GE IC695ALG600 PACSystems* RX3i
GE IC695ALG600 PACSystems* RX3i
The PACSystems* Universal Analog Input module IC695ALG600 provides eight general purpose input channels and two Cold Junction Compensation (CJC) channels. Inputs are divided into two equal groups of four. Channels can be individually-configured using the Machine Edition software for:
▪ Any combination of up to 8 channels of voltage, current, thermocouple, RTD, and resistance inputs.
▪ Thermocouple Inputs: B, C, E, J, K, N, R, S, T
▪ RTD Inputs: PT 385 / 3916, N 618 / 672, NiFe 518, CU 426
▪ Resistance Inputs: 0 to 250 / 500 / 1000 / 2000 / 3000 / 4000 Ohms
▪ Current: 0–20 mA, 4–20 mA, +20 mA
▪ Voltage: +50mV, +150 mV, 0–5 V, 1–5 V, 0–10 V, +10V
This module must be located in an RX3i Universal Backplane. An RX3i CPU with firmware version 2.80 (Build ID 43A1) or later. Machine Edition 5.0 SP1A LD-PLC Hotfix 1 ) or later is required for configuration.
This module can be used with a Box-style (IC694TBB032), Extended Box-style (IC694TBB132), Spring-style (IC694TBS032), or Extended Spring-style (IC694TBS132)) Terminal Block. Extended terminal blocks provide the extra shroud depth needed for shielded wiring. See the PACSystems RX3i System Manual, GFK-2314 revision B or later for more information about Terminal Blocks. Terminal Blocks are ordered separately.
Module Features
▪ Module supports hot insertion/extraction
▪ Terminal Block insertion or removal detection
▪ Module Status, Field Status, and TB LEDs
▪ Module meets CE, UL/CUL 508 and 1604, and ATEX requirements
▪ Flash memory for future upgrades
▪ Autocalibration at power-up
▪ Completely software-configurable, no module jumpers to set
▪ Six hardware analog-to-digital filter frequencies, individually-selectable by channel
▪ Rapid channel acquisition times based on filter frequency
▪ On-board error-checking
▪ Open-circuit detection for most input types
▪ Short-circuit detection for RTDs.
▪ User-defined scaling
▪ Module fault reporting
▪ Overrange, underrange, high alarm, low alarm, high-high alarm, low-low alarm and calibration fault alarm detection and reporting on a per-channel basis.
▪ Positive and negative Rate of Change Alarms
▪ Configurable interrupts for channel alarms and faults
▪ Supports diagnostic point fault contacts in the logic program.
▪ CJC compensation on terminal block
▪ Temperature in Celsius or Fahrenheit
Specifications
Backplane Power Requirements:400 mA maximum @ 5V 350 mA maximum @ 3.3V
Power Dissipation within Module Thermal Dissipation:5.4 watts maximum
Max Overvoltage:+/-14.5VDC continuous
Max Overcurrent:28mA continuous
Gain Drift with Temperature:50 ppm/°C typical (90 ppm/°C maximum)