent protection: When the 5V output current exceeds 5.5A (A1S61P) or 3.3A (A1S62P), the power module will automatically turn off the output and turn off the LED. At this point, the load short circuit must be eliminated before power can be restored.

Overvoltage protection: If the 5V voltage rises to 5.5-6.5V, the protection will activate. Power off and then power on to reset. If it still cannot be restored, replace the power module.

Allowable instantaneous power down time: A1S63P is about 20ms under 24VDC input; A1S61P/A1S62P is over 20ms under AC input.

2. Key points for replacing input modules

The rated voltage of AC input modules (such as A1SX10, A1SX20) is 100-120VAC or 200-240VAC. It should be noted that CE compatible models (such as A1SX10EU, A1SX20EU) have a dielectric strength of 1780VAC and the same operating temperature range.

DC input modules (such as A1SX40, A1SX41, A1SX80, etc.) support 12/24VDC, input current 3-7mA, and response time is usually 10ms (high-speed models such as A1SX42 can reach 0.1ms). Attention should be paid when replacing:

Source/Drain Type: The A1SX80 series supports both sink and source connections, while the A1SX40 only supports the sink type.

Response speed: If the original system uses high-speed counting (such as encoder signals), a model with a response time of ≤ 0.2ms (such as A1SX42) must be selected, otherwise pulses will be lost.

3. Output module replacement

Relay output (A1SY10, A1SY14, A1SY18A): Contact capacity 240VAC/24VDC, 2A/point, 8A/common terminal. When replacing, pay attention to the higher dielectric strength (2830VAC) of CE compatible models (A1SY10EU, A1SY14EU, A1SY18AEU). The lifespan of the relay is 20 million mechanical cycles and 100000 electrical cycles (rated load).

Controllable silicon output (A1SY22, A1SY28A): suitable for AC loads, with a response time of approximately 1ms+0.5 cycles. When replacing, pay attention to the load current (0.6A/point, 2.4A/common terminal).

Transistor outputs (A1SY40, A1SY41, A1SY42, etc.): used for DC loads, with a response time of 2ms, and some high-speed types (such as A1SY71) can reach 2ms. Special attention should be paid to:

Output current: A1SY40 is 0.1A/point, A1SY42 is 0.5A/point, A1SY50 is 2A/point. When replacing, be sure to check the original load current to avoid overloading and burning out.

Surge suppression: The transistor output is internally integrated with a Zener diode, but for inductive loads, it is still recommended to use an external parallel freewheeling diode.

Fuse: Most transistor output modules do not come with fuses and require external installation (fast melting is recommended).


Code of practice for electrical wiring

1. Power wiring

Connect the live wire (L) and neutral wire (N) of the AC power supply to the corresponding terminals of the power module. LG is functional grounding, FG is protective grounding. FG must be connected to the grounding bar of the control cabinet.

For A1S63P (24VDC input), an external power supply that complies with SELV (Safety Extra Low Voltage) must be used, with the 24V positive pole connected to "24V" and the negative pole connected to "COM".

It is strictly prohibited to parallel the outputs of multiple power modules to the same I/O module for power supply, otherwise it may cause module heating or even fire.

2. Input module wiring

For DC input modules, the common terminal can be connected to the positive or negative pole to achieve source or drain type. For example, when the COM of A1SX40-S1 is connected to 0V, the input terminal is connected to 24V effectively (source type).

To improve anti-interference, the input signal line should be laid separately from the power line, with a spacing of ≥ 100mm. If necessary, shielded cables should be used, and the shielding layer should be grounded at one end.

For the communication input module (A1SX10EU), attention should be paid to the power supply frequency of 50/60Hz, input current of 6mA, and minimum ON voltage of 80VAC.

3. Wiring of output module

The common terminal (COM) of the relay output module can be connected to AC or DC power supply, but it must be consistent with the power supply of the load. Inductive loads must be connected in parallel with RC absorption circuits (AC) or freewheeling diodes (DC).

The "external power" terminal of the transistor output module must be connected to 24VDC, otherwise the output cannot conduct. The manual clearly requires' SELV power required '.

When driving incandescent lamps or capacitive loads, the impulse current may reach 10 times the rated value and needs to be reduced for use.

4. Communication wiring (A1SCPUC24-R2)

The RS-232C interface adopts a 9-pin D-sub male connector, with pin definitions of 2-RD, 3-SD, 5-SG, 7-RS, and 8-CS. Cable length ≤ 15m, it is recommended to use 7/0.127mm shielded twisted pair.

If the external device cannot provide the CD signal (pin 1), the RS232C CD terminal with buffer address 10BH needs to be checked as "not executed" in the program.

Self loop test: Short circuit 2-3 and 7-8 to verify if the interface hardware is functioning properly.

