ABB REF 610 Protection Relay
ABB REF 610 Protection Relay
INTRODUCTION
REF 610 is a versatile multifunction protection relay mainly designed for protection of incoming and outgoing feeders in MV distribution substations. REF 610 can also be used as back-up protection for motors, transformers and generators, in industrial as well as in utility applications.The large number of integrated protection functions, including three-element overcurrent protection, two-element, non-directional ground-fault protection as well as thermal protection, makes REF 610 a complete protection against overcurrent and ground faults.
FEATURES
ï Three-phase non-directional overcurrent protection with definite-time or IDMT (mode) characteristic, low-set element
ï Three-phase non-directional overcurrent protection with definite-time or instantaneous characteristic, high-set element
ï Three-phase non-directional overcurrent protection with definite-time or instantaneous characteristic, instantaneous element
ï Non-directional ground fault protection with definite-time, IDMT (mode) or instantaneous characteristic, low-set element
ï Non-directional ground-fault protection with definite-time or instantaneous characteristic, high-set element
ï Three-phase thermal overload protection for cables
ï Arc protection - two lens sensors for arc detection (optional) - automatic reference level adjustment based on backlight intensity
- arc detection via a remote light signal
ï Automatic reclosing 1...3 shots
ï Circuit-breaker failure protection
ï Trip counters for circuit-breaker condition monitoring
ï Trip-circuit supervision with possibility to route the warning signal to a signal output
ï Trip lockout function
ï Four accurate current inputs
ï User-selectable rated frequency 50/60 Hz
ï Three normally open power output contacts
ï Two change-over signal output contacts and three additional change-over signal output contacts on the optional I/O module
ï Output contact functions freely configurable for desired operation
ï Two galvanically isolated digital inputs and three additional galvanically isolated digital inputs on the optional I/O module
ï Disturbance recorder
- recording time up to 80 seconds
- triggering by one or several internal or digital input signals
- records four analog channels and up to eight user
-selectable digital channels
- adjustable sampling rate
ï Non-volatile memory for
- up to 100 event codes with time stamp
- setting values
- disturbance recorder data
- recorded data of the five last events with time stamp
- number of AR shots and pickups/trips for protection elements
- target messages and LEDs showing the status at the moment of power failure
ï HMI with an alphanumeric LCD and manoeuvring buttons
- eight programmable LEDs
ï Multi-language support
ï User-selectable password protection for the HMI
ï Display of primary current values
ï Demand values
ï All settings can be modified with a PC
ï Optical front communication connection: wirelessly or via cable
ï Optional rear communication module with plastic fibre-optic, combined fibre-optic (plastic and glass) or RS-485 connection for system communication using the SPA-bus, IEC 60870-5-103 or Modbus (RTU and ASCII) communication protocol
ï Optional DNP 3.0 rear communication module with RS-485 connection for system communication using the DNP 3.0 communication protocol.
ï Battery back-up for real-time clock
ï Battery charge supervision
ï Continuous self-supervision of electronics and software.