ABB CP450 a Human Machine Interface
ABB CP450 a Human Machine Interface
INTRODUCTION
CP450 is a Human Machine Interface (HMI) with a 10.4" TFT Liquid Crystal Display, and is water- and dust-resistant according to IP65/NEMA 4X (indoor use only). CP450 is CE-marked and meets your need to be highly transient-resistant while in operation. Also, its compact design makes connections with other machinery more flexible, thus achieving the optimal performance of your machines.
General
– Only qualified personnel may install or operate the operator terminal.
– The operator terminal must be installed according to the installation instructions.
– The operator terminal is designed for stationary installation on a plane surface, where the following conditions are fulfilled:
• no high explosive risks
• no strong magnetic fields
• no direct sunlight
• no large, sudden temperature changes
• for use in Pollution Degree 2 Environment
• for use on the flat surface of Types 1 and 4X (indoor use only) enclosures
– Never allow fluids, metal filings or wiring debris to enter any openings in the operator terminal. This may cause fire or electrical shock.
– The operator terminal fulfills the requirements of article 4 of EMC directive 2004/108/EC.
– Storing the operator terminal where the temperature is lower/higher than recommended in this manual can cause the LCD display liquid to congeal/ become isotopic.
– The LCD display liquid contains a powerful irritant. In case of skin contact, wash immediately with plenty of water. In case of eye contact, hold the eye open, flush with plenty of water and get medical attention.
– The supplier is not responsible for modified, altered or reconstructed equipment.
– Use only parts and accessories manufactured according to specifications of the supplier.
– Peripheral equipment must be appropriate for the application and location.
– The figures in this manual serves an illustrative purpose. Because of the many variables associated with any particular installation, the supplier cannot assume responsibility for actual use based on the figures.
– The supplier neither guarantees that the operator terminal is suitable for your particular application, nor assumes responsibility for your product design, installation or operation.
Power source
– The operator terminal is equipped with a 24 V DC input. Supply power other than 24 V DC ± 15% will severely damage the operator terminal. Thus, check the power supply supporting the DC power regularly.
Grounding
– Without grounding, the operator terminal may be severely affected by excess noise. Make sure that the grounding is done properly from the power connector at the rear side of the operator terminal. When power is connected, make sure that the wire is grounded. – Use a cable of at least 2 mm2 (AWG 14) to ground the operator terminal. Ground resistance must be less than 100 Ω (class3). Note that the ground cable must not be connected to the same ground point as the power circuit.
Service and Maintenance
– Only qualified personnel should carry out repairs.
– The agreed warranty applies.
– Before carrying out any cleaning or maintenance operations, disconnect the equipment from the electrical supply.
– Clean the display and surrounding front cover with a soft cloth and mild detergent.
– Replacing the battery incorrectly may result in explosion. Only use batteries recommended by the supplier.
Product Specifications
Cut-out dimensions:286.0 x 211.0 mm
Weight:1.9 kg
USB Device:1 port
CPU:32-bit RISC
Data/Recipe:512 KB