Fault safety circuit design

According to Chapter 5 of the manual, a safety circuit must be constructed outside the PLC to prevent danger caused by power failure or PLC hardware failure.

1. Essential external circuits

Emergency stop circuit (hard wired, not through PLC).

Positive and reverse interlock (contactor electrical interlock).

Hardware travel switch for upper/lower limit positioning control.

Output module monitoring circuit: For a single output point that may cause serious accidents (such as a motor contactor), an external relay should be connected in parallel, and its contacts should be connected to the PLC input for program monitoring of its status.

2. Power sequence control

To avoid accidental output during power on, the following sequence is recommended:

First, power the PLC.

Provide external load power supply (such as the load power supply of 24V output module).

After a delay of 0.5 seconds through the PLC program, connect the main contactor (MC) and allow the output action.

The specific example circuit is shown in Figure 5.2 (pages 5-2 of the manual). For the DC output module, voltage relay RA2 can be used to detect the establishment of the load power supply, and then a timer can be used to delay the connection of MC.

3. Safety status in case of PLC failure

When the PLC detects the following faults, all outputs will be turned off:

Power module overcurrent/overvoltage protection action.

CPU watchdog timer timeout (WDT ERROR).

Program execution error (such as instruction code error, no END instruction).

But for faults that the CPU cannot detect (such as I/O control bus damage), the output may randomly remain ON or OFF. At this point, it is necessary to rely on external safety circuits (such as the monitoring circuit or safety relay mentioned above) to cut off the hazard source.


Common error codes and troubleshooting

Based on the error code table in Chapter 7 of the manual, the most common errors and their handling methods on site are extracted.

1. Instruction code error (INSTRUCT CODE ERR., error code 10)

Phenomenon: CPU stops, ERROR LED stays on.

Possible reasons:

The memory contains instruction codes that the CPU cannot decode (such as damaged ROM or downloaded incompatible programs).

Noise causes changes in memory content.

Exclusion steps:

Read the wrong step with a programmer and check if the instruction for that step is valid.

If using an EPROM memory card, reprogram the correct program.

If it occurs frequently, check the grounding and power filtering.

2. Parameter Error (Error Code 11)

Phenomenon: CPU stops.

Possible reasons: Parameter settings exceed the CPU range (such as incorrect program capacity or file register capacity settings) or the total exceeds the memory card capacity.

Solution: Use peripheral devices to read parameters, reset and write them.

3. Missing END INS instruction (Error code 12)

Phenomenon: CPU stops.

Reason: There is no END (or FEND) instruction at the end of the program.

Solution: Write the END instruction at the end of the program.

4. Watchdog timer error (WDT ERROR, error code 22)

Phenomenon: CPU stops or ERROR flashes during RUN.

Reason:

The scanning time of the user program exceeds the set watchdog time (default 200ms).

Transient power failure occurred during scanning, resulting in a false increase in scanning time.

solve:

Check if there is an infinite loop or excessively long sequence in the program, and use the CJ instruction to jump to unrelated segments.

Monitor special register D9005. If it is not 0, it indicates power fluctuation and the power supply line needs to be checked.

The watchdog setting value can be appropriately extended (through parameter settings).

5. Fuse Break OFF (error code 32)

Phenomenon: The CPU continues to run (RUN state), but the ERR LED of the corresponding output module lights up.

Reason: The internal fuse of the output module is blown (usually due to a short circuit of the output load).

solve:

Observe the fuse indicator LED on the output module panel and replace it with a fuse of the same specification.

Read the special registers D9100~D9107 through peripheral devices to identify which module (bit 1) is specific.

6. Unit verification error (UNIT VERITY ERR., error code 31)

Phenomenon: CPU stops.

Reason: The configuration of the I/O module after power on is inconsistent with the actual module currently inserted (for example, someone unplugged and plugged in the module).

Solution: Check the special registers D9116~D9123, and the module corresponding to bit 1 has changed. Re plug or replace it.

7. Battery Error (BATTERY ERROR, error code 70)

Phenomenon: The ERROR LED flashes while the CPU is running, or an alarm is triggered when powered on.

Reason: Low battery voltage or disconnected battery.

Solution: Immediately replace the battery (model A6BAT). Before replacement, ensure that the PLC is powered on (or connected to an external power source through the programming port) to prevent program loss. Reset the "low battery" flag in the parameters after replacement.

8. Special module layout error (SP. UNIT LAY. ERR., error code 44)

Phenomenon: CPU stops.

Possible reasons:

Installed 3 or more computer link modules (up to a maximum of 2).

Installed 2 or more MELSECNET modules.

The I/O allocation in the parameters does not match the actual module type (such as setting a special module as a regular I/O).

Solution: Reduce the number of modules or correct parameter allocation.


Maintenance and battery replacement

1. Daily inspection items (recommended for each shift)

Power LED, RUN LED, ERROR LED status.

