ABB REM545 Machine Terminals
ABB REM545 Machine Terminals
DESCRIPTION
The REM 543 and REM 545 rotating machine terminals are designed to be used as an integrated main protection system of generator and generator-transformer units in small and medium-power diesel, hydroelectric and steam power plants, etc. The protection of large and/or important MV synchronous and asynchronous motors used e.g. in pumps, fans, mills and crushers during start-up and normal run forms another application area. The REM 54_ machine terminals as integrated packages make possible compact marine environment solutions for unit protection, too.
FEATURES
• Integrated machine terminals for the protection, control, measurement and supervision of small and medium size generators, synchronous motors and large asynchronous motors.
• Voltage and current measurement via conventional measuring transformers or current sensors and voltage dividers.
• Fixed man-machine interface including a large graphic display, or an external display module for flexible swichgear installation.
• Extended functionality including protection, control, measurement, condition monitoring and communication.
• Non-directional/directional overcurrent/earth-fault protection functions, over- /undervoltage protection functions and special functions for the protection of motors and generators, e.g. voltage controlled overcurrent protection, differential protection with several principles, underexcitation protection, underimpedance protection (line back-up prot.), thermal overload protection, protection against unbalanced load, abnormal frequency protection, reverse or low-forward power protection and start-up supervision for motors.
• Control functions including local and remote control of switching objects with synchro-check, status indication of the switching objects and interlockings on bay and station level.
• Measurement of phase currents, phase-tophase and phase-to-neutral voltages, neutral current and residual voltage, frequency, power factor, active and reactive power and energy.
• Optional RTD/mA I/O-module for stator winding, bearing and ambient temperature monitoring. Analog mA outputs for interfacing with process control system.
• Condition monitoring including circuitbreaker condition monitoring, trip circuit supervision and internal self-supervision of the machine terminal.
• Communication over three communication interfaces: one for local communication with a PC and the others for remote communication with a substation control system or with a substation monitoring system.
• Part of the ABB’s Distribution Automation system.
DESIGN
The machine terminals REM 543 and REM 545 differ from each other in the number of digital inputs and outputs available. Please refer to the section “Ordering” for more details. The REM 54_ machine terminals incorporate a wide range of functions:
• Protection functions
• Measurement functions
• Control functions
• Condition monitoring functions
• General functions
• Communication functions
• Standard functions
Protection functions
Protection is one of the most important functions of the REM 54_ machine terminal. The protection function blocks are independent of each other and have their own setting groups, data recording, etc. Typical current-based protection functions (e.g. overcurrent) can use either Rogowski coil or conventional current transformer measurement. Correspondingly, voltage-based functions (e.g. overvoltage) use either voltage dividers or voltage transformers.
For further information about functionality levels and the protection functions included in them, refer to the table “Functionality levels, protection functions” in section “Ordering”.
Measurement functions
The measurement functions include threephase currents, neutral current, three-phase voltages, residual voltage, frequency, active and reactive power and power factor. An optional RTD/analogue module can be used for measuring stator winding, bearing, and ambient temperatures.
Disturbance recorder
The transient disturbance recorder is able to record 16 current or voltage waveforms and 16 logic digital signals. The sampling frequency of the analogue inputs is 2 kHz at the rated frequency of 50 Hz and 2.4 kHz at the rated frequency of 60 Hz.The user can set the length of a recording within a range determined by the number of analogue inputs used. The number of recordings depends on the sampling frequency, length of recordings and number of analogue inputs.
Control functions
The control functions are used to indicate the status of switching devices, i.e. circuit breakers and disconnectors, and to execute open and close commands for controllable switching devices of the switchgear. Furthermore, control functions provide on/off switching objects for control logic purposes and miscellaneous objects for data monitoring, etc.