ABB C1627 Silicon Controlled Modules
ABB C1627 Silicon Controlled Modules
Here is the English introduction of ABB C1627 Silicon Controlled Modules:
The ABB C1627 is a silicon controlled module with the following characteristics3:
Current Output
The factory setting for the current output is 4 - 20 mA. For devices without explosion protection or operating in Zone 2/Div. 2, the signal can be configured in "active" or "passive" mode, and the current setting is noted in the order confirmation. For devices operating in Zone 1/Div. 1, the current output cannot be reconfigured later, and the required configuration (active/passive) must be specified when placing the order.
Power Supply
If the signal is configured in "active" mode, no external power supply is needed for the current output. If it is configured in "passive" mode, an external power supply for the current output is required, similar to pressure and temperature transmitters.
Bus Address
For units with PROFIBUS PA, the bus address needs to be checked or configured before start-up. If the customer doesn't provide bus address information, the unit will be shipped with its bus address set to "126". During start-up, the address should be reset to a number within the valid range of 0 - 125. The selected address can only appear once in the segment. The address can be set locally on the unit via the DIP switches on the digital board, using system tools, or via a PROFIBUS DP master class 2 such as Asset Vision Basic. The factory setting for DIP switch 8 is OFF, meaning the address is set using the fieldbus. The front cover can be unscrewed to change the settings, and it's also possible to set the address via the menu using the keys on the display board.
Interface and Signal Standards
The PROFIBUS PA interface complies with Profile 3.01, that is, the fieldbus standard PROFIBUS (EN 50170, alias DIN 19245(PRO91)). The transmitter transmission signal is designed according to IEC 61158 - 2. The manufacturer-specific PROFIBUS PA ID number is 0x3430, and the unit can also be operated with the PROFIBUS standard ID numbers 0x9700 or 0x9740.
Instructions and warnings related to the operation of the product:
The following specifications must be strictly observed:
l The technical specifications and typical applications of the product system must be strictly observed.
l PERSONNEL TRAINING: Only trained personnel may install, operate, maintain or repair the product system. These personnel must be instructed on the
Hazardous area conditions must be instructed and explained to these personnel.
l Unauthorised modifications: No modifications or structural changes may be made to the product system.
l Maintenance Responsibility: It must be ensured that the product system is only used under appropriate conditions and in a condition that is fully fit for purpose.
l Working environment: The user must fulfil the specified environmental conditions:
Safety regulations
The following safety regulations must be fully observed when (maintenance) work is carried out on the product system:
1 Disconnect completely.
2 Secure to prevent reconnection.
3 Confirm that the installation has been completed.
4 Perform grounding and short-circuiting.
email:1583694102@qq.com