The input/output LED is consistent with the actual device status.

No abnormal noise or odor.

2. Regular inspections (every 6-12 months)

Environmental temperature and humidity (0-55 ℃, 10-90% RH).

Check if the wiring terminals are loose (torque check).

Internal dust accumulation (cleaned with a vacuum cleaner).

Battery voltage status: Monitor special relays M9006 (low battery voltage warning) and M9007 (low battery voltage error). If M9006 is ON, replacement should be arranged.

3. Battery replacement steps

Ensure that the PLC power is turned on (at least 1 minute).

Open the front panel of the CPU and unplug the old battery connector.

Insert a new battery (A6BAT), pay attention to polarity.

Close the panel. After replacement, M9006/M9007 should be reset.

If it needs to be replaced in a power-off state, it must be completed within 5 minutes, otherwise the program will be lost (backup is required in advance).

  • Keyence LJ-V7000 Controller Laser Profiler
  • Siemens 6EP3437-8SB00-0AY0 Power Supply 20A
  • Pasaban MC-2006 03 CAN Bus PLC Card
  • ETAS ES600.2 PLC Module Prototyping
  • ABB ACS800-01-0005-3+P901 Frequency Converter
  • Omron NX102-1100 PLC Module Machine Automation
  • Square D BMXCPS3500 PLC Power Supply Module
  • Allen-Bradley 96657704 Fiber Optic Converter 1771-AF
  • Corcom 20VK1 Power Line Filter
  • Novellus 2805-11407 PLC Rack Assembly
  • Sick RLY3-EMSS100 Safety Relay Module
  • Microchip PIC12F508-I/P Microcontroller
  • Fanuc A02B-0098-B511 Motherboard
  • Merlin Gerin PB80 PLC Rack Module
  • ABB Pluto S20 V2 CFS Safety PLC
  • Honeywell TK-PRR021 Redundancy Module
  • B&R 7XX419L.50-1 Bus Controller
  • Mitsubishi NV400-SW 3P 300A Breaker
  • B&R X20AT2222 Temperature Module
  • Corcom 20VK1 EMI RFI Filter
  • Novellus 2805-11407 PLC Rack Assy
  • Mitsubishi FXAOM01BD Analog Output Module 4CH
  • NORIS A1-91 PCB Rack Module A1-91-4 A1-91-5 A1-91-6 A1-91-7 A1-91-8
  • Omron ZFV-SC50 Smart Camera Vision Sensor
  • Schneider Electric EOCR-PMZ Motor Protection Relay
  • B&R X20 SO 6300 PLC Module Safety Output
  • Mitsubishi A2ACPU21-S1 CPU Module MELSEC
  • Siemens 6ES7405-0KA02-0AA0 PS405 10A Power Supply
  • Samsung PVU-2424 Power Supply Unit DC24V 24W
  • ATTO controlSYS ATT0-CPU44 PLC with Display
  • Lenze EPZ-10203 CANPT010W3E Absolute Encoder
  • GE IS215WEMAH1A+IS210BPPBH2CAA Mark VIe Embedded Processor and Backplane Power Distribution Board
  • GE IS215AEPAH1CH+IS210BPPBH2CAA Mark VIe Application Processor and Backplane Power Distribution Board
  • GE IS215WECAH1B+IS210BPPBH2CAA Mark VIe Control Platform
  • GE PCM Regulator for EX2100e Power Conversion Module 151X1235DB15SA1
  • Lenze ECSEA048C4B servo drive
  • ABB PM665 3BDS005799R1 redundant CPU module
  • BAUMULLER b maXX 3000 Servo Controller BM3401-LIFBO-ACOOOCB-G-02-O-02
  • R&S EPL10200-W EMI Test Receiver
  • Schneider M522220000 16 way relay output module
  • ABB 3HAC031851-001 SMB Unit Technical Manual
  • Fuji NB1U56X-01 Programmable Controller Guide
  • Siemens 6AG1153-2BA02-7XB0 SIPLUS IM 153-2 Manual
  • Beckhoff EL6631 PROFINET Terminal Manual
  • Lenze E82EV302-4C Frequency Inverter Manual
  • Siemens 6SE7038-6EK84-1JC2 IGD8 Board Specifications
  • Pilz 774595 Safety Relay Specifications
  • Fanuc A20B-8200-0847 PLC Board Specification
  • Allen Bradley 1785-L60B/E PLC CPU Manual
  • PASABAN MC-2006 03 PLC Card Specifications
  • B&R X20CP1382 PLC Control Module X20 CPU
  • B&R X20DC2395 PLC Module Digital Output
  • AS-2P-70M-B Industrial PLC Communication Cable 70M
