4. Input/output configuration and control mode
MLS supports a wide range of sensors and output types to meet various industrial needs.
Analog input configuration:
Thermocouple: directly connected to J, K, T, S, R, B types. Non grounded thermocouples (T/C leads isolated from protective sleeves) must be used. For specific temperature ranges (such as J-type below 400 ° F), an offset can be set for calibration.
RTD: It is recommended to use a three wire 100 Ω platinum resistor (DIN 43760 curve). Scaling resistors (such as RTD1 configuration: RA=5.49K Ω, RB=11.0K Ω, RC=11.0K Ω) need to be installed on the AIM terminal board.
Linear input (pressure, flow rate, etc.): The input signal is mapped to engineering units using two-point scaling method. For example, inputting 0-10mA corresponds to 0-100 PSI, which needs to be divided to the range of -10 to+60mV through an external resistor, and the corresponding PV value and instrument reading need to be entered in the Setup menu.
Control output type:
TP (time ratio): Simulate analog output by changing the on-off time ratio. Need to set cycle time (1-255 seconds), suitable for driving SSR.
DZC (Distributed Zero Crossing): It determines on/off at the zero crossing point of each AC line cycle, with a very high switching frequency, suitable for fast heating loads.
SDAC (Serial DAC): With optional digital to analog converters, it provides high-precision analog current (4-20mA) or voltage output.
Alarm function: Each circuit can independently set high/low process alarms and deviation alarms. An alarm can activate a single digital output or a configured output.
5. PID control parameter tuning and tuning
The correct PID parameters are the key to achieving stable control.
Control mode: Supports on/off, proportional, proportional integral (PI), and proportional integral derivative (PID). For high-precision requirements, PID mode is usually used.
Parameter starting value:
Proportional Bands (PB): typically set at 5% -10% of the set point. For set points below 1000 ° F, set to 10%; Above 1000 ° F, set to 5%.
Integral time (TI): The recommended starting value is 60 seconds per repetition.
Differential Time (TD): The recommended starting value is 15% of TI. For example, if TI=60s, then TD=9s.
Auto tuning: Select "TUNE" mode in the Setup menu. The controller will automatically make the circuit output 100%, calculate the PID parameters, and automatically switch back to automatic mode.
6. Communication interface configuration (RS-232/RS-485)
MLS supports standard serial communication and can be networked with computers or PLCs.
Interface type: configured as RS-232 (point-to-point, single unit) or RS-485 (multi-point, up to 32 units) through internal jumpers.
RS-485 Connection Specification:
Shielded twisted pair cables must be used.
200 Ω terminal resistors need to be connected to the farthest end of the communication line (computer end) and the farthest controller end (last station) respectively.
If the common mode voltage exceeds 7V, the 5th wire must be used as the common ground connection. Otherwise, a shielding layer can be used (note: the shielding layer at the MLS terminal is not grounded, only grounded at the computer terminal).
Parameter settings: Set the controller address (1-32), baud rate (2400 or 9600), and protocol in the Setup Global Parameters menu.
7. Troubleshooting and System Testing
After system deployment, strict testing is required.
Power test: Confirm that the PM's+V voltage is normal and the AIM's+5V power supply is normal.
Communication test: Confirm that communication between AIM and PM is normal (when AIM communication fails, the controller will switch to manual mode and trigger a global alarm).
I/O test: Use the Manual I/O Test menu to forcibly turn on/off the digital output, and measure the voltage with a multimeter (low level=0V, high level ≈ 3.75-5.5V); Short circuit the digital input and check if the screen status has changed.
Common faults:
Display blank: Check if the power supply is working properly.
CPU reset: It may be caused by RFI interference. Check if an RC buffer network is installed on the external relay line.
AIM communication failure: Check the communication cable connection and attempt to perform a 'No Key Reset' (press and hold the No key to power on).
8. Conclusion
The Watlow MLS controller provides a solid platform for complex industrial furnace temperature control with its modular hardware architecture, powerful PID algorithm library, and flexible I/O configuration capabilities. Following the installation specifications (especially power wiring updates, RC buffering anti-interference) and PID tuning principles in this guide can significantly improve the stability and control accuracy of the system. For engineers seeking high reliability and scalability multi loop temperature control solutions, mastering the deployment and configuration skills of MLS is crucial.
