CC-PAOH01/51 with HART protocol 16 4-20mA support FAILOPT (maintain last value/switch to safe value), open circuit detection, accuracy ± 0.35% of full range at 25 ℃
CC-PAOX01/PAON01 without HART protocol 16 4-20mA and with HART module parameters consistent, without HART communication function, maximum load 800 Ω (24V power supply)
5. Digital Input Module (DI)
Receive discrete voltage signals, adapt to different voltage levels, and partially support sequence of events (SOE) recording.
Module model, voltage level, channel number, key characteristics
CC-PDIL01/51 24VDC 32 CC-PDIL01 supports open circuit detection and isolation voltage of 1500VAC; CC-PDIL51 has no open circuit detection and is isolated from 1000VAC
CC-PBIS01 24VDC 32 supports SOE (1ms resolution), three scanning modes (normal 20ms/fast 5ms/SOE mode)
CC-PDIH01 high voltage (110VAC/220VAC/125VDC) 32 is compatible with different high voltage signals, and can switch voltage types by replacing IOTA, reducing the variety of spare parts
6. Digital Output Module (DO)
Output discrete signals to control external devices (such as solenoid valves, intermediate relays), with short-circuit protection and fault safety configuration.
Module model, output type, number of channels, key characteristics
CC-PDOB01 24VDC bus type (source output) 32 no fuse short circuit protection, supports FAILOPT, maximum 0.5A per channel, maximum 6A per module
CC-PDOB01 (relay IOTA) dry contact (NO/NC configurable) 32 with CC-TDOR01/11 IOTA, maximum contact 250VAC/125VDC, mechanical life 5 million times
CC-PDOD51 24VDC current output with 32 coating protection, maximum 0.1A per channel, isolation voltage 1000VAC
7. Universal Input/Output Module (UIO)
Single module supports multiple types of signal configurations, with high flexibility and adaptability to complex mixed signal scenarios.
Module model, channel number, configurable type, key characteristics
CC-PUIO01 32 AI/AO/DI/DO/pulse input (15-18 channels) supports HART 7, -40 to+70 ℃ working temperature, electronic short circuit protection
CC-PUIO31 32 AI/AO/DI/DO/SOE/pulse input (any 4-channel) HART channel independent modem, SOE 1ms resolution, pulse frequency 0-15kHz

IOTA size and compatibility configuration
The size of IOTA varies with module type (analog/digital) and redundancy requirements. Non redundant configurations have smaller sizes, while redundant configurations require longer IOTA. The specific adaptation relationship is as follows (excerpt from core combinations):
IOM type non redundant IOTA model non redundant size (inches) redundant IOTA model redundant size (inches) number of channels
Analog Input (AI) CC-TAIX01 6 CC-TAIX11 12 16
Temperature input (LLMUX) CC-TAIM01 6-64 (FTA required)
Pulse Input (PI) - CC-TPIX11 12 8
Analog Output (AO) CC-TAOX01 6 CC-TAOX11 12 16
Digital input (24VDC) CC-TDIL01 9 CC-TDIL11 12 32
Universal Input Output (UIO) CC-TUIO31 9 CC-TUIO41 12 32
Installation and safety regulations
1. Installation requirements
Module positioning: IOM needs to be plugged into the corresponding IOTA, which is fixed to the 24VDC bus power supply rail of the cabinet with screws
Wiring specifications:
Wire specifications: It is recommended to use copper wire with a rated temperature of 75 ℃, and a single terminal can support 2 wires of the same specification or 1 maximum 12AWG wire
Stripping length: Unified at 0.25 inches (7mm), excessive length may result in exposed wires and pose a risk of electric shock
Noise protection: Ensure that the module installation screws are tightened and grounded according to specifications; The noise reduction gasket on the right side of the module (both sides of the power module) should be in contact with adjacent modules/cabinets to avoid electromagnetic noise interference
2. Installation requirements for hazardous areas
For Class I Zone 2 hazardous environments, the following regulations must be followed:
Only applicable to Class I Zone 2 A/B/C/D hazardous areas or non hazardous areas, and cannot be used for other hazardous level scenarios
It is prohibited to replace module components, otherwise it may damage the explosion-proof applicability
Before power outage or confirming the safety of the area, it is forbidden to disconnect the equipment connection to avoid the risk of explosion

Ordering Information (Core Components)
In addition to the IOM module, matching IOTA and fan components need to be selected based on the number of cabinet slots and power supply type. Some key models are as follows:
Product Description Model
16 channel with HART analog input module CC-PAIH01
32 channel 24VDC digital input module CC-PDIL01
32 channel 24VDC bus type digital output module CC-PDOB01
32 channel universal input/output module CC-PUIO31
17 slot cabinet 120VAC fan component IC697ACC721
17 slot cabinet 24VDC fan component IC697ACC744
9-slot cabinet 240VAC fan component IC697ACC624
Supplementary explanation
Environmental specifications: The temperature and humidity tolerance, vibration and impact and other environmental parameters of the module should refer to the "Series-C Platform Specifications" and technical document EP03-520-xxx
Compliance certification: FCC, EU directives and other compliance information, please refer to Appendix A of the "Expert RX7i Installation Manual" (GFK-2223)