  • Siemens 6ES7136-6BA00-0CA0 PLC Module ET 200SP
  • Siemens 1FK7083-5AF71-1EB3 Servo Motor SIMOTICS S
  • WAGO 750 Series I/O Modules 750-842 750-530 750-430 750-602 750-514 750-600
  • Microchip TC9401CPD F/V Converter 100kHz 14DIP
  • Mitsubishi GT2310-VTBA GT2310-VTBD HMI Touch Screen 10.4 Inch
  • Siemens 3RT2036-1AN20 AC Contactor SIRIUS
  • Mitsubishi GT2708 HMI Touch Screen GT2708-VTBA VTBD STBA STBD
  • Siemens 6FC5110-0CB01-0AA0 CNC PLC CPU
  • ABB SINT4130C PCB Board
  • Omron NX1P2-1040DT PLC Controller
  • Fuji FRN3.7C1S-2J VFD
  • PLC-60/75 /E2UK Shielded Braided Cable
  • Omron CJ1W-NC434 Position Control Unit
  • Omron NX-AD2208 Analog Input Module
  • PASABAN MC-2006 03 PLC Card
  • Schneider 9038CR34 Pressure Switch
  • Pilz 240340 Safety Control Module
  • Mitsubishi A2NCPU Programmable Controller MELSEC
  • Mitsubishi Alpha XL Alarm Modem M20 Expansion
  • AutomationDirect D0-06DD2-D PLC DL06 Controller
  • Toshiba COMW01-21 PCB Control Board Turbine
  • Siemens 6FX1122-1AC02 Coupling Module SINUMERIK
  • Omron CVM1-CPU21-V2 CPU Unit Programmable
  • Beckhoff EL7041 Stepper Motor Terminal EtherCAT
  • B&R X20AI4622 Analog Input Module 4 Channels
  • OAT PMC25.2-003 Programmable Controller Module
  • Fanuc A16B-2200-0350 Graphic Board Series 16
  • Eaton Cutler Hammer 6-26-2 Contactor Contact Kit
  • Omron D4SL-NSK10-LK-K Safety Switch
  • Siemens C98043-A7001-L24 CUD1 Control Board
  • Mitsubishi A2NCPUR21-S1 PLC Module
  • National Instruments NI-9242 4-channel analog input module
  • BEMAC UST-202-D PLC Interface Board
  • Omron CJ1W-DA08C Analog Output Module
  • Mitsubishi QX521 CNC Interface Board
  • Schneider BMEP586040 High-Performance PLC Processor
  • Emerson 5X00875G01 Process Control PLC
  • Siemens SIMODRIVE 611 Power Module 6SN1145-1AA01-0AA0
  • Siemens 840C NC-CPU 486DX4 6FC5110-0BB04-0AA1
  • Mitsubishi GT2708 Series Operation Panel Touch HMI
  • Fanuc A04B-0103-C220 Programmable Controller Module
  • IFM CR2530 Programmable Controller for Mobile Automation
  • Omron FH-3050 Vision Controller i7-2715QE High Performance
  • National Instruments NI-9242 4-Ch Analog Input Module
  • B&R X20AI4632 Analog Input Module 4 Channels
  • Pilz 773600 Input Module Safety Automation
  • Panasonic AFPX-C60P Programmable Controller PLC
  • Siemens 6ES7414-2XL07-0AB0 S7-400 CPU Manual
  • Cutler Hammer WM34V Interlock Kit Manual
  • Pilz 777587 Safety Relay Specifications
  • Omron CJ2H-CPU64-EIP CPU Module Manual
  • B&R X20AI1744-3 Analog Input Module Guide
  • Schneider LC1G185BEEA Contactor Specification
  • Sharp LM64P101 LCD Screen Specifications
  • B&R X20AT4222 Temperature Module Guide
  • Mitsubishi A2UCPU-S1 Controller Specifications
  • Stein Sohn E 083.1 Rack Module Technical Guide
  • Omron CK3W-AX1515N Motion Controller
  • Schneider TSXP572634M PLC Processor
  • Epson RAIOC-33 Programmable Controller
  • GRID T&D iRTUe-D1R1-W.125 I/O Module
  • Fanuc A20B-2002-0520 Control Board
  • B&R X20IF1030 Interface Module
  • Schneider ATV320U55N4B VFD
  • Omron NA5-9W001B-V1 HMI Touchscreen
  • Mitsubishi A2NCPU PLC CPU Unit
  • Omron CJ2M-CPU34 PLC CPU Unit
  • Omron NS12-TS01B-V2 Touch Screen HMI
  • Mitsubishi FX3GE-24MT/ESS PLC Controller
  • Grundig NEA02 AES 0 PLC I O Module
  • Beckhoff EP3204-0002 EtherCAT Box Module
  • Mitsubishi MDS-A-CV-220 Power Supply Unit
  • MCX20B2 080G0330 Motion Controller
  • Toyo Keiki P CARD5 Interface Board YH-212
  • National Instruments NI 9242 Analog Input Module