GE IC660BBA025 Current-source Analog Output Blocks
GE IC660BBA025 Current-source Analog Output Blocks
Description
Current-source Analog Output Blocks have 6 output circuits for devices that accept 4 to 20mA signals. Outputs 5 and 6 can also be used for voltage applications. Two Current-source Analog Output blocks are available: 115 VAC Current-source Analog Output Block (IC66*BBA105) 24/48 VDC Current-source Analog Output Block (IC66*BBA025) These blocks are identical except for the power supply
Features
Block features include:
Six 4-to-20 mA analog output circuits
No calibration required for operation
Software configurable
Advanced diagnostics
Dedicated Bus Switching Module control
These blocks provide power to all circuits; no separate power is required for 4-20mA signals. Each output provides power and control of a 4-to-20mA current loop. This power is isolated from the rest of the block. The outputs and BSM circuitry are electrically common. Output accuracy is 0.15% at 25°C. Output resolution is 6µA.
The block has a dedicated digital output that can be used to drive a Bus Switching Module (IC66*BSM012 only). The outputs and BSM circuitry are electrically common.
Configurable features of these blocks include:
Output Hold Last State or default
Circuit scaling to engineering units values
Output feedback checking and feedback time
CPU Redundancy
Fault reporting can be enabled or disabled circuit-by-circuit. These blocks automatically perform the following diagnostic checks:
Output Overrange and Underrange
Output Feedback
Installation Instructions
Carefully inspect all shipping containers for damage. If any equipment is damaged, notify the delivery service immediately. Save the damaged shipping container for inspection by the delivery service. After unpacking the equipment, record all serial numbers. Save the shipping containers and packing material in case it is necessary to transport or ship any part of the system.
Block Mounting
Genius I/O blocks are considered "open equipment" and therefore must be installed within a protective enclosure. They should be located in an area that is clean and free of airborne contaminants. There should be adequate cooling airflow. The block can be mounted right side up, or upside down. Leave at least 2 inches of space between blocks. Mount the block by drilling two screw or bolt holes for 8-32 hardware. Position the block so that the notches in the upper and lower flanges line up with the mounting holes. Mount the block using 8-32 screws. Use star washers to provide ground integrity.
Output Specifications
Output accuracy at 25° C:0.15% of full scale reading
Output resolution:6µA
Output update frequency:25ms
Range:< 4mA to 20mA
Overrange capacity:0mA to 24mA
Output diagnostics:Underrange, Overrange, Feedback error
Thermal drift (from 25°C):35 PPM per degree C typical
Environmental Specifications
Operating temperature:0° C to +60° C (+32° to +140° F)
Storage temperature:-40° to +100° C (-40° to +212° F)
Humidity:5% to 95% (non-condensing)
email:1583694102@qq.com
wang@kongjiangauto.com