GE IS200TBAIH2C Analog Input/Output Terminal Board
GE IS200TBAIH2C Analog Input/Output Terminal Board
Part Number IS200TBAIH2C Manufacturer General Electric Country of Manufacture As Per GE Manufacturing Policy Series Mark VI/VIe Function Module Availability In StockIS200TBAIH2C is an Analog Input/Output Terminal Board manufactured and designed by General Electric as part of the Mark VI Series used in GE Speedtronic Gas Turbine Control Systems. The Analog Input/Output (TBAI) terminal board supports 10 analog inputs and 2 outputs.
The 10 analog inputs accommodate two-wire, three-wire, four-wire, or externally powered transmitters. The analog outputs can be set up for 0-20 mA or 0- 200 mA current. Inputs and outputs have noise suppression circuitry to protect against surge and high-frequency noise. TBAI has three DC-37 pin connectors provided on TBAI for connection to the I/O processors. Simplex applications are supported using a single connector (JR1). TMR applications are supported using all three connectors. In TMR applications, the input signals are fanned to the three connectors for the R, S, and T controls.
TMR outputs combine the current of the three connected output drivers and determine the total current with a measuring shunt. TBAI then presents the total current signal to the I/O processors for regulation to the commanded setpoint. INSTALLATION: Connect the input and output wires directly to two I/O terminal blocks mounted on the terminal board. Each block is held down with two screws and has 24 terminals accepting up to #12 AWG wires. A shield terminal attachment point is located adjacent to each terminal block. TBAI can accommodate the following analog I/O types: Analog input, two-wire transmitter Analog input, three-wire transmitter Analog input, four-wire transmitter Analog input, externally powered transmitter Analog input, voltage 5 V, 10 V dc Analog output, 0-20 mA Analog output, 0-200 mA OPERATION: TBAI provides a 24 V DC power source for all the transducers.
The inputs can be configured as current or voltage inputs using jumpers (J#A and J#B). One of the two analog output circuits is 4-20 mA and the other can be configured as 4-20 mA or 0- 200 mA. The following table displays the analog I/O capacity of TBAI. Each 24 V dc power output is rated to deliver 21 mA continuously and is protected against operation into a short circuit. Transmitters/transducers can be powered by the 24 V dc source in the control system, or can be independently powered. Jumper JO selects the type of current output. Diagnostics monitor each output and a suicide relay in the I/O controller disconnects the corresponding output if a fault cannot be cleared by a command from the processor.
SPECIFICATIONS:
Part Number: IS200TBAIH2C
Manufacturer: General Electric
Series: Mark VI
Function: Analog Input/Output Terminal Board
Operating temperature: -30 to 65 degrees Celsius
Number of Channels: 12
Output load: 500 Ohm
Size: 10.16 cm wide x 33.02 cm
Repair: 3-5 Days
Availability: In Stock
Country of Manufacture: United States (USA)
Manual: GEH-6421M
The IO module has the following main functions
Input Function
The IO module can receive input signals sent by external devices and convert them into digital or analogue signals for use by the computer system or control system. These input signals can come from a variety of sensors, such as temperature sensors, pressure sensors, photosensitive sensors and so on. By receiving and parsing these input signals, the system can monitor and control the external environment in real time.
Output Functions
The IO module is capable of converting the output signals generated by a computer system or control system into the form required by an external device. These output signals are typically used to control actuators such as motors, valves, lights, etc. By sending appropriate output signals to external devices, the system enables control and operation of the external environment.
Data Acquisition and Processing
The IO module is capable of acquiring data from external devices and transferring it to a computer system or control system for further processing. This enables the system to acquire environmental data, status information and user inputs in real time and make appropriate decisions or perform specific tasks based on these data.
Communication Interfaces
IO modules are usually equipped with different types of communication interfaces, such as serial interfaces (RS232, RS485), Ethernet interfaces, CAN bus interfaces, and so on. These interfaces enable IO modules to exchange data and communicate efficiently with computer systems or other external devices.