Communication interference (poor grounding of RS485 or parallel wiring with power cables)
Power supply voltage fluctuation (unstable ship power grid)
Troubleshooting steps:
Install a 10 L gas storage tank and pressure regulator valve at the inlet of the gas source, and observe whether the fluctuation disappears.
Use an oscilloscope or multimeter to measure whether there is a common mode voltage (ideal value<2 V) between the communication line and ground. If exceeded, check if the shielding layer is grounded at both ends (should be changed to single ended grounding).
The AC input voltage of TN3801 should be measured within ± 10% of the rated value. If there is a large fluctuation, an online UPS can be added.
4.3 Fault phenomenon three: The reading of a single channel is significantly high (exceeding the actual liquid level)
Possible reasons:
The bubble tube is damaged or detached, causing gas to leak from the middle and increasing back pressure.
Density parameter setting error (the liquid density value stored in the microcontroller is too high).
Zero drift of back pressure sensor.
Troubleshooting steps:
Turn off the gas source of the channel, open the inspection port on the top of the cabinet, remove the bubble tube, and visually inspect for cracks, bends, or detachment.
Use a standard pressure source (such as a piston pressure gauge) to directly input simulated pressure to the back pressure sensor of the channel, and compare the displayed liquid level value. If the deviation exceeds 0.5%, perform the calibration procedure (see maintenance manual MM5015).
Check if the liquid density value in the TN3801 configuration parameters matches the current cabin medium (e.g. fuel density 0.86 kg/L, seawater 1.025 kg/L).
4.4 Fault phenomenon four: Communication interruption (Modbus master station reading timeout)
Phenomenon: The upper computer cannot read any channel data or returns an error code when reading.
Troubleshooting steps:
Physical layer inspection
Confirm that the communication cable is connected to the correct RS485/422 terminal (usually A, B, GND).
Check the terminal resistance: A 120 Ω resistor should be connected at both ends of the bus (TN3801 and the main station). If TN3801 is an end device, has the terminal resistor been enabled internally (refer to manual MT5015 jumper settings).
Measure the resistance between A and B, which should be around 60 Ω (two 120 Ω parallel connections).
Protocol parameter matching
Use the PC serial port debugging assistant to set the same baud rate (default 9600), data bits (8), stop bit (1), and no checksum as TN3801. Send Modbus read hold register command (function code 03) and check if there is a correct frame response.
Common error: The main station address does not match the station address set by TN3801. TN3801 corresponds to a Modbus address for each channel, but typically the device itself has a global address. Refer to the manual for confirmation.
Redundant port switching test
TN3801 has two redundant RS485 ports (usually labeled as COM1 and COM2). If COM1 does not respond, switch the main station cable to COM2 and confirm that the main station program has also been switched accordingly. If COM2 is working properly, it indicates that COM1 hardware is damaged. COM2 can be temporarily used and repairs can be arranged.
4.5 Fault phenomenon five: The liquid level reading is normal, but there is no signal output from 4-20 mA
Possible reasons:
Analog output not activated or channel configuration error
External load resistance is too high or short circuited
Open circuit output circuit
troubleshoot
Measure the AO+and AO - terminals of TN3801 directly with a multimeter in mA mode, which should normally be between 4-20 mA as the liquid level changes. If there is no current, check if the internal jumper is set to "active output" mode.
If there is current but the external device displays zero, please check the input impedance of the external receiving device (should be ≤ 500 Ω).
Maintenance and Calibration Plan
To ensure the long-term stable operation of TN3801, it is recommended to perform maintenance tasks according to the following cycle:
5.1 Monthly Inspection
Air path filter: Observe the water cup of the integrated filtration unit, and if the accumulated water exceeds 1/3, discharge it in a timely manner.
Gas supply pressure: Record whether the inlet pressure is stable at 6-10 bar.
Alarm log: Read the system self-test alarm through the display unit or Modbus. If there is a record of "Low Air Pressure" or "Channel Failure", handle it in a timely manner.
5.2 Quarterly maintenance
Accuracy verification: Select 1-2 representative cabinets and compare the readings of TN3801 using a manual ruler (such as a depth gauge). If the deviation exceeds ± 0.5% FS, perform online two-point calibration.
Bubble tube inspection: For tanks with scaling risks (such as sewage tanks and crude oil tanks), check whether the bubble tube opening is blocked and remove sediment.
Tightening of wiring terminals: In vibration environments, electrical terminals may become loose. Use a torque screwdriver to tighten them again.
5.3 Annual in-depth maintenance